Инструкция на Сплит-кондиционеры универсальные Fujitsu
AB*A(F) 18, 24 LAT (внутренние блоки). Напольно-подпотолочные кондиционеры. Техническое руководство.
Смотрите также: Руководство по эксплуатации →
Загружаем документ…
Текст инструкции
-
INDOOR UNIT
-
MODEL
INDOOR UNIT OUTDOOR UNIT AB A18LAT AB F18LAT AO A18LACL AO A18LALL AO B18LACL AO B18LALL AB A24LAT AB F24LAT AO A24LACL AO A24LALL AO B24LACL AO B24LALL FEATURES Energy saving rank A (AO A18LACL, AO A18LALL, AO A24LACL, AO A24LALL connection model) European energy ranking rank A achieved by all…
-
Filter sign operating time (Standard/long/short/no display)
Filter sign display time interval and filter sign no display can be selected. Ceiling height (standard/high ceiling) Air conditioner operation capacity (air flow) switching is possible as response to height of installation ceiling. Cooling room temperature correction (Standard/low control) Air…
-
2. REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER FEATURES Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. Four kinds of timers. Easy operation. Easy to change transmission code (4 patterns) by button operation. Simple function setting Setting of the air conditioner selection function is performed by…
-
FUNCTIONS
1 MODE button 2 Economy button 3 Set temp. button ( / ) Set remote controller custom code buttons 16 Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). /Start / end R.C. custom code change. (Max 4 types) Sets the indoor temp./ Sets R.C. custom code. Filter reset button 5 Sleep button 6 Fan…
-
FLOOR CEILING MODEL
Type INVERTER HEATPUMP Model name AB A18LAT, AB F18LAT AB A24LAT, AB F24LAT AO A18LACL, AO A18LALL AO A24LACL, AO A24LALL Power source 230V Available voltage range European energy label Rated Cooling Min. - Max. Capacity Rated Heating Input power Heating Cooling Current Heating A Heating A A kW 5.20…
-
Model name
AB A18LAT, AB F18LAT AB A24LAT, AB F24LAT AO B18LACL, AO B18LALL AO B24LACL, AO B24LALL Power source 230V Available voltage range European energy label Rated Cooling Min. - Max. Capacity Rated Heating Input power Heating 50Hz Cooling B Heating B B B kW 5.20 7.10 BTU/h 17700 24200 kW 0.90-5.70…
-
(Unit : mm)
6 Rear view Side view 2 Bottom view 3 1 Refrigerant piping flare connection (Gas) 2 Refrigerant piping flare connection (Liquid) 3 Drain piping connection 4 Knock out hole for drain piping 5 Knock out hole for refrigerant piping 6 Hole for lifting bolt (Use M10 screw bolt) Wall bracket Side of set…
-
(Unit : mm)
Left Right 300 or more 300 or more Ceiling Left Right Indoor unit 150 or more 300 or more 1000 or more Ceiling 2300 or more FLOOR / CEILING TYPE AB A18-24L MOUNTING POSITION 20 or more Obstruction Floor - (01 - 08) -
-
6-1. COOLING CAPACITY
-
This table is created using the maximum capacity
-
7. FAN PERFORMANCE
7-1. AIR VELOCITY DISTRIBUTION MODEL : AB A18L, AB F18L (FLOOR CONSOLE) 2 Unit : m/s (m) 1 0 0.5 1 2 0.25 1 2 TOP VIEW VERTICAL FLAP : Downward HORIZONTAL FLAP : Center (m) Right 4 3 0.25 2 2 0.5 0.5 2 3 0.25 Unit : m/s (m) 5 8 TOP VIEW VERTICAL FLAP : Downward HORIZONTAL FLAP : Right & Left Left…
