Инструкция на Компактные вентиляционные установки VTS серии VENTUS Platinium
Модели: VENTUS PLATINIUM VVSA11c–VVSA56c. Руководство по монтажу, эксплуатации и обслуживанию: безопасность, транспортировка и хранение, установка, подключения, автоматика и панели HMI, ввод в эксплуатацию, коды аварий, обслуживание. Документ на английском языке.
Загружаем документ…
Текст инструкции
-
Before starting the product installation, carefully read the manual
Installation work must be carried out in accordance with national electrical installation standards and only by authorized personnel. This installation manual must be retained for future reference after being read carefully. PL User Manual (Installation, Operation, and Maintenance) Compact Air…
-
HEALTH AND SAFETY INSTRUCTION (HSE)
Thorough review of this manual, as well as proper installation, commissioning, and operation of the air handling unit in accordance with the provided instructions and all applicable safety regulations, will lay a solid foundation for efficient, safe, and trouble-free operation of the device. This…
-
INSTALLATION, SERVICE, AND OPERATION
! ! ! ! ! ! ! ! ! ! ! ! BEFORE PERFORMING ANY WORK, DISCONNECT AND SECURE THE POWER SUPPLY TO PREVENT UNINTENTIONAL START-UP OF THE UNIT. SERVICE WORK MUST BE CLEARLY ANNOUNCED AND MARKED. THE UNIT IS FACTORY-CONFIGURED TO START AUTOMATICALLY WHEN THE POWER SUPPLY IS CONNECTED FOR THE FIRST TIME.…
-
ELECTRICAL INSTALLATION
! ! ! ! ! ! ! ! ALL ELECTRICAL WORK MUST BE CARRIED OUT BY A LICENSED ELECTRICIAN HOLDING AT MINIMUM THE FOLLOWING QUALIFICATIONS: o CERTIFICATE OF QUALIFICATION FOR OPERATION OF DEVICES, INSTALLATIONS, AND NETWORKS o CERTIFICATE OF QUALIFICATION FOR SUPERVISION OF DEVICES, INSTALLATIONS, AND…
-
WARNING! HOT SURFACES
! THE DEVICE CONTAINS COMPONENTS WITH POTENTIALLY HIGH SURFACE TEMPERATURES, SUCH AS HEAT EXCHANGERS, HEATING ELEMENTS, OR MOTOR HOUSINGS. DIRECT CONTACT WITH THESE PARTS MAY RESULT IN BURNS OR OTHER INJURIES. SPECIAL CARE MUST BE TAKEN – USE APPROPRIATE PROTECTIVE CLOTHING AND BEGIN SERVICE WORK…
-
RESIDUAL RISK
DURING THE DESIGN AND MANUFACTURING PROCESS, EVERY EFFORT WAS MADE TO MINIMIZE RISKS TO PEOPLE AND PROPERTY. HOWEVER, A CERTAIN LEVEL OF RISK MAY STILL EXIST, WHICH IS BEYOND THE MANUFACTURER'S CONTROL. • HAZARDS RESULTING FROM IMPROPER INSTALLATION AND ASSEMBLY: o INSTALLATION IN AREAS ACCESSIBLE…
-
FAULTS, REPAIRS, MODIFICATIONS
! ! ! ! ! ! IN THE EVENT OF A MALFUNCTION OR IMPROPER OPERATION, THE UNIT MUST BE IMMEDIATELY SHUT DOWN AND AN AUTHORIZED SERVICE PROVIDER MUST BE CONTACTED. ALL REPAIRS MUST BE CARRIED OUT BY THE MANUFACTURER’S AUTHORIZED SERVICE CENTER USING GENUINE SPARE PARTS ONLY. ROUTINE INSPECTIONS PERFORMED…
-
EMERGENCY SITUATIONS – FIRE
PROCEDURE IN THE EVENT OF A FIRE IN ELECTRICAL EQUIPMENT: STAY CALM – DON'T PANIC, ASSESS THE SITUATION. DISCONNECT POWER: • • IF POSSIBLE, TURN OFF THE POWER SUPPLY (E.G. BY TURNING OFF FUSES OR THE MAIN CIRCUIT BREAKER). DO NOT TOUCH THE DEVICE OR WIRES WITH BARE HANDS - THEY MAY STILL BE…
-
GENERAL INFORMATION VENTUS PLATINIUM floor-standing ventilation and air conditioning units can be installed indoors or outdoors. The units are designed to work with air duct systems that supply and extract air from rooms, according to the ventilation design and parameters specified in the unit…
-
AD
Air Damper FLX.CON Flexible connection IN Inlet (supply e.g. medium) OUT Outlet (return e.g. medium) The devices can be designed as right- or left-handed. The orientation of the device is determined by the direction of airflow in the supply air path (air outlet) relative to the side of the device…
-
MARKING OF AIR INLET AND OUTLET IN THE UNIT
VIEW FROM THE INSPECTION SIDE - RIGHT-HAND EXECUTION EA Air outlet for removing air from the room RA Intake of air extracted from the room. FA Fresh air intake RE Outlet of the air supplied to the room MARKING OF AIR INLET AND OUTLET IN THE UNIT VIEW FROM THE INSPECTION SIDE - LEFT-HAND VERSION RA…
-
BASE SECTIONS WITH HEAT RECUPERATION (COUNTER-FLOW HEXAGONAL
EXCHANGER) A – Optional electric heater, B – Optional water heater MARKING OF AIR INLET AND OUTLET IN THE UNIT VIEW FROM THE INSPECTION SIDE - RIGHT-HAND EXECUTION RA Intake of air extracted from the room. FA Fresh air intake EA Air outlet for removing air from the room RE Outlet of the air supplied…
-
