lindab | f ire dampers and smoke evacuation
Fire dampers & Smoke evacuation Lindab 1 General information and theory 2 Safe 3 Dampers & Measure units 4 Fire dampers & Smoke evacuation 5 Roof hoods 6 Transfer 7 Rectangular 8 Other circular products 9 Flexible ducting 10 Access doors 11 Duct suspensions & Support systems 12 Fastening material 13…
-
CR60
Dimensions Ød1 3 4 25(*) * Extending damper blade only for Ø 315 Description The CR60 is a very light circular fire damper with a fire resistance up to 90 minutes, which is installed in ventilation ducts passing through a construction element in order to stop the propagation of fire. The refractory…
-
CR60
Technical data for the motors 1 Installation • In rigid wall, floor and in flexible wall • Provide an additional zone of 200 mm to have free access to the mechanism MFUS Ød1/2 + 75 Ød1/2 + 75 2 • Avoid deflection of the tunnel • Installation and air movement may be from either direction 3 • Verify…
-
CR2
Dimensions 1 375 x 50 Ød1 y 253 5 Description The circular fire damper CR2 with a fire resistance of 120 minutes is installed in ventilation ducts passing through a construction element in order to stop the propagation of fire. The fire damper can be equipped with a common fusible link mechanism up…
-
CR2
Technical data for the motors 1 Installation • Installation in rigid wall with horizontal or vertical axis • Installation in massive floor or ceiling with horizontal axis • Provide an additional zone of 200 mm to have free access to the mechanism • Avoid deflection of the tunnel • Installation and…
-
CR2
Circular reduction piece for connection to a duct with a smaller diameter than the damper. 1 Delivered per piece. 2 RCVF l 10 BCM CR2 11 Ød2 12 13 L Ø d2 Ød CR2 L l We reserve the right to make changes without prior notice 353
-
CU2
-
CU2
Technical data for the motors Installation • Installation in rigid or flexible wall with horizontal or vertical axis H ≥ 300 mm P • Provide an additional zone of 200 mm to have free access to the mechanism • Installation and air movement may be from either direction Z Q 1 • Installation in rigid…
-
CU2L
-
MEC
MANO (+ME) The unlocking mechanism MANO unlatches the fire damper blade via remote control by sending an electric impulse (VD) or by interruption (VM) of the magnet’s power supply, or automatically, as the fusible link melts when the temperature in the duct rises above 72°C. For high temperatures…
-
MEC
BLF – Belimo 1 2 When connected to the power supply the servomotor moves the damper blade into its stand-by position. When the power is interrupted, the internal armed spring returns the damper blade into its safety position. BLF 24 BLF 230 24 Vdc -10% +20% 24 Vac ±20% 230 Vac ±15% 3 Voltage 4…
-
таблицы и схемы — в просмотре
-
MEC
DB – Joventa When connected to the power supply the servomotor moves the damper blade into its stand-by position. When the power is interrupted, the internal armed spring returns the damper blade into its safety position. DB 24 DB 230 24 Vdc ±10% 24 Vac ±20% 230 Vac ±10% Consumption holding 4W 4,5 W…
-
MEC
EX-Schischek When connected to the power supply the explosion proof motor moves the damper blade into its standby position. 1 When the power is interrupted, the internal armed spring returns the damper blade into its closed safety position. 2 For deflagration risk. Several risk areas are…
-
Frame
PG PG30 H×W H×W PG20 23 Standard for the damper CU2 20 6 PG30 Connection with ducts via frames of 30 mm: 12 13 PG20 H×W PG40 The four corners of the flange are provided with elliptical holes Ø 6,5 × 16 mm. PG40 Connection with ducts via frames of 40 mm: 43 Connection with ducts via frames of 20 mm…
-
Frame
PG Variants PM 1 PM PP No connection 2 H×W H×W Connection with ducts by socket joint. This type of frame is used in case of shortage of space for standard frames PG30. 3 This type of frame is used on transfer dampers or on one side of a damper that opens into a room. L-70 4 40 PP 5 H×W 6 7 L-70…
-
CU-LT
-
CU-LT
Option PG20 Inspection shutter UL: (Wn+40)x(Hn+40) 1 An inspection shutter can be used to visually determine the state and the condition (e.g. filth) of the damper. The inspection shutter is always mounted two-fold, one on the lower side and one on the upper side of the fire damper. 2 3 Positioning…
-
таблицы и схемы — в просмотре
-
CU-LT
-
таблицы и схемы — в просмотре
-
CU-LT
-
таблицы и схемы — в просмотре
-
CU-LT
-
таблицы и схемы — в просмотре
-
CU-LT
-
CU-LT
Correction factor ∆L To obtain the sound power level for the LW oct octave midband 1 LWA = A-weighted sound power level 2 ∆L = Correction factor LW oct = Sound power level for each octave midband 3 LW oct = DL + LWA [Hz] 1000 2000 4000 8000 2 - 4 m/s 22 9 -2 -11 -18 -21 -17 -8 6 - 8 m/s -4 -8 -13…
-
CU-LT
Operating mechanisms 1 MFUSP: simple operating mechanism with fusible link 2 The damper needs to be rearmed manually. The operating mechanism MFUSP automatically unlocks the blade when the temperature in the duct exceeds 72°C. Standard: 3 4 Options: • Fusible link 72° C • Manual unlocking possible •…
-
таблицы и схемы — в просмотре
-
CU-LT
