Крышные зонты Lindab для приточного и вытяжного воздуха. Каталог продукции
Крышные зонты Roof hoods Lindab для приточного и вытяжного воздуха. Каталог с техническими данными.
Загружаем документ…
Текст каталога
-
Lindab
1 General information and theory 2 Safe 3 Silencers 4 Dampers & Measure units 5 Fire dampers & Smoke evacuation 6 Air valves 7 Roof hoods 8 Other circular products 9 Transfer 10 Rectangular 11 Flexible ducting 12 Isol 13 Access doors 14 Smart tools 15 Duct suspensions & Support systems 16 Fastening…
-
General
Version Extract air – All Lindab’s roof hoods are suitable for use as extract air hoods. When choosing extract air hood, the architectural design is important to ensure that the hood is in harmony with the rest of the building. Our range includes ribbed hoods, rectangular and circular roof hoods…
-
Example – Noise from roof hood
3 This is now to be moved, and we want to know the sound pressure level 30 metres from its new location closer to a vertical wall surface. We assume that the noise from the fan is unchanged in the two cases. Lp = 60 dB m 4 First you extract the sound power level LW from the equation above. L ⎛ 4 ⋅ π…
-
2 Products used for penetration of roof Prinipal sketch Roof hood | Roof transition connection piece, upper | 6 Roof weather protection, outer | 7 Roof weather protecation, inner | 8 9 Vapour membrane | 10 Roof transition | 11 Roof transition fastener | 12 13 Roof transition connection piece, lower…
-
H
Dimensions 1 ØD 2 H 3 4 Ød Description Circular roof hood intended for outdoor air and extract air. The hood is designed for location above the roof with or without a roof through connection. The air runs both on the top- and downside of the hood. This is valid both for outdoor and extract air. The…
-
H
1 Roof hood 2 AGIS Roof transition connection piece, upper TGR-OA 3 SR SRI Sits around the roof transition VHING / VHINP Roof weather SRIP 4 protection, outer GISOL / GISOLP TGR 5 UG 6 Roof weather protection, inner Roof transition 7 MG / MGL 8 Vapour membrane SBG1 9 Roof transition fastener 10…
-
HV
Dimensions 1 ØD 2 H 3 h 4 5 Ød Ordering example Ød ØD h H nom mm mm mm 1015 1188 630 1115 780 1470 800 1407 1040 1872 1000 1712 1270 2285 1250 2092 1585 2780 α ° Free area m² 0,008 0,012 0,020 0,031 0,049 0,078 0,126 0,196 0,312 0,503 0,785 1,230 Technical data 1000 HV Product Dimension Ød…
-
HV
1 Roof hood 2 AGIS Roof transition connection piece, upper SR SRI TGR-OA 3 Sits around the roof transition VHING / VHINP Roof weather SRIP 4 protection, outer GISOL / GISOLP TGR 5 UG 6 Roof weather protection, inner Roof transition 7 MG / MGL 8 Vapour membrane SBG1 9 Roof transition fastener 10…
-
HU
-
HU
1 Roof hood 2 AGIS Roof transition connection piece, upper SR SRI TGR-OA 3 Sits around the roof transition VHING / VHINP Roof weather SRIP 4 protection, outer GISOL / GISOLP TGR 5 UG 6 Roof weather protection, inner Roof transition 7 MG / MGL 8 Vapour membrane SBG1 9 Roof transition fastener 10…
-
HN
Dimensions 1 h H Ød 5 12 m kg 0,66 0,96 1,26 1,95 2,92 4,31 6,75 Roof through connection TGR 50 100 mm mm Size As special delivery the hood can be supplied with three anchoring wire-loops. LWA [dB] 1000 0 Technical data 20 The hood has a female connection, which fits outside a ventilation duct. The…
-
HN
1 Roof hood 2 AGIS Roof transition connection piece, upper TGR-OA 3 SR SRI Sits around the roof transition VHING / VHINP Roof weather SRIP 4 protection, outer GISOL / GISOLP TGR 5 UG 6 Roof weather protection, inner Roof transition 7 MG / MGL 8 Vapour membrane SBG1 9 Roof transition fastener 10…
-
HF
Dimensions 1 H Ød 5 14 1000 0 Ød [mm] LWA [dB] The hood is delivered with three turnable lifting and anchoring wire-loops. A single wire-loop shall not be exposed for forces exceeding 1500 N. To avoid damage to the net in the opening the hood is supplied with transport protection. This must be…
-
VHL
Dimensions 1 H Ød1 ØD 5 Description The VHL lamella hood is developed specially to achieve an architectally correct ending of air intake and outlet on the roof. The lamella hood is as standard delivered in galvanised design, can also be delivered in black powder coating. In order to achieve a…
-
таблицы и схемы — в просмотре
-
VHL
1 Roof hood 2 TGR-VHL Roof transition connection piece, upper SR SRI 3 Sits around the roof transition VHING / VHINP Roof weather SRIP 4 protection, outer GISOL / GISOLP TGR 5 UG 6 Roof weather protection, inner Roof transition 7 MG / MGL 8 Vapour membrane SBG1 TGR-NA Roof transition connection…
-
VHL
Dimensions 1 2 H 30 ØD 3 4 Ød1 Description Circular lamella hood for air intake and outlet. The hood is as standard delivered in galvanized finish, but is also available with black powder coating or in acid-proof stainless material. Ød1 nom ØD mm H mm Free area m² m kg Outdoor air max. rec. * m³/h…
