Клапаны и измерительные устройства Lindab. Каталог продукции
В каталоге приведены технические данные продукции Lindab: регулирующих и запорных клапанов, клапанов с приводами, постоянного и переменного расхода, а также измерительные устройства для определения фактического расхода воздуха на участках вентиляционной системы.
Загружаем документ…
Текст каталога
-
Dampers & Measure units
Lindab 1 General information and theory 2 Safe 3 Silencers 4 Dampers & Measure units 5 Fire dampers & Smoke evacuation 6 Air valves 7 Roof hoods 8 Other circular products 9 Transfer 10 Rectangular 11 Flexible ducting 12 Isol 13 Access doors 14 Smart tools 15 Duct suspensions & Support systems 16…
-
Content – Dampers
Tightness and pressure classes Tightness class 2 3 To shut-off To regulate DRU DIRU DIRBU DIRVU DSU 2 3 A 4 Pressure class 7 DTU DTMU DTWU DTHU DTH1U DTBU DTBCU DTU DTMU DTWU DTHU DTH1U DTH2U DTBU DTBCU DTFU DTBLU Ø355–630 Ø355–630 Ø355–630 Ø355–630 Ø355–630 Ø355–630 Ø355–630 Ø80–315 Ø80–315 Ø80–315…
-
Summary, motorized dampers
-
2 Preference Final Damper Motor Dimension 3 Extension spindle First choise 2nd choise 3rd choise DTBU LM 80–315 Last choise VREDF 15 60 LÖMOK Which parts to use when building motorized dampers at building sitestarting from; manual dampers or dampers prepared for motorizing. Lindab recommends to…
-
Preference
Final Damper Motor Dimension First choise 80–500 2nd choise 3rd choise DTBU SM 500–630 80–450 AXFL Last choise 1 First choise GM 80–630 710–800 2 900–1000 VREDF 15 60 Extension spindle 3 KOMHY LONG KOMHY LONG 4 KOMHY Motor Shelf 5 DTH1U DTHU DTU DTHU 6 Starting damper 7 Preference Final Damper Motor…
-
Preference 2 Final Damper Motor Dimension 3 First choise 2nd choise 3rd choise Last choise DTFU LMQ 80–250 VREDF 15 60 Extension spindle LÖMOK 4 KOMHY LONG Motor Shelf 5 DTH1U 6 DTHU DTU Starting damper Preference Final Damper Motor Dimension First choise 2nd choise 3rd choise DTFU LMQ-SR 80–250…
-
Preference
Final Damper Motor Dimension First choise 1 Last choise DTBLU CM 80–160 DTH2U 2 LM 80–315 DTH2U 3 Starting damper Preference Final Damper Motor Dimension 4 5 First choise Last choise First choise Last choise DTPU AK 31 P AK 41 P 80–200 250–315 MSATS AK 31 6 MSATS AK 41 7 Extension spindle KOMHY LONG…
-
General
The damper blade is normally designed so that a certain flow of air can always leak through, even if the damper is closed. This makes the sensitivity to angle changes less than for a shut-off damper. Dampers are available in both manual and automatic versions. The manual dampers are adjusted when…
-
DRU
Dimensions 1 45 Ø 80–630 Ød1 2 3 l 4 Ø 800–1000 5 Has a turning, cut-off blade. The blade is stepless adjustable 0–90°. The damper admits an insulation thickness of approx. 50 mm. 7 The blade is designed to generate a minimum of noise. The noise is approx. the same as for a perforated blade. But the…
-
DRU
Ø 630 3 The blade is set via a knob in a protec- × tive cup. The setting of the blade is read against × an embossed scale at the rim of the cup. The blade is locked with two screws, × type Pozidriv (PZD2). The blade has reinforced locking with a sturdy wing nut. The blade is reinforced. The blade is…
-
таблицы и схемы — в просмотре
-
DRU
-
таблицы и схемы — в просмотре
-
DRU
-
таблицы и схемы — в просмотре
-
DRU
-
DIRU
Dimensions 1 Ød1 g lockin en the ent Thigt djustm after s screw DIRU 125 6524 21-nov-05 ØD Description The damper DIRU with flow meter offers measurement of the air flow. DIRU has following characteristics: low noise level, centric flow, fixed measurement nozzles for accurate flow measurement and is…
-
2 Technical data for DIRU, DIRBU and DIRVU l = straight distance before and after disturbances Method error ± 7% Dimensioning The dimensioning graphs show the pressure drop over the damper with flow meter, Δpt. They should be used to determine the pressure drop and to provide information about sound…
-
Pressure drop graphs with noise data for
-
таблицы и схемы — в просмотре
-
Ø400
-
DIRU, DIRBU,
-
таблицы и схемы — в просмотре
-
DSU
Dimensions 1 45 Ø 80–630 Ød1 2 3 l 4 Ø 800–1000 5 Has a turning, circular blade. The blade is stepless adjustable 0–90°. The damper is used when you have lower demands for shut-off capacity. The damper admits an insulation thickness of approx. 50 mm. 7 The damper can on occations be used for…
