Инструкция на Чиллеры Clivet серии WDATA..., WDAT-3..., WDATC-3... с воздушным охлаждением
Чиллеры Clivet серии WDAT-3 2.160-2.180-2.200-2.220-2.250-2.280-2.300-2.320-2.340-2.360-2.390-2.420-2.450-2.480-3.480-3.500-3.540-3.630 -3.660 с воздушным охлаждением для наружной установки. Инструкция по монтажу и эксплуатации.
Смотрите также: Инструкция по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
2.1602.160-2.1802.180-2.2002.200-2.2202.2202.2502.250-2.2802.280-2.3002.300-2.3202.3202.3402.340-2.3602.360-2.3902.390-2.4202.4202.4502.450-2.4802.480-3.4803.480-3.5003.5003.5403.540-3.630 -3.660 AIR COOLED WATER CHILLER FOR OUTDOOR INSTALLATION Installation and Use Manual M02J40M6-04 WDAT-3…
-
- GENERAL INFORMATION GENERAL WARNINGS MANUAL PURPOSE This manual has been designed to enable the unit to be installed, started up and maintained correctly. MANUAL INSTRUCTIONS It is essential to observe these instructions. The manufacturer declines all liability for any damage that may be caused…
-
WDAT-3 2.160-3.660 STANDARD UNIT SPECIFICATIONS COMPRESSOR Compact semi hermetic helicoidal twin screw compressors: the main screw (male, with five lobes) is driven directly by the electric motor, while the secondary screw (female with six vanes) is driven by the primary one. The intrinsic…
-
ELECTRICAL PANEL the Power Section includes: - isolating transformer for auxiliary circuit power supply - fan overload circuit breakers - compressor control contactor - fan control contactors the control section includes: - proportional + integral water temperature control - antifreeze protection…
-
(2) (3) S B FC S ( St andard) R D - (St andard) B 2.300 - (St andard) FCD (1) VERSION Standard (S) Total Recovery ( R) made using tube bundle exchangers to recover 100% of the condensing heat for production of hot water. The version in question is supplied as standard with a variable-speed low…
-
- REGULATIONS AND CERTIFICATIONS UNI EN ISO 9001 CERTIFICATION CERTIFIED QUALITY SYSTEM UNI EN ISO 9001:2000 Clivet S.p.A., in order to guarantee customer satisfaction, has chosen the ISO 9001 Quality System as the reference for all its business activities. This is demonstrated by the company’s…
-
- RESIDUAL RISKS - GENERAL This section lists some of the more common situations which, being beyond the control of the manufacturer, could be a source of risk to persons or property. DEFINITION OF DANGER AREA The figure below highlights the area in which only authorised personnel may operate.…
-
ELECTRICAL SYSTEM - If the power line connecting the unit to the a.c. supply is incomplete, or if the connection is made with cables of incorrect cross section and/or with insufficiently rated protective devices, this can result in electric shock, toxicity hazard, damage to the unit or fire. All…
-
storage 08 Control of individual exposure/protection 09 Physical and chemical properties 10 Stability and reactivity 11 Toxicological information Manipulation: Technical measures/precautions. Form of storage and manipulation applicable to the products: PRESSURIZED GAS. Ensure adequate ventilation…
-
GENERAL TECHNICAL SPECIFICATIONS Acoustic configuration: standard (ST) / compressors insulation (SC) / energy efficiency: high efficiency (H) SIZES 2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480 COOLING Cooling capacity Compressor power input Total power input…
-