TRANSPORT AND STORAGE Air handling units are packaged in a way that facilitates easy internal transport and storage at the installation site. Upon delivery, all components must be inspected for any potential transport damage. Detailed instructions can be found in the Delivery Inspection Checklist.…
-
! ! ! ! ! ! IMMEDIATELY UPON RECEIPT OF THE EQUIPMENT, CHECK THE CONDITION OF THE PACKAGING AND VERIFY THE COMPLETENESS OF THE DELIVERY BASED ON THE ATTACHED SPECIFICATIONS AND SHIPPING DOCUMENTS. A VISUAL INSPECTION MUST BE CARRIED OUT AFTER DELIVERY TO IDENTIFY ANY POTENTIAL DAMAGE. IN THE EVENT…
-
TRANSPORT GUIDELINES FOR AHU SECTIONS
Air handling units must be transported in the position and manner indicated on the original manufacturer’s packaging. Any deviation from the designated orientation or handling instructions may result in mechanical damage, loss of warranty, or improper functioning of the device. Always refer to…
-
! ! ! ! ! ! ! USE SPECIALIZED LIFTING EQUIPMENT TO LIFT THE UNIT. NEVER STAND UNDER A LIFTED UNIT. DESIGNATE AND MARK A HAZARD ZONE THAT MUST REMAIN CLEAR. TAKE THE UNIT'S WEIGHT INTO ACCOUNT DURING LIFTING OPERATIONS. ONLY LIFT TRANSPORT BLOCKS (BEFORE THEY ARE CONNECTED). USE CERTIFIED LIFTING…
-
THE EQUIPMENT AS WELL AS ITS COMPONENTS SHOULD BE
• STORED IN ROOMS WITH THE FOLLOWING CONDITIONS: o RELATIVE HUMIDITY: Φ < 80 %, AT T = (+20) °C, o AMBIENT TEMPERATURE: (-40) °C < T < (+60) °C. • PROTECTED FROM CONTACT WITH CORROSIVE (CAUSTIC) DUSTS, GASES OR VAPOURS, AS WELL AS WITH ANY OTHER CHEMICAL SUBSTANCES LIABLE TO HAVE A CORROSIVE EFFECT…
-
4.1 INSTALLING THE DEVICE PREPARING FOR INSTALLATION When choosing the installation location, make sure that after the device is installed there will be enough space to properly connect the technological and electrical installations to the device and to easily carry out maintenance of the device.…
-
DEVICE DIMENSIONS AND SERVICE SPACE
VVSA11c VVSA14c VVSA22c VVSA29c VVSA40c VVSA56c H 1082 1182 1295 1450 1598 1838 W (1) 1124 1284 1514 L (RRG) 2000 2000 2540 2811 2811 1752 L ( Hex ) Duct connection 2000 2000 2540 2811 2811 - Ø315 Ø 400 500x400 700x400 800x400 1000x500 RRG/HEX RRG/HEX RRG/HEX RRG/HEX RRG/HEX RRG/HEX 900/1205…
-
! ! ! ! ! ! ! DEVICE INSTALLATION THE AIR HANDLING UNIT MUST BE POSITIONED ON: • A FOUNDATION SLAB, • A STEEL FOUNDATION FRAME EMBEDDED IN THE FLOOR, • A SPECIALLY PREPARED RIGID STEEL STRUCTURE. THE FOUNDATION, FRAME OR STEEL STRUCTURE MUST BE FLAT, LEVEL AND SUFFICIENTLY STRONG TO SUPPORT THE…
-
CONDENSATE DRAINAGE Moisture from the air may condense on the surfaces of air coolers and heat recovery exchangers. Moisture condensed on the surfaces of the air cooler and heat recovery exchanger is collected in drip trays located below these components. To ensure proper condensate drainage: • The…
-
CONDENSATE DRAINAGE – SIPHON CONNECTION TO THE COOLING COIL SECTION
IMPORTANT CONDENSATE DRAINAGE REQUIREMENTS ! SIPHONS MUST BE INSTALLED ON DRIP TRAYS LOCATED ON THE SUCTION (NEGATIVE PRESSURE) SIDE OF THE FAN TO ENSURE PROPER OPERATION OF THE AIR HANDLING UNIT. ! IT IS RECOMMENDED TO INSTALL SIPHONS ALSO ON DRIP TRAYS LOCATED ON THE DISCHARGE (POSITIVE PRESSURE)…
-
FIXING THE UNIT TO THE FOUNDATION FIXING THE UNIT TO THE FOUNDATION ! ! ! ! The support feet must be fastened through the holes in the bottom part of each foot. All foot profiles of the air handling unit must be fully supported. Use M10 bolts or anchors to secure the frame to the foundation. The…
-
MOUNTING THE LEVELING FOOT
! ! ! ! ! ! Adjustable leveling feet are not permitted for outdoor installation. The leveling foot must be mounted using the designated holes located at the base of the foot. Ensure that the entire weight of the unit is evenly distributed across all installed leveling feet. The surface under the…
-
REQUIREMENTS FOR ON-SITE SECTION CONNECTIONS SECTION CONNECTION DISCLAIMER AND INSTALLATION REQUIREMENTS Section connection is not included in the standard VTS offering. However, it is possible to purchase an additional option for section connection performed by the Authorized VTS Service. Assembly…
-
CONNECTION OF BASE BLOCK SECTIONS POSITIONING CONNECTORS FOR BLOCKS IN SECTION VVSA29c–VVSA56c www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 29
-
BASE BLOCK SECTION CONNECTION RRG VVSA29c–VVSA56c
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 30
-
BASE BLOCK SECTION CONNECTION RRG VVSA29c–VVSA56c (cont.)