-
DSU
Ø 630 3 The blade is set via a knob in a protective cup. The setting of the blade is read against an embossed scale at the rim of the cup. The blade is locked with two screws, type Pozidriv (PZD2). The blade has reinforced locking with a sturdy wing nut. The blade is reinforced. The blade is…
-
таблицы и схемы — в просмотре
-
DSU
-
таблицы и схемы — в просмотре
-
DSU
-
таблицы и схемы — в просмотре
-
DSU
-
DTU
Dimensions 1 45 Ø 80–630 Ød1 l Ø 800–1000 5 Description 6 Ød1 Has a turning circular blade with an EPDM-rubber seal which tightens against the inside of the damper when closed. The blade can be adjusted in a 0–90° angle. 7 The cup at Ø 80–630 can be complemented with the special insulation cup IK at…
-
DTU
Ø 400 Ø 500 Ø 630 The blade is set via a knob in a protective cup. × × × × The dashed curves give the A-weighted sound power data, LWA, in dB to the duct. The setting of the blade is read against an embossed scale at the rim of the cup. × × × × Example Given The blade is locked with two screws, type…
-
таблицы и схемы — в просмотре
-
DTU
-
таблицы и схемы — в просмотре
-
DTU
-
таблицы и схемы — в просмотре
-
DTU
-
DTMU/DTWU
Description DTMU/DTWU are tight-closing shut-off dampers. The dampers can be used to completely shut off the air flow. The blade consists of double sheet metal with a intermediate sealing of EPDM-rubber, which is in contact with the inside of the damper housing when in the closed position. DTMU is…
-
таблицы и схемы — в просмотре
-
DTMU/DTWU
-
таблицы и схемы — в просмотре
-
DTMU/DTWU
-
Shut-off damper with
motor shelf DTHU Dimensions 1 Ø 80–450 l1 Ød1 4 5 l 6 Description 7 Shut-off damper with motor shelf KOMHY Ø 80–630 consists of a DTU damper with a KOMHY combined motor shelf added. The damper has no knob, and has a longer spindle to avoid the need for extension spindle VREDF. The damper is designed…
-
Shut-off damper with
motor shelf DTHU Dimensions 1 Ød1 nom l mm l1 mm M Nm m kg Sealing class past closed blade 2,0 0,67 2,0 0,75 2,0 0,85 2,0 0,90 2,0 0,97 2,0 1,00 2,0 1,11 2,0 1,19 2,0 1,41 3,0 1,64 3,0 1,89 4,0 2,14 4,0 2,33 4,0 2,51 8,0 2,81 8,0 4,02 5,21 6,44 7,84 8,48 9,17 18,2 20,7 27,6 4 1000 32,6 We reserve…
-
shelf
DTH1U Dimensions Ød1 l Description Shut-off damper with motor shelf HYLLA LMNM. Consists of a DTU damper with motor shelf HYLLA LMNM added. The damper is designed to have a motor added on site. There is a separate assembly, measuring, balancing and maintenance instruction for this product. Ø 80–315…
-
shelf
DTH2U Dimensions Ød1 l Description Shut-off damper with motor shelf HYLLA DTH2U. Consists of a DTU damper with motor shelf HYLLA DTHU2U added. The damper has neither any cup nor any knob, and has a longer spindle to avoid the need for extension spindle VREDF. The damper is designed to have a motor…
-
DIRBU
Dimensions 1 l3 2 Ød1 Description The motor-driven damper DIRBU with flow meter is suitable for systems where it should be possible to increase the air flow or lower it to the basic level. Examples of such systems are conference rooms and public areas. It fulfils tightness class C. DIRBU is intended…
-
DIRBU
Technical data for the motors 1 Power supply Power consumption For wire sizing Connection Operating angle Torque at rated voltage Direction of rotation Position indication Running time for 95° Sound power level Protection class Protection type Ambient temperature range Ambient moisture LM 24 A LM…
-
DIRVU
Dimensions 1 l3 2 Ød1 Description The motor-driven damper DIRVU with flow meter is suitable for systems where it should possible to vary the air flow. Examples of such systems are conference rooms and public areas. It fulfils tightness class C. Maximum and minimum flow is set with the measurement…
-
DIRVU
Technical data for the motor 1 Power supply Power consumption For wire sizing Connection Operating angle Torque at rated voltage Direction of rotation Position indication Running time for 95° Sound power level Protection class Protection type Ambient temperature range Ambient moisture LM 24 A-SR AC…
-
DSUSN