Acoustic configuration: standard (ST) / compressors insulation (SC) / energy efficiency: high efficiency (H) SIZES COOLING Cooling capacity Compressor power input Total power input EER ESEER COMPRESSOR Type of compressors No. of Compressors Std Capacity control steps Refrigerant circuits INTERNAL…
-
- E L E C T R I C AL D A T A Acoustic configuration: low noise (LN) / energy efficiency: high efficiency (H) SIZES 2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480 2.92 4.18 2.91 4.18 2.92 4.18 2.91 4.18 2.92 4.17 3.01 4.31 3.07 4.38 3.06 4.37 3.09 4.42 3.06 4.38…
-
- E L E C T R I C AL D A T A Acoustic configuration: low noise (LN) / energy efficiency: high efficiency (H) SIZES COOLING Cooling capacity Compressor power input Total power input EER ESEER COMPRESSOR Type of compressors No. of Compressors Std Capacity control steps Refrigerant circuits INTERNAL…
-
- E L E C T R I C AL D A T A Acoustic configuration: extremely low noise (EN) / energy efficiency: high efficiency (H) SIZES 2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480 353 123.1 133.4 2.65 3.98 387 135.5 145.8 2.65 3.98 447.5 156 168.7 2.65 3.98 503.9 180.6…
-
- E L E C T R I C AL D A T A Acoustic configuration: extremely low noise (EN) / energy efficiency: high efficiency (H) SIZES COOLING Cooling capacity Compressor power input Total power input EER ESEER COMPRESSOR Type of compressors No. of Compressors Std Capacity control steps Refrigerant circuits…
-
INTERNAL EXCHANGER PRESSURE DROP 80 70 EVAPORATOR PRESSURE DROP LIMIT. CAUTION: DO NOT USE UNDER THIS LIMIT. 2.3 40 - 60 2. 3 00 - 50 2 .4 50 - 2 .1 80 -2 2.2 2.2 . 2.3 60 -2 2 .2 .39 80 0-2 2. 4 . 20.2 35.4 35.4 35.4 35.4 53.6 53.6 53.6 53.6 53.6 53.6 53.6 64.4 64.4 2.1 60 11.6 15.5 15.5 18.6 17.2…
-
INTERNAL EXCHANGER Maximum operating pressure on refrigerant side Maximum operating pressure on refrigerant side kPa 1650 1650 kPa 1600 1600 CLIVET (C) PED (CE) SOUND LEVELS Acoustic configuration ST Acoustic configuration SC Sound Sound pressure power level level Octave band (Hz) Size 2.160 2.180…
-
- RECEPTION -
- RECEPTION - INSPECTION UPON RECEPTION Check on arrival that the unit has not suffered damage during transit and that it is complete in every part as specified in the order. In the event of visible damage/deficiencies being discovered, make a note immediately on the delivery document with the…
-
- RECEPTION 3 lifting points
use 3-boom tie rods (3 cables/chains/straps for each unit side) Insert safety pins ( 1 ) and split pins ( 2 ) lifting points use 4-boom tie rods (4 cables/chains/straps for each unit side) Charge balancing According to the spring equalizing rocker arm type, move the upper or lower hooks = = a a<b b…
-
- POSITIONING -
- POSITIONING - GENERAL For installing air-conditioning systems, it is necessary to consider the following: • the technical spaces necessary for the machine and system • the place where the machine will be installed • the transport of thermal carrier fluids and relevant connections to the unit: o…
-
- POSITIONING INSTALLATION OF ANTIVIBRATION MOUNTS
-
- POSITIONING -
-
- POSITIONING DIMENSIONS / WEIGHT DISTRIBUTION
-
- POSITIONING -
-
таблицы и схемы — в просмотре
-
- POSITIONING Sizes 2.390 LN
-
- POSITIONING -
-
- POSITIONING -
2510 Sizes 3.480 ST/SC 3 83 B 3 2160 83 2326 2440 (**) 1500 (12) 14 14 C3 14 C1 700 (10) 1500 (12) 700 (11) C2 14 SIZES A B C D M N O P OD W1 W2 W3 W4 W5 W6 mm mm mm mm mm mm mm mm mm kg kg kg kg kg kg ST SC 3.480 3.480 (*) (*) (*) (*) (*) (*) (*) (*) 4232 4708 1023 1303 219 2015 2678 1599 1552 2061…
-
таблицы и схемы — в просмотре
-