-
(m)
0.5 1 0.25 1 2 TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Center (m) Unit : m/s (m) 0.25 3 0.5 0.5 3 0.25 TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Right & Left (m) 0 Unit : m/s (m) 0.5 (m) Unit : m/s (m) 3 SIDE VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Center 0.25 (m) 2 2 0.25…
-
(m)
1 0 0.5 1 2 0.25 1 2 TOP VIEW VERTICAL FLAP : Downward HORIZONTAL FLAP : Center (m) Unit : m/s (m) 5 9 Right 4 3 0.25 2 2 0.5 0.5 2 3 0.25 4 5 TOP VIEW VERTICAL FLAP : Downward HORIZONTAL FLAP : Right & Left Left (m) 0 Unit : m/s (m) 0.25 (m) Unit : m/s (m) 4 SIDE VIEW VERTICAL FLAP : Downward…
-
(m)
0.5 1 0.25 1 2 TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Center (m) 0.5 0.5 3 TOP VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Right & Left 0.25 (m) Unit : m/s (m) 0.25 Unit : m/s (m) (m) Unit : m/s (m) 3 SIDE VIEW VERTICAL FLAP : Upward HORIZONTAL FLAP : Center 0.25 0.5 0.25 0.25 1 0 SIDE…
-
7-2. AIR FLOW
-
8-1. NOISE LEVEL CURVE
-
8-2. SOUND LEVEL CHECK POINT
-
AB A18L
AB F18L Model Name Power Supply Voltage V 230 Frequency Hz 50 Max Operating Current *1)Wiring Spec. AB A24L AB F24L A 0.5 0.7 Circuit breaker A 0.6 0.9 Connection Cable mm 2 1.5 - 2.5 1.5 - 2.5 Limited wiring length m 26 31 *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical…
-
10. SAFETY DEVICE
-
Exterior
Parts name Model No. Wired remote controller UTB- UD - (01 - 24) - Summary Unit control is performed by wired remote controller FLOOR / CEILING TYPE AB A18-24L FLOOR / CEILING TYPE AB A18-24L 11. OPTIONAL PARTS
-
2. SINGLE TYPE
-
1. SPECIFICATIONS
INVERTER HEATPUMP AO AO OUTDOOR UNIT AO A18-24L Model name A18LACL A18LALL AO AO Power source 230V Available voltage range Fan Airflow rate Cooling Heating Motor output Cooling Heating Dimensions (H × W × D) Heat exchanger type 7.7 10.0 3 2000 2470 1910 2470 m /h Propeller × 1 W dB(A) mm Fin pitch…
-
2. DIMENSIONS
MODELS : AO A18L, AO A24L OUTDOOR UNIT AO A18-24L OUTDOOR UNIT AO A18-24L (Unit : mm) Top view Front view AO A18L AO A24L Side view Air flow Bottom view MOUNTING POSITION When there are obstacles at the back, side(s), and top. When there are obstacles at the back, side with the installation of more…
-
AO A18-24L
-
4. WIRING DIAGRAMS
-
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE Pipe length (m) COOLING 1 Indoor unit is upper than outdoor unit. 5 7.5 - - - 0.953 0.950 0.947 10 - - 0.983 0.968 0.966 0.962 7.5 - 0.988 0.987 0.972 0.970 0.966 5 0.992 0.992 0.991 0.976 0.974 0.970 0 1.000 1.000 0.999 0.984 0.982 0.978 -5 1.000 1.000 0.999 0.984 0.982 0.978…
-
Pipe length (m)
COOLING 1 Indoor unit is upper than outdoor unit. Height difference H (m) 2 Indoor unit is under than outdoor unit 5 7.5 - - - - 0.963 0.961 0.959 10 - - 0.984 0.981 0.979 0.977 0.975 7.5 - 0.988 0.988 0.985 0.983 0.981 0.979 5 0.992 0.992 0.992 0.989 0.987 0.985 0.983 0 1.000 1.000 1.000 0.997…
-
6. ADDITIONAL CHARGE CALCULATION
-
7. AIR FLOW
-
8. OPERATION NOISE
-
AO A18-24L
OUTDOOR UNIT AO A18-24L 8-2. SOUND LEVEL CHECK POINT - (02 - 10) -