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 31
-
BASE BLOCK SECTION CONNECTION HEX VVSA29c–VVSA56c
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 32
-
BASE BLOCK SECTION CONNECTION HEX VVSA29c–VVSA56c (cont.)
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 33
-
BASE BLOCK INSTALLATION CONNECTION
The base configuration of the VENTUS PLATINIUM with heat recovery is delivered as a factorywired unit with a pre-connected and configured power supply and control system. In the case of base sections delivered in multiple transport modules, internal installations of the sections must be connected…
-
CONNECTION OF THE COOLING COIL SECTION CONNECTING THE COOLER BLOCK SECTIONS VVSA22c-VVSA56c The cooler section must be connected to the heat recovery block by means of an air duct. The air ducts are not included in the manufacturer's scope of supply. www.vtsgroup.com IOMM VENTUS PLATINIUM - ver.…
-
CONNECTION OF THE COOLING COIL SECTION WITH FLANGE VVSA22c-VVSA56c
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 36
-
CONNECTION OF THE COOLING COIL SECTION VVSA22c-VVSA56c (cont.)
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 37
-
INSTALLATION OF THE UNIT ROOF INSTALLATION OF THE UNIT ROOF Assembly Sequence www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 38
-
таблицы и схемы — в просмотре
-
INSTALLATION OF THE UNIT ROOF – COOLING COIL SECTION
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 41
-
INSTALLATION OF THE UNIT ROOF – COOLING COIL SECTION (cont.)
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 42
-
INSTALLATION OF THE UNIT ROOF – COOLING COIL SECTION (cont.)
INSTALLATION OF THE UNIT ROOF – COOLING COIL SECTION (cont.) www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 43
-
SLN.WSH
M5,3x12M www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 44
-
CABLE ENCLOSURE INSTALLATION (OUTDOOR UNIT) Screw the canopy in place using the holes in the enclosure. 4.3.8 HANDLE INSTALLATION www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 45
-
CONNECTION OF VENTILATION DUCTS AND DUCT ACCESSORIES CONNECTION OF ROUND VENTILATION DUCTS Ducts, accessories, and duct coolers intended for use with round air ducts shall be connected using sleeve couplings. Sleeve couplings for ventilation fittings are not included in the scope of supply. It is…
-
3 Fresh air intake/exhaust outlet Flexible connection (for duct connections) Air damper www.vtsgroup.com Sleeve Air duct (spiro) Self-drilling screw IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 47
-
RECTANGULAR AIR DUCT CONNECTIONS
1 2 Louvered Air Inlet/Outlet Air Damper ! ! ! ! ! Gasket Flexible Connection Air Duct Ventilation ducts should be connected to the air handling unit using flexible connectors (optional equipment), which help absorb vibrations from the unit and compensate for any misalignment between the duct…
-
5.1 CONNECTIONS OF THE UNIT HOT WATER HEATER AND CHILLED WATER COOLER CONNECTIONS WARNING ! ! ! ! ! ! ! ! THE OPERATION OF A WATER-BASED HEAT EXCHANGER REQUIRES CONNECTION TO THE PROCESS HEATING (OR COOLING) SYSTEM, DEPENDING ON THE INTENDED FUNCTION OF THE COIL. HEAT EXCHANGERS MUST BE PROTECTED…
-
REQUIREMENTS FOR THE MEDIUM SUPPLYING THE WATER COILS
! ! ! ! ! ! ! ! Oil and grease content: < 1 mg/l pH at +25°C: 8–9 Oxygen content: < 0.1 mg/l (as low as reasonably possible) Minimum cooler temperature: +3°C Maximum operating temperature: +130°C Maximum operating pressure: 16 bar If the return temperature of the medium may drop below 0°C, an…
-
PRINCIPLE OF POWERING WATER EXCHANGERS - HEATER
! a) The supply and return connections to the coil should be configured to ensure counterflow operation. Co-current (parallel) flow results in a lower mean temperature difference, which negatively affects the coil’s performance. b) a) Left-hand version b) Right-hand execution (1) Supplying the…
-
EXAMPLE OF WATER PIPING
When connecting exchangers equipped with screw connections, relieve the exchanger connector using an additional wrench. www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 52
-
WATER EXCHANGER POWER SUPPLY PRINCIPLE - COOLER
! a) The supply and return connections to the coil must be configured to ensure counterflow operation. Parallel flow operation results in a lower mean temperature difference, which reduces the coil’s overall efficiency. b) b) Left-hand version c) Right-hand execution (1) Supplying the exchanger with…
-
