18. MULTI-TYPE(V MULTI)
PACKAGED AIR-CONDITIONER Split system, Air to air heat pump type ( ) OUTDOOR UNIT FDC508HES3 808HES3 1008HES3 INDOOR UNIT FDT208-A FDR208-A 258-A 258-A 308-A 308-A 408-A 408-A 508-A 508-A 677
-
18.1 GENERAL INFORMATION
18.1.1 Specific features Ideal for the installation conditions characteristic of larger rooms and L-shaped or other non-standard-shaped rooms, the Multi-Type V series allows an extensive degree of flexibility in the selection of indoor units. Specifically, the selection of indoor units with…
-
18.1.3 Table of models
Capacity Model Ceiling recessed type (FDT) Cassetteria type (FDR) Outdoor unit to be combined(FDC) FDC508HES3 (5 Horse Power) FDC808HES3 (8 Horse Power) FDC1008HES3 (10 Horse Power) 18.1.4 Table of system combinations Outdoor unit Type Indoor unit assembly capacity Branch pipe set (Optional)…
-
18.2 SELECTION DATA
18.2.1 Specifications (1) Indoor unit (a) Ceiling recessed type (FDT) Models FDT208-A, 258-A Model FDT208-A FDT258-A W 5000 5700 W 5400 Item (1) Nominal cooling capacity Nominal heating capacity(1) 6100 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Hi: 39 Lo: 35 Hi: 38 Lo: 33 Exterior…
-
Model FDT308-A FDT408-A W 7100 10000 12500 W 8000 11200 14000 dB(A) Hi: 41 Lo: 35 Item (1) Nominal cooling capacity Nominal heating capacity(1) Power source FDT508-A 1 Phase 220/240V 50Hz Noise level 840 950 Hi: 48 Lo: 40 Exterior dimensions Height Width Depth mm Unit:260 Panel:30 840 950 Net weight…
-
(b) Cassetteria type (FDR)
Models FDR208-A, 258-A Model FDR208-A Item Decorative panel Panel model (Option) FDR258-A Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-36W-E R-PNLC-36W-E Nominal cooling capacity(1) W 5000 Nominal heating capacity(1) W 5400 5700 6100 Power source 1 Phase…
-
Model FDR308-A Item Decorative panel Panel model (Option) FDR408-A Silent panel Canvas panel Silent panel Canvas panel R-PNLS-36W-E R-PNLC-36W-E R-PNLS-46W-E R-PNLC-46W-E Nominal cooling capacity(1) W 7100 10000 Nominal heating capacity(1) W 8000 11200 Power source 1 Phase 220/240V 50Hz dB(A) Noise…
-
Model FDR508-A
Model FDR508-A Item Decorative panel Panel model (Option) Silent panel Canvas panel R-PNLS-46W-E R-PNLC-46W-E Nominal cooling capacity(1) W 12500 Nominal heating capacity(1) W 14000 Power source 1 Phase 220/240V 50Hz dB(A) Hi: 46 Lo: 39 Exterior dimensions Height Width Depth mm Unit:406 1370 635…
-
Outdoor unit Models FDC508HES3, 808HES3, 1008HES3 Model Item FDC508HES3 FDC808HES3 Power source 3 Phase 380/415V 50Hz Nominal cooling capacity(1) W 12500 20000 Nominal heating capacity(1) W 14000 21200 Noise level dB(A) 55 Exterior dimensions Height Width Depth mm Net weight kg Refrigerant equipment…
-
(3) Operation chart
The Multi series is a system that allows for different models and capacities of indoor units to be combined so the individual operating characteristics of the indoor and outdoor are provided. Use the procedure shown in Item (c) to calculate the combined operating characteristics. (a) Operating…
-
Operation characteristics of each unit
(Cooling/Heating) Model FDC808HES3 FDT308-A FDT508-A Power input (kW) 8.44/6.44 0.11/0.11 0.27/0.27 Running current (A) 14.2/11.6 0.6/0.6 1.4/1.4 Item 1 Total power input (kW) (Cooling) 8.44 + 0.11+ 0.27 = 8.82 (kW) (Heating) 6.44 + 0.11+ 0.27 = 6.82 (kW) 2 Total running current (A) . (Cooling) 14.2…
-
Height and length restrictions for refrigerant piping
Models FDC508HES3 Outdoor unit L Indoor unit ra L +ra +rb < = 50 lra – rbl < = 10, ra < = 30, rb < = 30 • One-way pipe length (m) • Branch pipe length (m) A rb • Vertical height difference between outdoor unit and indoor unit B Outdoor unit is higher Max. 30m Outdoor unit is lower Max. 15m •…