Dimensions 1 2 Ød1 3 4 l Description Shut-off or regulating damper. With internal Belimo-motor and blade combination type CM … D, with plastic blade, specially suitable where space is limited. The housing fulfills tightness class D. For systems with low requirements at shut-off capacity. With…
-
Regulating damper with
motor DSVUSN Dimensions 1 2 Ød1 3 4 l 5 Description 6 Shut-off or regulating damper. With internal Belimo-motor and blade combination type CM … D, with plastic blade, specially suitable where space is limited. The housing fulfills tightness class D. For systems with low requirements at shut-off…
-
DTBU
Dimensions Ød1 l Description Shut-off damper with electric motor – LM 24 A-F or LM 230 A-F Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has reached…
-
DTBU
Dimensions Ød1 3 4 l 5 Description 6 Shut-off damper with electric motor – NM 24 A-F or NM 230 A-F Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has…
-
DTBU
Dimensions Ød1 l Description Shut-off damper with electric motor – SM 24 A or SM 230 A Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has reached its…
-
DTBU
Dimensions 1 2 Ød1 l Description 6 Shut-off damper with electric motor – GM 24 A or GM 230 A Consists of a DTU damper with a 24 or 230 V electric motor added. Ø900 and 1000 has two motors. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops…
-
DTBCU
Dimensions Ød1 4 5 l Description Shut-off damper with spring return motor – TF 24 or TF 230 Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has…
-
DTBCU
Dimensions Ød1 l Description 6 Shut-off damper with spring return motor – LF 24 or LF 230 Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has reached…
-
DTBCU
Dimensions Ø Ød1 l Shut-off damper with spring return motor – SF 24A or SF 230A Consists of a DTU damper with a 24 or 230 V electric motor added. The motor is controlled by a single-pole breaking contact. The motor has overload protection and stops automatically when the blade has reached its end…
-
таблицы и схемы — в просмотре
-
fastrunning motor
DTFU Dimensions Ød1 3 4 l 5 Description Shut-off damper with electric motor LMQ 24A or LMQ 24ASR. Consists of a DTU damper with a 24 V electric motor added. 1) Motor LMQ 24A is a fast-running reversing on/off-motor, suitable for extraction at working places where a fast operation is wanted. 2) Motor…
-
таблицы и схемы — в просмотре
-
DTBLU
Dimensions Ød1 3 4 l 5 Description 6 Shut-off damper with electric motor CM 24 F or CM 230 F. Consists of a DTU damper with a 24 or 230 V motor added. Has a low height to fit at narrow spaces. In outdoor installation, the motor should be protected from direct UV radiation. There is a separate…
-
DTBLU
Dimensions Ød1 l Description Shut-off damper with electric motor LM 24 A-F or LM 230 A-F. Consists of a DTU damper with a 24 or 230 V motor added. Has a low height to fit at narrow spaces. In outdoor installation, the motor should be protected from direct UV radiation. There is a separate assembly…
-
DTPU
Dimensions 105 B 1 H 2 3 Ød1 4 5 l Description Shut-off damper with pneumatic actuator Consists of a DTU damper with a pneumatic actuator installed. The actuator consists of a glass-reinforced polyamide housing with an internal rolling diaphragm to which the spindle is fixed. When air pressure…
-
DTPU
Dimensions B 1 H 2 105 Ød1 l 6 Description 7 Shut-off damper with pneumatic actuator Consists of a DTU damper with a pneumatic actuator installed. The actuator consists of a glass-reinforced polyamide housing with an internal rolling diaphragm to which the spindle is fixed. When air pressure rises…
-
DTPU
Dimensions 105 1 B 2 3 Ød1 4 5 Description 6 Shut-off damper with pneumatic actuator Consists of a DTU damper with a pneumatic actuator installed. The actuator consists of a glass-reinforced polyamide housing with an internal rolling diaphragm to which the spindle is fixed. When air pressure rises…
-
Cleaning regulating
damper PSDRU Dimensions 1 140 Ød3 100 H 2 3 Ød Description Cleaning regulating damper Consists of a KCU cleaning cover with a blade without rubber gasket similar to the DRU and a PSU collar saddle in whose branch the cleaning cover is fixed. The branch is provided with a Safe seal. Since it is easy…
-
Cleaning regulating