! ! ! ! ! ! ! ! ! CONNECTION OF DX (DIRECT EXPANSION) COILS The DX coil must be connected by a qualified refrigeration system installer in accordance with applicable standards and regulations for fluorinated gas systems (F-gas certification required). The DX coil is designed to operate with…
-
POWER SUPPLY PRINCIPLE OF DX EXCHANGERS (COOLERS, HEATERS)
! ! a) DX exchangers have copper connectors suitable for brazing. DX heat exchangers have capillary connections. When brazing or welding pipes, avoid exposing pipe components to high temperatures when making capillary connections and protecting the valve closest to the connection being made with a…
-
ELECTRICAL POWER CONNECTION The VENTUS PLATINIUM base unit, equipped with heat recovery (using either a counterflow hexagonal heat exchanger or a rotary heat exchanger), fans, and air filters, is delivered as a prewired unit. The power supply is connected to a designated connection point located…
-
CONTROL CABINET AND CABLE ENTRY SYSTEM
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 57
-
POWER AND CONTROL SWITCHBOARD
X0 Main power connection strip 380-415V 3N~ 50Hz X1 Internal power connection strip LFx Internal fan power supply connection strip, x LP Heater circulation water pump connection strip (up to 250W 230V N~) LR F1 Internal power supply connection strip for the rotary heat exchanger Connecting the power…
-
CONNECTING THE POWER SUPPLY OF THE UNIT WITH A ROTARY HEAT EXCHANGER
-
POWER CONNECTION OF THE UNIT WITH A COUNTER-FLOW (HEXAGONAL) HEAT EXCHANGER
-
таблицы и схемы — в просмотре
-
6.1 ELECTRIC HEATER GENERAL INFORMATION The electric heater is an optional component of the air handling unit. If the unit is delivered with an electric heater, the heater is factory-wired to the power supply point of the unit and integrated into the unit’s automation system. The electric heater…
-
HEATER SAFETY – CUT-OFF THERMAL SWITCH The thermal protection function is based on the properties of a bimetallic element – it opens the heater control circuit contacts when the air temperature near the cut-off thermal switch reaches 65°C. After an emergency shutdown, the heater is automatically…
-
HEATER SAFETY - DIFFERENTIAL PRESSURE SWITCH The differential pressure switch is an additional safety element, alongside the thermostat, which protects the heater from operating under improper conditions. It prevents the heater from being activated when the pressure generated by the supply fan…
-
таблицы и схемы — в просмотре
-
CONTROL SYSTEM The base unit of VENTUS PLATINIUM with heat recovery (either with a counterflow hexagonal exchanger or a rotary heat exchanger) is delivered as a pre-wired unit with a connected and configured automation system. The control system is based on a factory-programmed and integrated uPC3…
-
STANDARD CONTROL COMPONENTS – FACTORY ASSEMBLY
Designation Control Box Name uPC3 controller Terminal 1.1 (T1.1) Location Power and control switchboard (see: "Wiring Diagram") Connection terminal for peripheral control elements Security B2 Temperature sensor H2 (RH+T) Moisture transducer B3 Temperature sensor Return air from the room (exhaust…
-
CONNECTION TERMINAL 1.1 (T1.1) Terminal 1.1 (T1.1) is factory-connected to the uPC3 controller and it is a terminal dedicated to connecting field control components that are located outside the device's base unit and therefore cannot be connected at the factory. Additional control components not…
-
TEMPERATURE SENSORS
B1 B2 Duct air temperature sensor – air supplied to the room. The sensor is mounted and connected on site. The B1 sensor should be placed in the air supply duct after the last section of the air handling unit, in a place representative for temperature measurement (in a homogeneous air stream with…
-
AIR SUPPLY DUCT TEMPERATURE SENSOR B1
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 70
-
ANALOG INPUTS (NTC10K) ANALOG INPUTS (NTC10K) – CONNECTION TO TERMINAL T1.1 SENSORS www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 71
-
DIGITAL INPUTS DIGITAL INPUTS DI1 Fire alarm DI2* Heater alarm (freeze) DI3 Radiator alarm DI4 Humidifier alarm DI5 Cooling source alarm Remote Programmable external input (permission to operate the control panel or forcing the selected operating mode. DI2* - Heater alarm (freezing). In the absence…
-
FIRE ALARM FIRE ALARM If no fire alarm signal from an external source is connected, a jumper must be installed. www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 73
-
ANALOG OUTPUTS (0-10V DC) ANALOG OUTPUTS AO1 Heat recovery. Factory connection outside of Terminal 1.1 (T1.1) MainBoard AO2 Air mixing. AO3 Humidification or post-heater. AO4 Pre- or post-heater. Main heater or secondary heater after DX-H or mixing chamber. Priority: 1. Main heater, 2. Secondary…
