INSTALLATION, OPERATING
& MAINTENANCE MANUAL Ultima Compact FreeCool Free-Cooling Chiller 75 – 450 kW
-
About Airedale Products & Customer Services
WARRANTY, COMMISSIONING & MAINTENANCE The equipment carries Airedale’s standard Parts (non consumable) & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, which ever is the sooner. (Excludes the cost of any specialist access or lifting…
-
Contents
GENERAL STATEMENT 4 WARRANTY 5 GENERAL DESCRIPTION 6 Unit Identification Standard Features Optional Extras – Energy Saving Optional Extras – General INSTALLATION DATA Dimensions Point Loadings, Weights & Centre of Gravity (C of G) Unit lifting Anti Vibration Mounting Positioning Water System…
-
General Statement
IMPORTANT The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. SAFETY The equipment has been designed and manufactured to meet…
-
Warranty
GENERAL To be read in conjunction with Airedale International Air Conditioning Ltd standard Conditions of Sale and any related quotation. The equipment carries Airedale’s standard Parts (non consumable) & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the…
-
General Description
UNIT IDENTIFICATION INTRODUCTION ULTIMA COMPACT FREE-COOLING CHILLER UCFC Ultima Compact FreeCool 75 - 450 Model Size (Expressed as Nominal Cooling in kW) D- Double Circuit - Standard Chiller DQ- Double Circuit - Quiet Chiller DSQ- Double Circuit - Super Quiet Chiller 2 - 16 Number of Fans /1 or /2…
-
General Description
STANDARD FEATURES With all the features of the Standard range, the Quiet and Super Quiet chillers are available with additional features: Quiet Chiller - DQ • Fan speed reduced to 750 rpm Super Quiet Chiller DSQ • • • Fan speed reduced to 570 rpm Acoustically lined compressor compartment Enhanced…
-
General Description
OPTIONAL EXTRAS – ENERGY SAVING Power Factor Correction When applied to the motors of each compressor, the compressor power factor is controlled to a minimum operating value of 0.95 at the full operating capacity. This satisfies many supply authorities that may impose surcharges on equipment with…
-
Installation Data
-
таблицы и схемы — в просмотре
-
Installation Data
-
Installation Data
UNIT LIFTING • • • • • • • CAUTION Employ lifting specialists. Local codes and regulations relating to the lifting of this type of equipment should be observed. Use the lifting eye bolts provided. Use the appropriate spreader bars/lifting slings with the holes/lugs provided. Attach lifting chains to…
-
TECHNICAL UPDATE
Date: 18/10/05 MANUAL AFFECTED: TECHNICAL & INSTALLATION ULTIMA: UCC/UCCU 30-450 UCFC/URAC/UWC75-450 UFC/USC200-750 MANUAL PART NO: 901-108 TM E 02/05/A CHANGE: ANTI-VIBRATION MOUNT (SPRING TYPE) SPECIFICATION & INSTALLATION INSTRUCTIONS: COMPONENTS: 6a 6b Locating Screw Retaining Nut & Washer…
-
Installation Data
ANTI VIBRATION MOUNTING - OPTIONAL Spring Type (CLS) - 5mm - 5mm 9 2 X Selection: C Model Size 75 - 450 1 A 2 3 C 15 4 C 5 = = 16 A B 100 200 C 20 D 14 X 180 - 210 = Locate and secure mount using bolting down holes provided in base plate. Ensure mounts are located in line with the chiller base.…
-
Installation Data
POSITIONING The installation position should be selected with the following points in mind: • Position on a stable and even base, levelled to ensure that the compressor operates correctly • Levelling should be to +/- 5mm • Where vibration transmission to the building structure is possible, fit…
-
Installation Data
WATER SYSTEM CAUTION Chilled water pipework and ancillary components must be installed in accordance with: • National and Local Water supply company standards • The manufacturer's instructions are followed when fitting ancillary components • The system liquid is treated to prevent corrosion and…
-
Installation Data
WATER SYSTEM Pump Statement When installing circulating water pumps or equipment containing them, the following rules should be applied: • Ensure the system is filled with liquid then vented and the pump primed with water before running the pump. This is required because the pumped liquid cools the…