-
HRR
Dimensions 1 B 2 H 3 4 A 5 Description 6 Rectangular roof hood intended for outdoor air and extract air. HRR is designed for positioning above the outer roof on the roof through connection. The air runs both on the top- and downside of the hood. This is valid both for outdoor and extract air. The…
-
HRR
1 Roof hood Sits around the roof transition UG Roof weather protection, inner TGR Roof transition MG / MGL Vapour membrane 5 6 Roof transition connection piece, lower 7 TGR-NA SR LKR Ducting This diagram shows pricipally all possible combinations of how the products can be joined together. Normally…
-
HVR
Dimensions 1 B 2 α h H A Description 6 Rectangular roof hood with angled upper side intended for outdoor air and extract air. HVR is designed for positioning above the outer roof on the roof through connection. The air runs both on the top- and downside of the hood. This is valid both for outdoor…
-
HVR
1 Roof hood Sits around the roof transition UG Roof weather protection, inner TGR Roof transition MG / MGL Vapour membrane 5 6 Roof transition connection piece, lower 7 TGR-NA SR LKR Ducting This diagram shows pricipally all possible combinations of how the products can be joined together. Normally…
-
LHR
Dimensions 1 H 2 B+ A×B A + 100 5 Description 6 LHR is a rectangular roof hood with ribs that is used for both outdoor air and extract air. When used for outdoor air intake it is recommended not to let the air velocity exceed 2 m/s due to risk of rain or snow pull in. The hood is supplied as…
-
таблицы и схемы — в просмотре
-
LHR
1 Roof hood 2 TGR-LHR Roof transition connection piece, upper TGFR 3 Sits around the roof transition UG Roof weather protection, inner TGR 4 5 MG / MGL Roof transition 6 Vapour membrane 7 SBGR Roof transition fastener 8 TGR-NA Roof transition connection piece, lower 9 LKR SR 10 Ducting 11 12 This…
-
HKOMR
Dimensions 1 2 D A B H 3 C Description Combi-hood intended for outdoor air intake and the expelling of extract air. HKOMR is designed for location above the roof with or without a roof through connection. The intake and extract sections are separated with an internal wall. The intake section is…
-
таблицы и схемы — в просмотре
-
HKOMR
1 Roof hood 2 TGKOMR 3 Roof transition 4 5 Roof transition connection piece, lower 6 7 TGR-NA TGR-NA SR SR LKR LKR Ducting 8 9 This diagram shows pricipally all possible combinations of how the products can be joined together. Normally only one alternative is chosen and sometimes some options are…
-
TGR
Dimensions 1 TGR-OA – Upper connection 2 Ø80–315 70–170 C Ø400–1250 5 Description 45 6 Intended for connection to roof hood and roof fan. Available with various types of insulation for condensation or fire protection. Two fixing profiles are supplied to suit the root pitch. C 7 The C-measure of the…
-
TGR
Dimensions Accessories Size A mm 1000 1100 1200 1300 1400 1500 1600 B mm 50 mm 100 mm insul. insul. 1000 900 1100 1000 1200 1100 1300 1200 1400 1300 1500 1400 Weight kg 50 mm 100 mm insul. insul. 16,9 21,9 22,9 30,1 29,7 39,2 37,4 49,6 43,9 58,4 50,3 67,1 59,2 78,8 65,9 87,9 72,7 97,0 82,6 110,3…
-
VH
HN H HU VHA VHP HV VHL LHR HVR HRR 1 Roof hood 2 Roof transition connection piece, upper TGRVHL TGR-OA TGRLHR 3 Sits around the roof transition UG Roof weather protection, inner TGR 4 5 MG / MGL Roof transition 6 Vapour membrane 7 8 Roof transition connection piece, lower TGR-NA 9 SR Ducting LKR…
-
TGKOMR
Dimensions 1 C×D 40 2 * E E A×B Description Roof transition adapted for combi-hood HKOMR. The transition is produced with 50 mm fire or condensation insulation. At connection to circular duct two lower connections TGR-NA are used. The roof transition is manufactured as standard in galvanised steel…
-
HKOMR
1 Roof hood 2 TGKOMR 3 Roof transition 4 Roof transition connection piece, lower TGKOMR-NA TGKOMR-NA 5 SR SR LKR LKR 6 Ducting 7 8 This diagram shows pricipally all possible combinations of how the products can be joined together. Normally only one alternative is chosen and sometimes some options…
-
Vapour membrane
MG Dimensions 1 Ø5 2 L 3 C B R80 4 C Description 1 The product is based on a special flexible 2-component rubber (1) that is integrated with a 1 mm aluminium plate (2). 2 Used for sealing of the building envelope for all types of pipes and ducts, wich is lead trough a vapour barrier of roofing…
-
Vapour membrane
MGL Dimensions 1 2 A B 6 Description Made from a special flexible syntetic rubber and provided with tape with adhesive on both sides. Is used for sealing of the climate shield to all sorts of pipes and ducts, which passes through moisture barrier or roofing underlay. A special mounting instruction…