-
9. ELECTRIC CHARACTERISTICS
Power Supply AO A18L AO Voltage V 230 Frequency Hz 50 A24L Max Operating Current A 15.0 16.2 Starting Current A 7.7 10.0 Main Fuse (Circuit breaker) Current A 20 20 Power Cable mm 2 *2)Limited wiring length m *1) Wiring Spec. 3.5 - 4.5 24 22 *1) Wiring Spec. Selected Sample (Selected based on Japan…
-
10. SAFETY DEVICES
Model AO A18L 5A 250V 15A 250V Current fuse (MAIN PRINTED CIRCUIT BOARD) Fan motor protection Compressor protection A24L 20A 250V Current fuse (NEAR THE TERMINAL) Circuit protection AO OUTDOOR UNIT AO A18-24L OUTDOOR UNIT AO A18-24L Protection form Thermal protection program 3.15A 250V OFF:100 ON:95…
-
2. SINGLE TYPE
-
1. SPECIFICATIONS
INVERTER HEATPUMP OUTDOOR UNIT AOB18-24L Model name AO B18LACL AO B24LACL AO B18LALL AO B24LALL 230V ~ 50Hz Power source 198-264V ~ 50Hz Available voltage range Starting current A Airflow rate Fan Cooling Heating 3 m /h Sound pressure level Cooling Heating Dimensions (H × W × D) Heat exchanger type…
-
2. DIMENSIONS
-
AOB18-24L
-
4. WIRING DIAGRAMS
-
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DIFFERENCE Pipe length (m) OUTDOOR UNIT AOB18-24L COOLING 1 Indoor unit is upper than outdoor unit. 5 7.5 - - - 0.953 0.950 0.947 10 - - 0.983 0.968 0.966 0.962 7.5 - 0.988 0.987 0.972 0.970 0.966 5 0.992 0.992 0.991 0.976 0.974 0.970 0 1.000 1.000 0.999 0.984 0.982 0.978 -5 1.000 1.000…
-
Pipe length (m)
OUTDOOR UNIT AOB18-24L COOLING 1 Indoor unit is upper than outdoor unit. Height difference H (m) 2 Indoor unit is under than outdoor unit 5 7.5 - - - - 0.963 0.961 0.959 10 - - 0.984 0.981 0.979 0.977 0.975 7.5 - 0.988 0.988 0.985 0.983 0.981 0.979 5 0.992 0.992 0.992 0.989 0.987 0.985 0.983 0…
-
6. ADDITIONAL CHARGE CALCULATION
-
7. AIR FLOW
-
8. OPERATION NOISE
-
AOB18-24L
OUTDOOR UNIT AOB18-24L 8-2. SOUND LEVEL CHECK POINT - (02 - 10) -
-
9. ELECTRIC CHARACTERISTICS
Voltage Frequency Max. operating current Starting current Main fuse (Circuit breaker) current *1) Wiring spec. Power cable *2)Limited wiring length Power supply OUTDOOR UNIT AOB18-24L AO B18L AO B24L 230 ~ 50 V Hz A A A 15.0 7.7 16.2 10.0 mm m 4.0 24 22 *1) Wiring spec. Selected sample (Selected…
-
10. SAFETY DEVICES
Model AO B18L 20A 250V Current fuse (NEAR THE TERMINAL) Circuit protection 5A 250V 15A 250V Current fuse (MAIN PRINTED CIRCUIT BOARD) Fan motor protection Compressor protection AO B24L OUTDOOR UNIT AOB18-24L OUTDOOR UNIT AOB18-24L Protection form Thermal protection program 3.15A 250V OFF:100 ON:95…
-
REMOTE CONTROLLER
-
REMOTE CONTROLLER
UTB- UD Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week) When setting up a timer, operation mode and a temperature setup can be changed. When a failure occurs,the error code is displayed. (Maximum of 16)…
-
FUNCTIONS
1 START/STOP button 2 Set temperature button Pressed to start and stop operation. Selects the setting temperature. Fan control button 5 Economy button 6 Timer mode (CLOCK ADJUST) button Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY). Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). Turns…