-
MAIN WATER HEATER VALVE ACTUATOR AND ELECTRIC MAIN HEATER CONTROL SIGNAL Y1
MAIN WATER HEATER VALVE ACTUATOR www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 75
-
OUTPUTS (24V DC) DIGITAL OUTPUTS (24V DC) DO1 Main heater (or secondary heater if DX-H) DO2 Air inlet and outlet dampers DO3 Cooler Stage 1 or DX-H Signal DO4 Cooling/heating switching signal DO5 Cooler stage 2 DO6 Preheater or Reheater or General Alarm If it is necessary to use 230V AC voltage or…
-
CONNECTING THE CONDENSING UNIT SIGNALS DX EXCHANGER (0-10V CONTROL) DX EXCHANGER (ON-OFF CONTROL) www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 77
-
MODBUS RTU RS485 COMMUNICATION MODBUS RTU RS485 COMMUNICATION (1) Air humidity sensor – room (exhaust – factory installed) (2) Air humidity sensor - supply (3) Air humidity sensor (4) CO2 sensor (5) HMI Basic Panel www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 78
-
таблицы и схемы — в просмотре
-
COMMUNICATION WITH THE CONTROLLER The user can communicate with the controller using: • HMI Advanced (administration and service panel), • HMI Basic, • mHMI application (mobile HMI - Bluetooth), • mHMI application (mobile HMI - GSM), • via WIFI router (2.4 GHz), • by connecting directly to the…
-
BLUETOOTH MODULE (BT)
The module transmits the RS485 serial communication signal [Modbus RTU] from the main controller to a mobile device via Bluetooth, eliminating the need for a communication cable. To control the air handling unit with VTS automation using the Bluetooth module, the dedicated mHMI application must be…
-
STARTING THE BLUETOOTH MODULE
• • • • Remove the cover of the unit’s connection box. Locate the button on the Bluetooth (BT) module and press it until the LED starts flashing. This indicates that the BT module is in pairing mode. Next, open the application and pair the air handling unit with the app. The pairing mode remains…
-
UPC3 CONTROLLER CONFIGURATION – mHMI and HMI ADVANCED
• "Address" – the controller address used for communication using an external protocol • "Speed" – speed ( baudrate ) of the external controller protocol • pLan controller external port " – type of protocol used by the controller pLan port (RJ11 socket) For mHMI , the pLan port parameter value…
-
WIRED COMMUNICATION WITH THE CONTROLLER WIRED COMMUNICATION WITH THE AHU CONTROLLER • Default address: 192.168.1.111/24. • Please enter the address: o 192.168.1.111 or o 192.168.1.111:80 • After entering 192.168.1.111:80 (http) the service interface will appear (default Login: admin, Password…
-
таблицы и схемы — в просмотре
-
9.1 HMI PANELS HMI ADVANCED HMI ADVANCED (SERVICE AND ADMIN HUMAN MACHINE INTERFACE) The electrical connection should be made using a 6-conductor telephone cable with RJ12 connectors on both ends. Using a different plug standard may damage the socket. www.vtsgroup.com IOMM VENTUS PLATINIUM - ver.…
-
HMI BASIC (2HY) HMI BASIC 2HY The HMI is powered by a 110-230V AC mains voltage. To ensure proper operation, separate power and control cables should be used, not exceeding the recommended length of 500m. The following cable types are recommended: • power supply: H05VV-F 2x1 mm 2 • communication…
-
mHMI APPLICATION – DEVICE REGISTRATION To pair your device with BT, see the section "WIRELESS COMMUNICATION" mHMI APPLICATION • • • Download the mHMI application from one of the Play App services Store or Apple App Store Create an account in the app Add device via Bluetooth ADDING A DEVICE If the…
-
таблицы и схемы — в просмотре
-
10 FIRST START-UP OF THE UNIT
10.1 PREPARATION FOR FIRST START-UP ! ! ! ! ! BEFORE CARRYING OUT ANY PROCEDURES RELATED TO FIRST START-UP, MAKE SURE TO READ THE OPERATOR PANEL USER MANUAL. THE AIR HANDLING UNIT MAY ONLY OPERATE WITH FILTERS PROPERLY INSTALLED. AFTER THE INITIAL HOURS OF OPERATION, AIR FILTERS MUST BE REPLACED…
-
PRE-START ACTIVITIES (continued)
Grounding installation Check whether grounding cables are installed, including grounding for the ventilation ducts. Condensate installation Verify that siphons and condensate drainage systems from the condensate tray are properly installed. Automation peripherals Check the connections of peripheral…
-
FIRST START-UP 10.2.1 FACTORY SETTINGS A unit delivered in the Plug&Play standard comes with preconfigured control automation, set according to the parameters and criteria specified in the unit’s selection sheet. To start the unit in factory default mode, no additional on-site configuration is…