Position of the thermo-electric fuse for BLFT(T) 1 Height Width Position ≤ 300mm = 200mm on the side opposite to the mechanism > 200mm on the W-side next to the inspection shutter > 300mm on the same side of the mechanism The mechanism is always mounted on the H-side. Standard: • Thermo-electric…
-
CU-LT
Evolution kits 1 KITS MFUSP Automatic operating mechanism MFUSP with fusible link 72°C 2 KITS FUS 72 MFUS(P) 3 Fusible link 72°C for MFUS(P) 4 KITS FDCU MFUS(P) 5 Unipolar beginning and end of range switches FDCU for MFUS(P) 6 KITS MMAG 7 Upgradable operating mechanism MMAG with fusible link 72°C 8…
-
CU-LT
1 KITS FDCB MMAG 2 Bipolar beginning and end of range switches FDCB for MMAG KITS BLF 24 KITS BLF 24-ST KITS BLF 230 Actuator Belimo BLF 24V/230V or BLF 24V with plug (ST), without thermoelectric fuse (T) KITS BLFT 24 KITS BLFT 24-ST KITS BLFT Actuator Belimo BLF 24V/230V or BLF 24V with plug (ST)…
-
CU-LT-1s
Dimensions y x 25 (Wn+40)x(Hn+40) wall limit - muurgrens - limite d’encombrement Description 6 The damper blade exceeds the tunnel: • Minimal pressure drop - very thin damper blade 25mm • Air tightness according to EN 1751 minimum class B (class C on demand) • Suitable for installing wall mounted on…
-
CU-LT-1s
Types of frames 23 PG20 20 1 H×W H×W Option : inspection shutter ul An inspection shutter can be used to visualise the position and the condition (e.g. filth) of the damper. The inspection shutter is always mounted two-fold, one on the lower side and one on the upper side of the fire damper. •…
-
таблицы и схемы — в просмотре
-
CU-LT-1s
-
таблицы и схемы — в просмотре
-
CU-LT-1s
-
таблицы и схемы — в просмотре
-
CU-LT-1s
-
таблицы и схемы — в просмотре
-
CU-LT-1s
-
CU-LT-1s
Correction factor ∆L To obtain the sound power level for the LW oct octave midband LWA = A-weighted sound power level ∆L = Correction factor LW oct = Sound power level for each octave midband LW oct = DL + LWA [Hz] 1000 2000 4000 8000 2 - 4 m/s 22 9 -2 -11 -18 -21 -17 -8 6 - 8 m/s -4 -8 -13 -19 -21…
-
CU-LT-1s
Operating mechanism MFUSP: operating mechanism with fusible link 1 The operating mechanism MFUSP automatically unlocks the blade when the temperature in the duct exceeds 72°C. 2 The damper needs to be rearmed manually. Standard: Options: • Fusible link 72° C • Manual unlocking possible • Manual…
-
таблицы и схемы — в просмотре
-
CU-LT-1s
Position of the thermo-electric fuse for BLFT(T) Height Width Position ≤ 300mm = 200mm on the side opposite to the mechanism > 200mm on the W-side next to the inspection shutter > 300mm on the same side of the mechanism The mechanism is always mounted on the H-side. Standard: • Thermo-electric fuse…
-
CU-LT-1s
Evolution kits 1 KITS MFUSP 2 Automatic operating mechanism MFUSP with fusible link 72°C 3 KITS FUS 72 MFUS(P) 4 Fusible link 72°C for MFUS(P) KITS FDCU MFUS(P) 5 Unipolar beginning and end of range switches FDCU for MFUS(P) 6 KITS MMAG 7 Upgradable operating mechanism MMAG with fusible link 72°C 8…
-
CU-LT-1s
KITS FDCB MMAG 1 Bipolar beginning and end of range switches FDCB for MMAG 2 KITS BLF 24 KITS BLF 24-ST KITS BLF 230 Actuator Belimo BLF 24V/230V or BLF 24V with plug (ST), without thermoelectric fuse (T) KITS BLFT 24 KITS BLFT 24-ST KITS BLFT 230 Actuator Belimo BLF 24V/230V or BLF 24V with plug…
-
Round connection with rubber sealing ring
-
VAN1V
1V 1V/P Description 6 The “VANTAGE”-shutters are used for the smoke evacuation in residential buildings in order to facilitate a safe evacuation of people. 7 Standard • locking mechanism 8 • connection box • blocking 9 • 1 shutter [1V] • hinge • front frame 10 • gaz spring (type ceiling) Fire…
-
таблицы и схемы — в просмотре
-
VAN2V
2V Description 2V/P 6 The “VANTAGE”-shutters are used for the smoke evacuation in residential buildings in order to facilitate a safe evacuation of people. 7 Standard 8 • centre support • locking mechanism • connection box 9 • blocking • 2 shutters [2V] 10 • hinge • front frame • gaz springs (type…
-
таблицы и схемы — в просмотре
-
MANF (+ME)
The unlocking mechanism MANF unlatches the smoke evacuation damper blade via remote control by sending an electric impulse (VD) or by interruption (VM) of the magnet’s power supply. By unlocking . the internal torsion spring unwinds and releases the damper blade into its safety position To indicate…
-
MEC
BF – Belimo 1 When connected to the power supply the servomotor moves the smoke evacuation damper blade into its stand-by position. 2 When the power is interrupted. the internal armed spring returns the damper blade into its safety position. BF 24 BF 230 24 Vdc -10% +20% 24 Vac ±20% 230 Vac ±15%…
-
MEC
DB – Joventa When connected to the power supply the servomotor moves the smoke evacuation damper blade into its stand-by position. 1 When the power is interrupted. the internal armed spring returns the damper blade into its safety position. 2 DB 24 DB 230 24 Vdc ±10% 24 Vac ±20% 230 Vac ±10%…
-
MEC
EX – Schischek 1 When connected to the power supply the explosion proof motor moves the smoke evacuaton damper blade into its stand-by position. 2 When the power is interrupted. the internal armed spring returns the damper blade into its safety position. For deflagration risk between several risk…