2022 VENTUS PRO AIR HANDLING UNITS OPERATION, INSTALLATION AND MAINTENANCE MANUAL OIMM – VENTUS PRO Ver. 1.0.0 (31-05-2022)
-
CONTENTS
1 GENERAL INFORMATION AND SAFETY INSTRUCTIONS 3 2 TRANSPORT AND STORAGE 4 3 FOUNDATION, ASSEMBLY, CONNECTION OF UNIT-RELATED SYSTEMS 5 3.1 AHU SUPPLIED IN SECTIONS 5 3.2 AHU SUPPLIED IN PACKAGES FOR ASSEMBLY ON SITE 5 3.3 AMBIENT CONDITIONS FOR AHU INSTALLATION / WARUNKI ZEWNĘTRZNE 3.4 DO PRACY…
-
GENERAL INFORMATION AND SAFETY INSTRUCTIONS In-depth familiarization with the content of this manual, assembly and operation of the air-handling unit in line with the instructions provided and obeying all safety regulations constitute the basis of efficient, safe and nonfailure operation of the…
-
TRANSPORT AND STORAGE The VENTUS PRO can be delivered as fully assembled, assembled in sections or in packages, placed on closed palettes, containing elements to be assembled on-site by the Manufacturer Authorized Service. This manual does not contain instructions and guidelines on assembly of the…
-
3.1 FOUNDATION, ASSEMBLY, CONNECTION OF UNIT-RELATED SYSTEMS AHU SUPPLIED IN SECTIONS ! ! Sections connection is out of the standard offer of VTS. It is possible to purchase additional option to connect to the section by Authorized Service VTS. ! When the customer connect the section by himself…
-
If a unit operates with the low inlet temperature of the air, it is recommended to use the mixture of the glycol (up to 45%) as the heating medium. All installation pipes of the water heating, condensate drying, hydraulic valves should be well isolated. It is recommended to use the pre-heater before…
-
• put into service a clean AHU labelled with provided pictograms and VTS labels, ready to be connected to a power source (wiring), utilities and control systems, • hand control elements over to the client’s representative if at his request they were not assembled in the AHU, • hand a filled in…
-
The outlet condensate connections, led outside the AHU’s casing are assembled in the drain plates of coolers, counter–flow heat exchangers (the diameter of drain pan connection pipe is 32mm). To avoid damage drain pipe of the counter-flow heat exchanger section during transportation, they are not…
-
» TYPICAL AHU CONCRETE BASE
Height of the foundation slab or base frame must allow for assembly of the u-trap which drains the condensate out of the draining tray. In case of the drain plates installed in the lower AHU sections, the unit has to be mounted onto additional foundation slab or a special hollow must be made…
-
! Appropriate operation of the flexible connection occurs if it is stretched to about 110 mm. ! The ducts connected to the AHU have to be suspended or underpinned with dedicated support elements. Conducting the ducts with the fittings should be done in a way to eliminate possible increase of noise…
-
» RULES DUCTED OUTLET CONNECTIONS WITH DIRECTION CHANGE
3.6.2 PIPING CONNECTIONS Coils should be piped in counter flow arrangement to achieve required capacity. This arrangement requires that the entering heating or cooling fluid contacts the air leaving the coil. ! ! The diameter of the connection and the type of connection of the exchanger are…
-
» COIL CONNECTION RULES
• Hydronic • Steam » COIL INSTALLATION – HYDRONIC COILS » COIL INSTALLATION – STEAM COILS OIMM – VENTUS PRO 12
-
CONDENSATE DRAIN LINES Moisture condensed out of the airstream on cooling or dehumidifying coils should be drained out from the unit in order to sustain the proper use of the air handling unit and the ductwork system. Following precautions should be observed in piping of condensate drain lines. ! !…
-
! Electrical installation and wiring works should be carried out by qualified and competent electricians. ! In case of the humidifier, frequency converter, electric heater, EC motor applications their own installation and connection manuals should be used. For the other equipment the installation…
-
! Before connecting the fan set one should check carefully the rated parameters of both power supply and the converter’s output. ! In fan sections equipped with more than one fan synchronous operation of fans should be ensured. The fan control system should be prepared in such a way so as to provide…
-
» THERMAL OVERLOAD RELAY SETTING
Fans' motors with belt drive are powered by 3x400V/50Hz voltage. The connection should be done through the overload and short-circuit protection suitable for rated current of the motor. • direct-on-line starting: The thermal overload really should preferably be set to the motor full load current…
-
INTERMEDIATE FAN DRIVE – 2-SPEED AC MOTOR
Dahlander pole changing motor – switch (2-speed) 3.7 SETTING UP OF COMPONENTS 3.7.1 CONTROL SYSTEM ! 3.7.2 Pole chnager with two separate windings (2-speed) ! Complete automatic control which should be an integral part of each air-conditioning system, enables continuous operation of a device, in…
-
AIR FILTERS Panel filters and zigzag filters are normally fitted within the unit prior to shipping. Bag filters are normally shipped in closed carton boxes to avoid any collection of dust and loss of efficiency prior to commissioning. Each bag filter is housed within a special holding frame with…