-
Installation Data
WATER SYSTEM Connections Water Inlet / Outlet (1) Water Drain/Bleed in Water System Min. System Water Volume (2) l Max. System Press Bar OPTIONAL EXTRAS Water Pump (3) (4) Nom External Head Std Single / kPa R&S Nom External Head Larger kPa Single/R&S Nom External Head Standard kPa Twin Nom External…
-
Installation Data
GLYCOL DATA CAUTION All free-cooling units should use minimum 20% glycol concentration. Ethylene Glycol Nominal Correction Factors Glycol in System / Freezing Point ºC Cooling Duty Input Power Water Flow Pressure Drop Catalogue Data x by: 20% / -9°C 1.00 1.00 1.00 1.00 30% / -15°C 0.98 0.98 1.09…
-
Installation Data
INTERCONNECTING WIRING No Pumps UCFC75 - 450 L1 L2 L3 E ! ! ! ! " " " " Mains incoming supply 400V/3PH/50Hz L4 N1 E ! ! ! " " " Separate Permanent Supply 230V/1PH/50Hz 2 N ! ! # " External Trace Heater Connections 240V/500W max. 502 522 ! ! # " 502 505 ! ! # " Unit Remote On/Off 24VAC 502 507 ! ! #…
-
Installation Data
ELECTRICAL DATA Unit Data Nominal Run Amps (1) Maximum Start Amps (2) Permanent Supply Mains Supply Rec Permanent Fuse Size Rec Mains Fuse Size Max Permanent Incoming Cable Size Max Mains Incoming Cable Size Control Circuit Evaporator Pad Heater Rating External Trace Heating Available (fitted by…
-
Installation Data
ELECTRICAL DATA Unit Data Nominal Run Amps (1) Maximum Start Amps (2) Permanent Supply Mains Supply Rec Permanent Fuse Size Rec Mains Fuse Size Max Permanent Incoming Cable Size Max Mains Incoming Cable Size Control Circuit Evaporator Pad Heater Rating External Trace Heating Available (fitted by…
-
Installation Data
ELECTRICAL DATA Unit Data Nominal Run Amps (1) Maximum Start Amps (2) Permanent Supply Mains Supply Rec Permanent Fuse Size Rec Mains Fuse Size Max Permanent Incoming Cable Size Max Mains Incoming Cable Size Control Circuit Evaporator Pad Heater Rating External Trace Heating Available (fitted by…
-
Controls
CONTROL SCHEME FEATURES Airedale recognises that all chiller applications are different but fall mainly into 2 application categories; Variable Supply Temperature and Constant Supply Temperature. The onboard microprocessor has the capability of satisfying either control requirement as illustrated…
-
Controls
GENERAL DESCRIPTION microprocessor controller offers powerful analogue and digital control to The meet a wide range of monitoring and control features including a real time clock and Industry standard communication port and network connections. The controller’s inbuilt display is used for viewing…
-
Controls
OPERATION Standard Operating Page cont. The following Menus can be accessed from the Operating Page, it is recommended that Password Protection To guard against unauthorised adjustments, a password is required to gain access to certain menus as defined below. the display is always returned to the…
-
Controls
VIEWING UNIT OPERATING STATUS Status Menu Allows access to view operating status of Digital and Analogue Inputs and Outputs. Using the Navigation instructions, the following Sub-Menus shown in sequence can be accessed: Tandem Compressor Units Digital Inputs ID1 ID2 ID3 ID4 ID5 ID6 ID7 ID8 ID9 ID10…
-
Controls
ALARMS The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order. Alarm Handling 1 A Red LED behind the Alarm alarms, simply press the 2 key will light in the event of an alarm. To view the key and the keys to scroll through. Auto reset alarms will…
-
Commissioning Data
GENERAL DATA Operating Limits Unit With Electronic Fan Speed HP Control (-20°C) Minimum ambient air db °C -20°C Maximum ambient air db °C Refer to Technical Manual - Performance Data - Capacity Data Minimum leaving water temperature °C +6C Maximum return water temperature °C +20°C 1 2 Temperatures…
-
Commissioning Data
WATERSIDE PRESSURE DROPS (20% Ethylene Glycol Concentration) CAUTION Constant water flow MUST be maintained. Variable water volume is NOT recommended and may invalidate warranty. Use the formula below to calculate the External Head Available: - Total Pump Head Available Chiller Pressure Drop =…