damper TDRU Dimensions 1 140 Ød3 100 H 2 Ød1 l Description Cleaning regulating damper Consists of a KCU cleaning cover with a blade without rubber gasket similar to the DRU and a TCPU T-piece in whose branch the cleaning cover is fixed. The branch is provided with a Safe seal. Since it is easy to…
-
Cleaning shut-off damper
TDSU Dimensions 1 140 Ød3 100 H 2 Ød1 l 6 Description 7 Cleaning shut-off damper Consists of a KCU cleaning cover with a blade with rubber gasket and a TCPU T-piece in whose branch the cleaning cover is fixed. The branch is provided with a Safe seal. Since it is easy to remove the cleaning cover…
-
Alternating shut-off
damper TASU Dimensions Ød1 l Ød3 l3 Description Alternating shut-off damper Consists of an extended T-piece and two linked DSU dampers. Can be used for "by pass" ducts. It thereby replaces two conventional dampers + two couplings + one T-piece and is 20–30% shorter. Ød1 nom Ød3 nom l mm l3 mm m kg…
-
Alternating shut-off
damper TATU Dimensions Ød1 l Ød3 l3 Description Alternating shut-off damper Consists of an extended T-piece and two linked DTU dampers. Can be used for "by pass" ducts. It thereby replaces two conventional dampers + two couplings + one T-piece and is 20–30% shorter. 9 10 Ød1 nom Ød3 nom l mm l3 mm m…
-
Motorized alternating shut-off
damper TATBU Dimensions 105 1 Ød1 2 3 l Ød3 4 l3 5 Description 6 Alternating shut-off damper with electric motor – NM 24 A-F or NM 230 A-F Consists of an extended T-piece with two linked DTU dampers and a 24 or 230 V electric motor installed. Can be used for "by pass" ducts. This means that it…
-
Motorized alternating
shut-off dampers TASU, TATU, TATBU Technical data 1 The dashed pressure drop curves refer to the flow direction in the right picture. 2000 [l/s] 1000 [Pa] 5 Ø [mm] 50 Δ pt 1000 q We reserve the right to make changes without prior notice 5000 [m3/h]
-
variable flow damper 1 Disturbance tolerance In order to achieve the stated accuracy for the pre-set flow a straight distance of at least 3×d before and at least 1,5×d after the units are required. A mounting close to a source of disturbance (bend, saddle etc.) decreases the regulation accuracy and…
-
variable flow damper 1 2 Technical data Pressure and flow ranges and sound to the surroundings Ø 100 v 5 [Pa] 10 1000 The graphs show A-weighted sound power level, LWA [dB], to the surroundings. With insulation shell around the unit (the DALU unit) the Aweighted sound pressure level in the mittle of…
-
DAU
Dimensions B 122 Ød1 3 4 l 5 Description Constant flow damper with manual setting of one flow DAU is a constant flow damper, which facilitates balancing of ventilation systems and gives correct flow from the start. The unit compensates for e.g. connection and disconnection of system parts, clogging…
-
DA2EU
Dimensions 1 B 130 2 Ød1 3 4 l 5 Description Constant flow damper with electric motor for switching between two flows DA2EU is a constant flow damper, which facilitates balancing of ventilation systems and gives correct flow from the start. The unit compensates for e.g. connection and disconnection…
-
DAVU
Dimensions 1 B 130 2 Ød1 3 4 l Description Constant flow damper with electric motor for continuous setting of one flow DAVU is a constant flow damper, which facilitates balancing of ventilation systems and gives correct flow from the start. The unit compensates for e.g. connection and disconnection…
-
LKSR
Dimensions 1 b 2 l 3 4 a 5 Description 6 Rectangular regulating damper Consists of a duct with trapezoid corrugations and a turning blade. Blade angle can be adjusted 0–90° using the knob in the cup, and blade angle is read from an embossed scale on the edge of the cup. Locking is done by two…
-
lindab | i sol
Damper DRUI Dimensions 1 Ød1 l 5 6 Description 25 mm insulation. Regulating damper, insulated. 7 Technical data according to DRU. Ød1 nom l mm m kg Sealing class past closed blade 100 100 1,00 1,10 1,30 1,40 1,80 2,50 2,90 3,10 3,60 4,30 5,30 6,20 0 Ød1 nom l mm m kg Sealing class past closed blade…
-
Sliding damper – manual
SKMTR Dimensions Ød 1 Ø 80 – 200 l 2 B 3 4 H1 5 H2 Description 6 Ød 7 l Manual shut-off sliding damper with transfer joint The damper meets the requirements for tightness class 4 at pressure class C. Ø 224 – 400 The damper meets the requirements for tightness class C only in fully closed or fully…
-
