Инструкция на Тепловые насосы Panasonic серии CS-XE...KUA / CU-XE...KUA
Тепловые насосы Panasonic CS-XE9PKUA/CU-XE9PKUA, CS-XE12PKUA/CU-XE12PKUA. Инструкция по сборке.
Загружаем документ…
Текст инструкции
-
11. Installation Instruction
11.1 Select the Best Location 11.1.1 Indoor Unit Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam near the unit. There should not be any obstacles blocking the air circulation. A place where…
-
11.2 Indoor Unit
The mounting wall shall be strong and solid enough to prevent it from vibration. Model XE9PKUA, XE12PKUA c 19-9/32" (490 mm) d 3-7/32" (82 mm) Dimension e f 17-9/32" 17" (439 mm) (432 mm) g 1-11/16" (43 mm) h 3-3/4" (95 mm) The center of installation plate should be at more than ○ 1 at right and…
-
Indoor Unit Installation 11.2.2.1 For the right rear piping 11.2.2.2 For the right bottom piping 11.2.2.3 For the embedded piping (This can be used for left rear piping and bottom piping also.) 26
-
Connect the Cable to the Indoor Unit The inside and outside connection cable can be connected without removing the front grille. Unscrew the conduit cover and fix the conduit connector to conduit cover with lock nut, then secure it against chassis. Connection cable between indoor unit and outdoor…
-
11.3 Outdoor Unit
11.3.1 Install the Outdoor Unit After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1 Fix the unit on concrete or rigid frame firmly and horizontally with a bolt nut ø13/32" (ø10 mm). 2 When installing at roof, please consider strong wind…
-
Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve. Connect the micron gauge between…
-
Secure the wire onto the control board with the holder (clamper). 10 After completing wiring connections, reattach the particular plate and control board cover (metal and resin) to the original position with the screws. 11 For wire stripping and connection requirement, refer to instruction 11.2.3 of…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.