-
HUMIDIFIERS Mat type or steam type humidifiers may be assembled in the unit. For the piping and wiring instructions please refer to humidifier manufacturer’s manual. The supply water, overflow / drain piping should be done before the start-up of mat type. The supply piping should have a valve for…
-
USE OF THE UNIT KLS air handling unit are used for heating, ventilating and air conditioning purposes. Any other use is considered not in conformity with general provisions. The manufacturer is not responsible for damages resulting; the user will be the only responsible. ! ! Air handling units can…
-
PREVENT OF COMMON DANGERS AND RISKS Air handling units are supplied with locked access doors as an option. So, unauthorized persons are not permitted to enter the sections which represent a danger. The most important potential dangers for life and health are described below. The units are…
-
THE HIDDEN DANGER In addition to the dangers of rotation machinery, fans present another potential danger by virtue of their ability to draw in loose material. Solid objects passing through a fan represent potentially dangerous projectiles. Solid objects can cause fan failure by physically damaging…
-
» OPERATIONS OF FANS
• check that pulleys are secure on shafts, • check tightness of belts, • check that all moving parts of the fan and motor are free to rotate, • check that no loose materials are left near the fan inlet, • check that direction of impeller rotation is correct. For this, momentarily energize the fan…
-
» AFTER TWO WEEK OPERATION
After start up and initial satisfactory operation of two weeks, it is recommended to have the following checks: • belt drive alignment and belt tension, • motor running current, • bearing temperature immediately after stop. Bearing temperature should not exceed 70C, • lubricate if necessary, •…
-
MAINTENANCE
ONCE A WEEK Check the conditions of filters every week. Clean, wash or replace if necessary. ONCE A MONTH Check belt drive alignment and tension, adjust if necessary. Check the condition of float and valve in humidifier. Check the condition of drain for free flow. Check the condition of access door…
-
COIL SECTIONS Coils should be cleaned to remove any accumulation of dust between the fins and tubes should be checked for any leakage. Cleaning process can be done in 3 ways: • vacuum, • compressed air, • water or steam spray (opposite to the air flow direction). During the application the water /…
-
PREVENT OF COMMON DANGERS AND RISKS
FILTER GRADE Panel Filter Bag Filter FILTER GRADE INITIAL PRESSURE DIFFERENTIAL RECOMMENDED MAXIMUM PRESSURE DIFFERENTIAL G-2 (65% ≤ Am ≤ 80%) 25 Pa 150 Pa G-3 (80% ≤ Am ≤ 90%) 40 Pa 150 Pa G-4 (90% ≤ Am) 50 Pa 150 Pa G-4 (90% ≤ Am) 65 Pa 150 Pa M-5 (40% ≤ Em ≤ 60%) 55 Pa 250 Pa M-6 (60% ≤ Em ≤ 80%)…
-
BELT TENSION AND ALIGNMENT CONTROL BELT TENSION AND ALIGNMENT CONTROL • A simple “Rule of thumb” for checking belt tension is illustrated at right. • When the belt is grasped as shown, a total deflection of approximately 25mm (1”) should be easily attained. • Excessive deflection is an indication…
-
LUBRICATION OF BEARINGS Bearings have to be controlled and cleaned regularly; have to be lubricated adequately to prevent direct metallic contact between rolling elements, to prevent wear and to project bearing surfaces against corrosion. The fans with low shaft power are equipped with bearings in a…
-
Temperature correction factors kT (for lithium soap grease)
Temperature of bearings (ºC ) Temperature correction factor, kT 0.6 0.35 0.2 0.12 0.07 0.04 ! Surround factor kS considers in particular the external influences such as humidity, shocks and vibrations GREASE STRESS SURROUNDING FACTOR, kS Low Medium 0.8 0.5 High 0.2 3.10.8.1 RELUBRICATION PROCEDURES…
-
3.10.8.3 RENEWING THE GREASE FILL
When the end of the relubrication interval t, has been reached, the used grease in the bearing should be completely removed and replaced by fresh grease. As stated before, under normal conditions, the free space in the bearing should be completely filled and the free space in the housing filled to…
-
TROUBLESHOOTING
PROBLEM NOISE SYMPTOMS Impeller hits inlet ring Noise from drive system Noise from bearings High air velocity POSSIBLE CAUSE OTHER CAUSES OR ACTION Damaged impeller Correct or change impeller Damaged inlet ring Correct or change inlet ring Impeller not centered on shaft Center the impeller Shaft…
-
TROUBLESHOOTING (cont.)
PROBLEM NO AIR FLOW Motor is not running POSSIBLE CAUSE SYMPTOMS Current is not reaching motor Current available to motor Electric power failure Starter overload tripped Control panel fault Isolating switches off Motor bearing seized Incorrect wiring to terminals Faulty motor windings Fan is not…
-
TROUBLESHOOTING (cont.)
PROBLEM COOLING COIL No cooling SYMPTOMS Cooling fluid temperature is high POSSIBLE CAUSE OTHER CAUSES OR ACTION Refrigeration plant cycles on- off Refrigeration plant capacity is insufficient. Circulating pump or compressor fault. Excessive heat gain in piping system. Insufficient coolant flow…