Sliding damper – pneumatic
SKPTR Dimensions 1 Ød l 2 B 3 4 H1 5 H2 6 Description 7 Pneumatic shut-off sliding damper with transfer joint The damper meets the requirements for tightness class 4 at pressure class C. 8 The damper meets the requirements for tightness class C only in fully closed or fully opened position.…
-
Air stream operated damper
CARU Dimensions 1 Ød1 l 5 Description The damper is used where you want an efficient closing at a standstill fan. The air stream operated damper is equipped with springs, which automatically close the damper when the fan stops. The housing is manufactured of galvanized sheet metal. The butterfly…
-
Air stream operated damper
CAR Dimensions 1 2 H 3 4 Ød Description The damper is used where you want an efficient closing at a standstill fan. The air stream operated damper is equipped with springs, which automatically close the damper when the fan stops. The damper is easy to mount since it is only "pushed" into the duct.…
-
FMDRU
Dimensions 1 2 Ødi Ød1 3 4 l Description Applications The flow meter is suitable both for setting up and for continous flow measurement. It is intended for permanent installation and must therefore be specified at the design stage. 5 Ød1 nom Ødi nom l mm m kg 0,78 0,94 1,21 There is a separate…
-
FMDRU
Technical data Flow graph for balancing The graph show the flow, q, as a function of the pressure difference in the measurement nozzles. Flow data for dimensioning differs from this graph. Measurement accuracy If the velocity profile is asymmetric, the measurement values can differ from the ideal…
-
таблицы и схемы — в просмотре
-
FMDRU
-
таблицы и схемы — в просмотре
-
FMDU
Dimensions 1 Ø 80–315 Ød1 l 5 6 Description 7 Applications The meter is suitable both for setting up and for continous flow measurement. It is intended for permanent installation and must therefore be specified at the design stage. 8 There is a separate assembly, measuring, balancing and maintenance…
-
FMDU
Technical data Flow graph for balancing The curves show the flow, q, as a function of the pressure difference in the measurement nozzles. Flow data for dimensioning differs from this graph. Measurement accuracy If the velocity profile is asymmetric, the measurement values can differ from the ideal…
-
таблицы и схемы — в просмотре
-
FMDU
-
таблицы и схемы — в просмотре
-
FMU
Dimensions 1 2 Ødi Ød1 3 4 l Description Applications The meter is suitable both for setting up and for continous flow measurement. It is intended for permanent installation and must therefore be specified at the design stage. 5 Ød1 nom Ødi nom l mm m kg 0,33 0,42 0,48 There is a separate assembly…
-
FMU
Technical data Pressure drop graph with sound data for dimensioning The solid lines give the pressure drop, Δp, as a function of flow, q. The dashed lines give the A-weighted sound power data, LWA, in dB to the duct. Flow data for balancing differ from this graph. Ød1 [mm] LWA [dB] Measurement…
-
таблицы и схемы — в просмотре
-
Measuring bend
MBU Dimensions 1 l 2 l rm 3 4 Ød1 r m ≈ 1·d 1 Description Applications The measuring bend is suitable both for balancing and for continous flow measurement. It is intended for permanent installation and must therefore be specified at the design stage. The measuring bend is a good choice, since bends…
-
Measuring bend
MBFU Dimensions 1 l 2 l 3 rm 4 Ød1 5 r m ≈ 0,9·d 1 Description Applications The measuring bend is suitable both for balancing and for continous flow measurement. It is intended for permanent installation and must therefore be specified at the design stage. The measuring bend is a good choice, since…
-
Measuring bends
MBU, MBFU Technical data 1 2 Pressure drop graph for dimensioning of MBU Measurement function By measuring the pressure difference, Δp, between the inner and outer bend radii, you can derive the flow in the duct by means of the equation on the units plate. Ød1 [mm] Measurement accuracy If the…
-
Accessories
DRHTG Insulation cup IK Ø100 If the insulation is thicker than 50 mm, there is a risk that the insulation will cover the knob cup and make it difficult to find or use. The insulation cup allows about 100 mm of insulation to be used at the same time as it gives good access to the damper knob. It is…