-
18.2.3 Exterior dimensions
(1) Indoor unit (a) Ceiling recessed type (FDT) Model FDT208-A Unit : mm 740 (Ceiling hole size) Decorative Panel 430 Fresh air opening for ducting 800 (Suspension bolts pitch) C 515 → → 359 295 D 336 680 (Suspension bolts pitch) Exhaust air opening for ducting 570 B→ 264 700 VIEW A Gas piping…
-
Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 310 VIEW A Air outlet grille…
-
Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 310 VIEW A Air outlet grille…
-
(b) Cassetteria type (FDR)
Model FDR208-A Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 57 786 (Suspension bolts pitch) 433 Drain hose (Accessories) 137 (Locality) 353 Fresh air opening (Knock out hole) ↑A 405 650 MIN320 0 φ20 Drain (Natural drainage) (VP20) Hole of wiring (I.D. φ35) Holes of tapping…
-
Model FDR208-A
Canvas Panel (Model: R-PNLC-26W-E) Drain hose (Accessories) 804 (Ceiling hole size) 9 Unit : mm 786 (Suspension bolts pitch) (Local Locality) 9 45 Panel center 150 193 Drain (Connectable with VP25) Control box 352 525 (Ceiling hole size) 90 Fresh air opening (Knock out hole) 69 Liquid piping φ6.35…
-
Unit : mm Silent Panel (Model: R-PNLS-36W-E) 1180 (Ceiling hole size) 986 (Suspension bolts pitch) Drain hose (Accessories) (Locality) Fresh air opening (Knock out hole) 70 45 Air outlet duct Suspension bolts (M10 × 4pcs.) 295~325 VIEW C 71 (Max. Drain up) 270 Control box Panel center (Suspension…
-
Silent Panel (Model: R-PNLS-46W-E) Unit : mm 1600(Ceiling hole size) Drain hose(Accessories) 1406(Suspension bolts pictch) (Locality) 663 Fresh air opening 284 45 Air outlet duct 70 150 690(Ceiling hole size) Control box Panel center 495 VIEW C (Suspension bolts pictch) 275 45 C 270 (Knock out hole)…
-
Canvas Panel (Model: R-PNLC-46W-E) Unit : mm Drain hose(Accessories) 1424(Ceiling hole size) 1406(Suspension bolts pictch) 9 Fresh air opening (Locality) 9 (Knock out hole) 150 45 C 193 69 Panel center 352 Control box 495 VIEW C 59 71 Suspension bolts 80 1370 (M10 × 4 pcs.) 295~325 235 (I.D.φ14) B→…
-
(2) Remote controller (Optional parts)
Unit : mm Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 83.5 For the passage after wiring ♦ Usable JIS box, JIS C 8336 ⋅ Switch box for 1 piece (without cover) (use of the mark hole as illustrated on the left)…
-
(3) Outdoor unit
Model FDC508HES3 Unit: mm Liquid piping: φ 9.52 (3/8") (Flare connecting) Gas piping: φ 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: φ 9.52 (3/8") (Flare connecting) Gas piping: φ 19.05 (3/4") (Flare connecting) 1250 Opening for electric wiring A Opening for piping and electric…
-
Models FDC808HES3, 1008HES3
Unit: mm 1350 Opening for exit wiring (ø50) 1450 50 600 A Connect of liquid piping 808: ø12.7 (1/2") 1008: ø15.58 (5/8") ( ) 80 Power supply connecting terminal block 291.5 Opening for exit piping (ø88) Opening for exit wiring (ø50) 80 Connect of gas piping 170 ø25.4 (1") ( 1008:808:ø28.58 (1 1/8")…
-
18.2.4 Exterior appearance
(1) Indoor unit (a) Ceiling recessed type (FDT) Models All models Type Item Panel model FDT208-A T-PSA-22W-E FDT258-A~508-A T-PSA-32W-E Remarks Without swing Pearl white (Decorative panel) (b) Cassetteria type (FDR) Models All models Canvas-duct panel type Silent panel type Ceramic White (2) Outdoor…
-
18.2.5 Piping system
(1) Twin type Model FDC508HES3 Indoor unit High pressure switch (63H2) (For fan motor control) Indoor unit Cooling cycle Heating cycle 4way valve (ø15.88) Outdoor unit Thermistor (ThO-A) (ø15.88) Strainer Gas line Strainer Service valve (Flare connecting) Branch pipe (ø19.05) (Brazing) Flare…