- POSITIONING 3.480-3.500-3.540 LN/EN
-
- POSITIONING -
-
WDAT-3 2.160-3.660 - W ATER CONNECTIONS GENERAL WARNINGS Piping must be designed with the least possible number of bends and head variations. If the pressure chute of the installation is above the useful prevalence of the pump, the water delivery capacity is reduced as well as, as a consequence, the…
-
SUGGESTED CONNECTION DIAGRAM An example of a plan is as follows: F = Impurity collector with filter GE = Flexible joint GRA = Automatic filling assembly with gate valve M = Pressure gauge P = Pump PD = Differential pressure switch R = Ball valve RS = Discharge cock SA = Storage tank (if necessary) T…
-
The characteristics of the electrical lines and relevant components must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with professional procedures and the regulations in force. All electrical operations should be performed…
-
ACOUSTIC CONFIGURATION: LOW NOISE (LN) Voltage: 400/3/50 SIZES 2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480 F.L.A. FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS F.L.A. - Total A 248.3 281.9 366.8 366.8 404.2 458.3 490.6 522.9 557 591.1 616.7 685.7 727.7 757.7…
-
ON 15 / 02 / 03 ONLY FOR UNITS IN THE CONSTRUCTIVE CONFIGURATION WITH A STANDARD KEYBOARD: 08:03:51 12.2 9.3 7.0 COOL STEP: 03 / 04 °C IN °C OUT °C SET MODE ALARM SETUP F1 F2 F3 STATE F4 I ? ESC HOME • Use voltage-free remote control devices that are suitable to commutate very low loads (12V, 10mA).…
-
CLIVET TALK MODULAR SYSTEM COMPOSITION CLIVET TALK system is made up of different modules connected to each other with the CAN OPEN protocol. The system configuration varies according to the typology of the unit and of the accessories: not always the represented electric modules are all presents on…
-
WDAT-3 2.160-3.660 REMOTE TERMINAL cod PE1W0005 The remote keyboard has the same functions of the keyboard on board of the machine. The connection of the remote keyboard to the system on board of the machine is carried out, using the “CAN to CAN” converter, which must be placed in the electric board…
-
UNIT NETWORK – MINI NETWORK – MASTER SLAVE The CLIVET TALK Local Network system allows to connect up to 6 machines in a network which all serve the same installation. To interact with the network which controls the working of the system, it is necessary to have a CAN to CAN converter code C5110692…
-
- START-UP - ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF THE SYSTEM. ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. PRELIMINARY CHECKS Before checking, please…
-
VERIFY TENSIONS – ABSORPTIONS Check that the temperatures of the fluids are included in the WORKING LIMITS. If the controls of the previous paragraphs are positive, it is possible to restart the unit. For information on the control panel, refer to the paragraph SETTING. While the unit is working…
-
- CONTROL - CONTROL -
CONTROL INTERFACE Enabled timing bands unit status (ON – ECO – OFF) COOL cooling HEAT heating Number of steps activated in comparison with the steps available INLET temperature alarm ; OK ON 15 / 02 / 03 ALARM menu access HEAT / COOL changement (see details in the following pages) 08:03:51 12.2 9.3…
-
- CONTROL -
PRESENT COOLING SET-POINT The COMPENSATED set-point, which keeps the compensations into account, is identified as the PRESENT set-point and it is displayed on the main display and at status n° 2. MAINTENANCE SET POINT It can be used to maintain the installation inside the working limits, even if the…