-
таблицы и схемы — в просмотре
-
Commissioning Data
WATERSIDE PRESSURE DROPS (20% Ethylene Glycol Concentration) CAUTION Constant water flow MUST be maintained. Variable water volume is NOT recommended and may invalidate warranty. UCFC160DSQ UCFC450DSQ WATERSIDE PRESSURE DROP (kPa) 300 330DSQ-360DSQ 250 225DSQ 200DSQ 160DSQ-180DSQ 200 450DSQ 400DSQ…
-
Commissioning Data
TOTAL PUMP HEAD AVAILABLE (kPa) 325 TOTAL PUMP HEAD AVAILABLE (kPa) Single Head Pump or Run/Standby 450 TOTAL PUMP HEAD AVAILABLE (kPa) PUMP PACKAGES WATERFLOW (l/s) WATERFLOW (l/s) WATERFLOW (l/s) UCFC75 UCFC100 UCFC125 UCFC150 UCFC160-450 32 Curve Chillers Installation & Maintenance : 903-132 IM E…
-
Commissioning Data
WATERFLOW (l/s) TOTAL PUMP HEAD AVAILABLE (kPa) Twin Head Pump TOTAL PUMP HEAD AVAILABLE (kPa) PUMP PACKAGES WATERFLOW (l/s) UCFC75 UCFC100 UCFC125 UCFC150 UCFC160-450 Curve Twin Head Pump Standard Larger Chillers Installation & Maintenance : 903-132 TM E 06/05/A 33
-
Commissioning Data
OPERATIONAL SEQUENCE Refrigerant Charge Check for the presence of a refrigerant charge in the condenser side. Sump Heater The mains supply to the sump (oil) heater should be switched on at least 8 hours prior to compressor starting to avoid refrigerant migration. CAUTION Pre-Start-Up Check CAUTION A…
-
Commissioning Procedure
GENERAL To be read in conjunction with the commissioning sheets provided, items highlighted should be recorded. CAUTION Please ensure all documents have been completed correctly and return to Technical Support immediately to validate warranty. PRE COMMISSIONING CHECKLIST CAUTION ALL work MUST be…
-
Commissioning Procedure
PRE COMMISSIONING CHECKLIST (CONT..) • • CAUTION Prior to the chiller compressors being allowed to start, the Water Flow Fail and Pump Interlock features MUST both be proven to work correctly. • RECORD Check that each circuit trips on low pressure. The alarm should appear within 3 minutes. The alarm…
-
Commissioning Procedure
COMMISSIONING CHECKLIST The following should be carried out with a load on the system, otherwise the unit is likely to short cycle. The following tests are to be carried out on 1 circuit at a time. • Switch the door interlocking MCCB to the ON position but again only on the circuit which is to be…
-
Maintenance
CAUTION ALL work MUST be carried out by Technically Trained competent personnel. The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work. GENERAL MAINTENANCE The maintenance schedule indicates the time period between maintenance operation. 3 MONTHS ACTION…
-
Maintenance
GENERAL MAINTENANCE (CONT..) 6 MONTHS ACTION NOTES Repeat 3 month checks plus the following: SYSTEM 12 MONTHS Check evaporator trace heating and low ambient thermostat Remember to re-cap the Schraeder are set to activate at 4.0ºC. connections! ACTION NOTES Repeat 6 month checks plus the following…
-
For ease of identification when ordering spares or contacting Airedale about your unit,
please quote the unit type, unit serial number and the date of manufacture, which can be found on the unit serial plate. A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on request. The serial plate can be located inside Item 24.…
-
Notes
-
таблицы и схемы — в просмотре
-
Head Office
Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY United Kingdom Tel: Fax: e-mail: website: +44 (0) 113 239 1000 +44 (0) 113 250 7219 enquiries@airedale.com www.airedale.com Regional Sales Offices: Midlands Tel: Fax: e-mail: 0121 7071010 0121 7071069…
-
Airedale Departmental Contact Details
CUSTOMER SERVICES For further assistance, please e-mail: enquiries@airedale.com or telephone: Customer Services UK Sales Enquiries International Enquiries Spares Hot Line Airedale Service Technical Support Training Enquiries + 44 (0) 113 238 7789 + 44 (0) 113 239 1000 + 44 (0) 113 238 7878 + 44 (0)…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.