-
BASIC FACTORY CONFIGURATION – WORKING PROFILES (MODE)
OPERATION PROFILES PARAMETER Comfort** Economy StandBy Temperature T °C Relative humidity - RH RH* % Air quality - CO2 content ppm ppm Airflow efficiency V S* % m3/h 100 60*** 60*** Exhaust efficiency V E* % m3/h 100 60*** 60*** • • • • • Work profiles: Comfort, Economic require setting the time and…
-
10.2.2 UNIT COMMISSIONING
UNIT COMMISSIONING ! THE UNIT IS FACTORYCONFIGURED TO START AUTOMATICALLY WHEN ELECTRICAL POWER IS CONNECTED FOR THE FIRST TIME. Turn on the power to the control panel Turn on HMI Advanced (virtual http:/192.168.1.111) Changing the device status (operating mode) OFF ECO HE Toggle OFF mode to any…
-
• • Unit start-up is strictly blocked by the following events: activation of the fire protection alarm, triggering of the fan motor thermal protection, three consecutive activations of the electric heater protection, or three consecutive activations of the antifreeze thermostat. Each of these events…
-
10.2.4 HMI ADVANCED
NAVIGATION IN THE HMI ADVANCED PANEL A 1 "Alarm" button (displays active and archived alarms, clears alarms). When an alarm is active, the button is highlighted in red. ! Button to change operating modes (OFF/Auto/Low/Economy/Comfort). Confirm with ENTER ESC button (return to previous field or…
-
Current date and time. 7 Current job profile 8 9 Current fan control Status of the ventilation unit (fan operation/stop, heating/cooling, recovery activation) Current value of the leading temperature The set value of the leading temperature Working status icon: Opening/closing throttles Fan…
-
10.2.5 HMI BASIC 2HY
HMI BASIC 2 HY The HMI Basic 2 HY is a basic control panel designed to operate VTS air handling units equipped with the uPC3 controller. It offers the following functions: • starting and stopping the control panel, • selection of operating mode, • ability to view and change parameters of individual…
-
BUTTON
FUNCTION change the operating mode / go to the settings menu / return to the previous menu confirming the selection / moving to the next setting parameters / returning to the general settings menu switching between displayed temperatures / exiting to the main screen / turning off the screen changing…
-
• supply fan speeds (S),
• exhaust fan speeds (E). Access to individual settings depends on the configuration of the control panel and its actual components. We make changes using approval with Exit to the main screen occurs automatically after a moment of inactivity or after pressing SETTING THE CONTROL UNIT'S OPERATION…
-
The MI Basic 2 HY allows you to view and clear active alarms. When an alarm is present, a bell
symbol appears on the main screen, and the alarm number is displayed instead of the time. To clear the alarm, after removing its causes, press and hold . PROGRAMMING MODE When the display is turned off by holding the button, hold the button to enter the programming mode (changing advanced…
-
10.2.6 mHMI APPLICATION
AHU COMMISSIONING Select the paired device Then, in the menu, choose one of the operating modes: Eco, Comfort, Standby, or Auto (under the “On” operating mode) Save your selection The application includes a tutorial for pairing and connecting the device. www.vtsgroup.com IOMM VENTUS PLATINIUM - ver.…
-
10.2.7 VERIFICATION OF OPERATION DURING FIRST START-UP
During the first start-up, it is recommended to perform the steps listed below. CHECKING THE OPERATION OF THE FANS Check that the fans are not generating excessive noise. Ensure that the impeller is not rubbing against the inlet cone and that there are no foreign objects within the fan’s operating…
-
CHECKING THE SENSOR READINGS
• Check whether the readings from temperature, pressure, CO₂, and humidity sensors are correct. Initially, when the air handling unit is powered but not yet running, temperature sensors should report values close to the ambient air temperature inside the unit. Other transmitters and sensors should…
-
VERIFICATION OF WATER HEATING VALVE ACTUATOR FUNCTIONALITY
Check whether the water heater valve actuator responds to the control signal. Manually control the valve from the service menu of the controller and observe whether it opens and closes accordingly. To perform this operation, set parameter D to ON and parameter A to the desired percentage value on…
-
• • adjusting the duct network, modifying the setting of control dampers, changing the fan speed www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 106