-
- CONTROL -
menu: PARAMETERS – THERMOREG. – SET POINT DEFAULT values 90 / CEN SecondSetC Secondary cooling Set Point 12 91 / CEN SecondSetH NOT USED - Secondary heating Set Point 35 118 / CEN SetCool Cooling Set Point 6.5 119 / CEN SetHeat NOT USED - Heating Set Point 45 272 / CEN SetRecovery NOT USED 35 menu…
-
- CONTROL -
SETUP – PARAMETERS: THERMOREG. Set the setpoint and the operating modes To enter in the SETUP menu button F3 SETUP I ? ESC H OME I ? ESC H OME ? ESC ? ESC ? ESC ? ESC buttons ▲▼ F2 – F3 To select the submenu SET (ATC ONLY) To access button F1 ENTER I To access the desired parameter buttons ▲▼ F1…
-
- CONTROL SETUP – CLOCK SETUP
button F3 SETUP To enter in the SETUP menu CLOCK Set the clock DATA Set the dater To select the CLOCK SETUP submenu I ? ESC H OME I ? ESC H OME ? ESC ? ESC ? ESC ? ESC buttons ▲▼ F2 – F3 To access to CLOCK button F1 ENTER I To set HOURS MINUTES SECONDS HOME buttons F2 F3 F4 I H OME To confirm the…
-
- CONTROL -
submenu: To enter in the STATA menu GENERALS UNIT 1 button F4 STATE I ? ESC HOME I ? ES C HOME I ? ES C HOME I ? ES C HOME I ? ESC HOME I ? ESC HOME buttons ▲▼ F2 – F3 To select the module mod_comp1 mod_comp2 To access mod_comp3 button F1 ENTER mod_evap buttons ▲▼ F2 - F3 To scroll the stata UNIT 2…
-
- CONTROL Index
UNIT_1 – MOD COMP_1 Stata Coil temperature Recovery temperature Condensation pressure Evaporation pressure Fan Status Defrost Status Defrost count time Compressor 1 operating time Comp. 1 starts Compressor 2 operating time Comp. 2 starts Compressor 3 operating time Comp. 3 starts Recovery valve…
-
- CONTROL -
An alarm list is associated with the inputs of each electronic module of the unit. According to the unit configuration, and then with electronic modules and options, some lists and/or ALARMS can not be used. ALARM STRUCTURE CENTRAL Unit_1 Mod_comp1 Mod_comp2 Mod_comp3 Mod_Evap Unit_2 Mod_comp1…
-
- CONTROL COMPRESSOR MODULE
Name E101 Cond./ Evap. temp. probe fault E102 Condensing pressure probe fault E103 Evaporation pressure probe fault E104 Recovery temp. probe fault E105 High pressure alarm E106 Low pressure alarm E107 Fan/Pump thermal cut-out alarm E111 Cond. / Evap. H2O flow alarm E112 High pressure pre-alarm 1…
-
- ROUTINE MAINTENANCE - PREVENTIVE MAINTENANCE All equipment is subjected to wear out. The maintenance makes: 1. keeps the unit efficiency 2. the components last longer, 3. keeps their efficiency and limits breakdowns. Therefore, it is fundamental to perform periodical checks: a few controls can be…
-
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well. Refer to local actuation norms. st In Italy, refer to the Ministerial Decree of 1 December 2004 no. 329 (and following modifications), which defines the st performances to be executed; the units of 1…
-
M02J40M6-04
-
- TROUBLESHOOTING -
- TROUBLESHOOTING - THE OPERATIONS MUST BE CARRIED OUT BY TECHNICAL QUALIFIED PERSONNEL HAVING THE REQUISITES UNDER LAW REQUISITES AND IN CONFORMITY WITH THE SAFETY REGULATIONS IN FORCE. THE INTERVENTIONS WITHIN THE WARRANTY PERIOD WILL BE CARRIED OUT BY AUTHORIZED SERVICE CENTERS. BEFORE RESETTING…
-
- DECOMMISSIONING OF THE UNIT -
WDAT-3 2.160-3.660 - DECOMMISSIONING OF THE UNIT - DISCONNECTING THE UNIT The units must be disconnected by authorised personnel, who before proceeding must first read the Residual Risks section in this manual. Before disconnecting the unit, the following must be recovered, if present: • the…
-