-
(2) Triple type
Models FDC808HES3,1008HES3 Indoor unit Indoor unit Indoor unit Outdoor unit Cooling cycle Heating cycle Flare connecting High pressure switch(63H2) (For fan motor control) Service valve (Brazing) Thermistor (ThO-A) Branch pipe(Brazing) Strainer : ø15.88 (208~308 408, 508 : ø19.05 ) Strainer : ø15.88…
-
Preset point of the protective devices
Parts name Equipped unit Mark Thermistor (for protection overloading in heating) FDC508HES3 FDC808HES3, 1008HES3 OFF 68˚C ON 61˚C ThI-R Indoor unit OFF 2.5˚C ON 10˚C Thermistor (for frost prevention) Thermistor (for detecting discharge pipe temp.) Tho-D Outdoor unit Thermistor (for detecting heat…
-
Table of bypass factor
FDT series Model 208 type 258 type 308 type 408 type 508 type Hi 0.112 0.050 0.065 0.076 0.025 Lo 0.073 0.030 0.030 0.050 0.013 208 type 258 type 308 type 408 type 508 type Hi 0.035 0.035 0.039 0.085 0.035 Lo 0.021 0.020 0.023 0.060 0.023 Item Air flow FDR series Model Item Air flow (2) Correction…
-
18.2.7 Characteristics of fan
• External static pressure table How to interpret the blower characteristics table Unit: Pa (mmAq) Example : Case of FDR308-A Duct specs. 1 spot closing(1) FDR258-A 18 30(3) 65(6.5) 45(4.5) 80(8) 50(5) 85(8.5) FDR308-A 20 25(2.5) 60(6) 45(4.5) 80(8) 50(5) 85(8.5) 90(9) 50(5) 85(8.5) 50(5) FDR408-A…
-
Model FDR308-A
-
18.2.8 Noise level
-
Model FDR408-A
-
18.3 ELECTRICAL DATA
-
N BK/WH
-
18.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 317. 18.5 APPLICATION DATA 18.5.1 Installation of indoor unit (1) Ceiling recessed type (FDT) Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 333. (2)…
-
When the unit is installed at the particular location as shown below, corrosion or failure may be caused. Please consult the dealer from which you purchased the air-conditioner. a) The place where corrosive gas is generated (hot spring, etc.). b) The place where wind containing salt blows (seaside…
-
(c)
Unit: mm Bolt securing position Models FDC808HES3, 1008HES3 20 Model FDC508HES3 380 Intake Anchor bolt position (4 locations) Discharge 160 Anchor bolt position (4 places) 1) Use anchor bolts (M10) to secure the unit's legs. 2) Securely install the unit so that it dose not fall over during earth…
-
• FDC808HES3 [Branch pipe set: DIS-WB]
-
(iii) Double twin
-
(b) Piping work
Request ¡ Use the pipe made of following material. Moreover, it is very convenient for you to use the separately sold piping kit. Material: Phosphor deoxidized seamless copper tube (C1220T, JIS H3300) ¡ In the case of this unit, condensation water is also generated on the liquid piping. Insulate…
-
Models FDC808HES3, 1008HES3
Leak test (1) The unit's air-tightness test has been conducted but after completing the piping connections conduct an air-tightness test of the connected piping and the indoor units using the outdoor gas side service valve check joint. Be sure to conduct this test with the service valve closed. 1…
-
Double twin specification (FDC808, 1008HES3 only)
G = main piping L (m) × C + branch piping L1(m) × f + branch piping L2 (m) × f + branch piping 1 (m) × f + branch piping 2 (m) × f + branch piping 3 (m) × f + branch piping 4 (m) × f - (D - B) Example of Calculation 1) For twin type Outdoor Unit: FDC508HES3 Indoor Unit: FDT258-A + FDR258-A Outdoor…
-
(b)
Wiring connection. ¡ Connect the same terminal number between the Indoor unit and Outdoor unit as shown in the following diagram. ¡ Make wiring to supply to the Outdoor unit, so that the power for the Indoor unit is supplied by 1 and 2 terminals. ¡ Secure the wiring with wiring clamp so that no…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.