-
10.2.9 THE MOST COMMON ADAPTATION CHANGES OF PARAMETERS TO
THE NEEDS OF THE FACILITY A full description of the uPC3 controller masks is available in the dedicated manual "AHU uPC3 Description of the upc3 Controller Masks" FUNCTION MAIN HEATER SCREEN SCOPE OF CHANGES WHEN TO CHANGE A07 PID unstable temperature control DXH MAIN A11 compressor activation…
-
DXH SECONDARY
A14 compressor operating time settings DXH PRELIMINARY A18 compressor operating time settings CENTRAL A21 next min supply temp and off delay SCREEN SCOPE OF CHANGES PRE-HEATER A29 support for supply air heating CENTRAL A21 DX MAIN B04 object sensitive to low airflow temperature next min supply temp…
-
PREHEATERS
G11 work permit output logic matching the heater properties AFTERHEATER REDUN. VENT. DAMP. FILTER PRESSURE CONVERTER ADDITIONAL FILTERS ADDITIONAL FILTERS G11 work permit output logic matching the properties of the humidifier G11 work permit output logic adjustment to throttle control properties.…
-
11 MAINTENANCE AND SERVICING
DANGER ! 11.1 !THE PERSONNEL RESPONSIBLE FOR THE OPERATION OF THE AIR HANDLING UNIT MUST READ THE DOCUMENTATION BEFORE CARRYING OUT ANY OPERATION OR MAINTENANCE ACTIVITIES. IF NO SUCH PERSONNEL WITH THE REQUIRED SKILLS AND COMPETENCIES ARE AVAILABLE, PERIODIC INSPECTIONS SHOULD BE CARRIED OUT BY…
-
Casing of the
handling unit Air fans Water heater Water cooler DX cooler Electric heater www.vtsgroup.com air • Inspect the condition of the gaskets. • Gaskets must not show signs of aging or permanent deformation. They must adhere securely to the inspection panels. If non-compliant, replace the faulty panels. •…
-
• At least every 4 months
• Checking the general condition of the exchanger, • Check the condition of the fins (whether they are damaged or bent). If necessary, restore them to their factory condition. If repair is not possible, replace the heat exchanger with a new one. • Cleaning the exchanger, especially the space between…
-
Intakes, exhausts,
ventilation ducts • Cleaning of air intakes, exhaust vents, and ventilation ducts • Every 3–5 years (or more frequently in the case of polluted environments or dusty facilities). • In facilities requiring high cleanliness (e.g. hospitals, laboratories): more often – according to industry standards.…
-
AIR FILTERS WARNING ! ! ! A SIGNIFICANT AMOUNT OF FINE DUST OR PARTICULATE MATTER HARMFUL TO HEALTH MAY ACCUMULATE ON THE FILTERS. EXERCISE CAUTION WHEN REPLACING FILTERS. CONTAMINATED FILTERS CAUSE INCREASED POWER CONSUMPTION OF FAN MOTORS CONTAMINATED FILTERS MAY LEAD TO DAMAGE TO THE AIR HANDLING…
-
WATER HEATER DANGER ! ! BE CAREFUL AROUND THE HOT SURFACE OF THE HEATER. BE CAREFUL WHEN CONNECTING THE WATER PIPELINE. THERE IS A RISK OF DAMAGE TO MATERIAL OR WATER HEATER. WATER HEATER • • • • • Active water heaters should be equipped with anti-freeze systems. Optionally, a non-freezing heating…
-
ELECTRIC HEATER WARNING ! ! BE CAREFUL AROUND THE HOT SURFACE OF THE HEATER WET CLEANING OF ELECTRIC HEATERS IS PROHIBITED ELECTRIC HEATER • • • During air handling unit operation, when the heater is turned off, dust may settle on the heating coils. When the heater is turned on again, heavy…
-
DX EXCHANGERS DX HEATERS AND COOLERS (DIRECT EXPANSION COILS) • Freon radiator maintenance involves the same steps as the heater and water cooler maintenance. Before washing the Freon radiator with warm water, the cooling system should be drained by draining the Freon into a container. Otherwise…
-
ROTARY EXCHANGER WARNING ! THE HEAT RECOVERY EXCHANGER IS HEAVY, BE CAREFUL WHEN MOVING THE EXCHANGER. THERE IS A RISK OF INJURY TO PERSONS OR DAMAGE TO THE HEAT RECOVERY EXCHANGER. ROTARY EXCHANGER • • • • • • When performing maintenance on the rotary heat exchanger, check that: o The rotor rotates…
-
HEAT RECUPERATOR WARNING ! ! THE HEAT RECOVERY EXCHANGER IS HEAVY, BE CAREFUL WHEN MOVING THE EXCHANGER. THERE IS A RISK OF INJURING PERSONS OR DAMAGE TO THE HEAT RECOVERY EXCHANGER. HEAT RECUPERATOR (COUNTER-FLOW-HEXAGONAL) Maintaining the heat exchanger involves checking its technical condition…
-
DISASSEMBLY OF THE HEXAGONAL EXCHANGER 1/4
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 120
-
DISASSEMBLY OF THE 2/4 HEXAGONAL EXCHANGER
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 121
-
DISASSEMBLY OF THE 3/4 HEXAGONAL EXCHANGER
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 122
-
DISASSEMBLY OF THE 4/4 HEXAGONAL EXCHANGER
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 123
-
ATTENUATORS (BAFFLE-TYPE ATTENUATORS) SOUND ATTENUATORS (BAFFLE-TYPE ATTENUATORS) The muffler section is equipped with non-flammable mineral wool baffles that absorb acoustic energy. Maintenance procedures include checking the contamination levels of these baffles. 11.9 FAN ASSEMBLY FAN ASSEMBLY • •…
-
vacuum cleaner or compressed air - ideal for removing dust and dirt without
touching the surface, ▪ using microfiber cloth soaked in a solution of isopropyl alcohol (IPA) and distilled water (a 1:1 mixture of 70%-90% isopropyl alcohol and distilled water). The alcohol evaporates quickly, leaves no streaks, and does not damage aluminum, ▪ using an antistatic brush - allows…
-
11.10 ELECTRICAL INSTALLATION
ELECTRICAL INSTALLATION INSTALLATION OVERVIEW. It is recommended to check the condition of the electrical installation at least once a year, including: • perform a visual inspection of the cables, plugs, terminal blocks and connections in the control cabinet. • check the condition and mounting of…
-
11.12 MAINTENANCE OF THE UNIT CASING
MAGNELIS® COATING The unit's casing is made of sandwich panels. The panels are made of 50 mm thick rock wool (mineral wool) insulation, covered on both sides with sheet metal. The sheet metal is coated with Magnelis®. Magnelis® is an advanced metallic coating composed primarily of zinc (Zn)…
-
RECOMMENDED CLEANING PROCEDURE
• Rinse the surface with lukewarm water (+30°C ÷ +40°C). • Apply cleanser.: o mild detergent: e.g. diluted dishwashing liquid or, o cleaning agents for metal or stainless-steel surfaces (but without chlorine and acids!) or, o non-corrosive metal cleaning products (sometimes available as "galvanized…
-
11.13 CONSUMABLE MATERIALS
-
таблицы и схемы — в просмотре
-
12 ELECTRIC DIAGRAMS
12.1 POWER SUPPLY DIAGRAM FOR VENTUS PLATINIUM WITH ROTARY HEAT EXCHANGER (230V AC MOTORS) 12.1.1 VENTUS PLATINIUM (RRG, motors 230V) – 1/2 www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 131
-
12.1.2 VENTUS PLATINIUM (RRG, motors 230V) – 2/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 132
-
12.1.3 VENTUS PLATINIUM (RRG, motors 400V AC) – 1/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 133
-
12.1.4 VENTUS PLATINIUM (RRG, motors 400V AC) – 2/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 134
-
VENTUS PLATINIUM POWER SUPPLY DIAGRAM WITH HEX EXCHANGER 12.2.1 VENTUS PLATINIUM (HEX, motors 230V AC) – 1/2 www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 135
-
12.2.2 VENTUS PLATINIUM (HEX, motors 230V AC) – 2/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 136
-
12.2.3 VENTUS PLATINIUM (HEX, motors 400V AC) – 1/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 137
-
12.2.4 VENTUS PLATINIUM (HEX, motors 400V AC) – 2/2
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 138
-
CONTROL SYSTEM DIAGRAM 12.3.1 VENTUS PLATINIUM CONTROLS - 1/3 www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 139
-
12.3.2 VENTUS PLATINIUM CONTROLS – 2/3
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 140
-
12.3.3 VENTUS PLATINIUM CONTROLS – 3/3
www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 141
-
ELECTRIC HEATER WIRING DIAGRAM 12.4.1 3kW ELECTRIC HEATER www.vtsgroup.com IOMM VENTUS PLATINIUM - ver. 6.0.9 (06.2026) 142
-
| vb | 5
-
таблицы и схемы — в просмотре
-
13 ADDITIONAL INFORMATION
13.1 TECHNICAL INFORMATION ACCORDING TO REGULATION (EU) No 327/2011 IMPLEMENTING DIRECTIVE 2009/125/EC FANS TYPE SR-FS #8 #1 #4 #9-1 #9-2 #9-3 #10 #11 [%] [%] [-] [kW] [m³/h] [Pa] [rpm] SR-FS-P-250-EAOB75 61.0 74.1 58.9 0,712 1813 SR-FS-P-250-EAOB11 63.6 73.7 61.0 1,07 2039 1159 4000 SR-FS-P-315-1.5…
-
RELATED MANUALS It is necessary to familiarize yourself with the detailed manuals and perform all connections and configurations in accordance with the documentation available at www.vtsgroup.com, as well as the manuals provided with the equipment. In particular, please refer to the following…
-
GENERAL DISMANTLING PROCEDURE
• Disconnect all utilities (power supply, water, refrigerant lines, etc.). • Remove heating and cooling media from the system. • Dismantle inspection panels. • Dismantle electrical and control systems. • Remove all accessories and components from the air handling unit. • Dismantle components…
-
NOTES Routine inspections carried out by qualified technical personnel or service teams authorized by VTS ensure long-term, reliable, and trouble-free operation of the equipment. Our service staff is always available to provide support during commissioning, maintenance, or in the event of any…
-