20. INVERTER DRIVEN MULTI-INDOOR
UNIT HEAT RECOVERY CLIMATE CONTROL SYSTEM Simultaneous heating & Cooling 3 Pipe System ( ) (OUTDOOR UNIT) Alternative refrigerant R407C use models FDCP2001HKXRE2, 2501HKXRE2 (INDOOR UNIT) FDTJ28HKXE2 36HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDTWJ28HKXE2B 45HKXE2B 56HKXE2B 71HKXE2B…
-
20.1 GENERAL INFORMATION
20.1.1 Specific features (1) Fuzzy control (a) Response speed and stability are enhanced. • The system automatically controls changes of return air temperature, set temperature and room temperature according to the fuzzy control. • The system response speed, can keep room temperature constant, and…
-
(3) Installation of automatic address setting function
• The address setting method are divided into three types according to wiring method: “Automatic Address Setting,” “Remote control Address Setting.” and “Manual Address Setting.” In case of the Automatic Address Setting, no address needs be set as usual. (4) Connectable indoor capacity Capacity from…
-
20.1.2 How to read the model name
Example: FDC P 2001 H KXR E 2 CE marking model Application power source...See the specifications Multi KXR series Heat pump type Nominal capacity R407C models Model name Indoor unit : FDT, FDTW, FDTS, FDR, FDUM FDE, FDK, FDFL, FDFU Outdoor unit : FDC 20.1.3 Table of models Capacity Model Ceiling…
-
20.2 SELECTION DATA
20.2.1 Specifications (1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2 Models Item FDTJ28HKXE2(3) FDTJ36HKXE2(3) Nominal cooling capacity*1 W 2800 3600 Nominal heating capacity*2 W 3200 4000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height…
-
Models FDTJ45HKXE2, 56HKXE2, 71HKXE2
Models FDTJ45HKXE2(3) FDTJ56HKXE2(3) W 4500 5600 7100 W 5000 6300 8000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ71HKXE2(3) 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg Hi: 38 Me: 35 Lo: 34 Unit:260 Hi: 40 Me: 38…
-
Models FDTJ90HKXE2, 112HKXE2, 140HKXE2
Models FDTJ90HKXE2(3) FDTJ112HKXE2(3) W 9000 11200 14000 W 10000 12500 16000 Item 1 Nominal cooling capacity* Nominal heating capacity*2 Power source FDTJ140HKXE2(3) 1 Phase 220/240V 50Hz dB(A) Hi: 42 Me: 40 Lo: 38 Exterior dimensions Height Width Depth mm Unit: 260 Panel:30 Net weight kg Noise…
-
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Models Item FDTWJ28HKXE2B(3) FDTWJ45HKXE2B(3) FDTWJ56HKXE2B(3) Nominal cooling capacity*1 W 2800 4500 5600 Nominal heating capacity*2 W 3200 5000 6300 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg…
-
Models FDTWJ71HKXE2B, 90HKXE2B
Models FDTWJ71HKXE2B(3) Item FDTWJ90HKXE2B(3) Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 Noise level dB(A) Hi: 41 Me: 38 Lo: 35 Exterior dimensions Height Width Depth mm Unit:330 Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 41 Me: 39 Lo: 36 1054 620…
-
Models FDTWJ112HKXE2B, 140HKXE2B
Models FDTWJ112HKXE2B(3) Item FDTWJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 44 Me: 41 Lo: 38 Exterior dimensions Height Width Depth mm Unit:345 Net weight kg Hi: 45 Me: 42 Lo: 39 1524 620…
-
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B
Model Item FDTSJ22HKXE2B(3) FDTSJ28HKXE2B(3) FDTSJ36HKXE2B(3) Nominal cooling capacity*1 W 2200 2800 3600 Nominal heating capacity*2 W 2500 3200 4000 Noise level dB(A) Hi: 39 Lo: 38 Exterior dimensions Height Width Depth mm Net weight Kg Power source 1 Phase 220/240V 50Hz Hi: 40 Me: 39 Lo: 38…
-
Models FDTSJ45HKXE2B, 71HKXE2B
Model FDTSJ45HKXE2B(3) Item FDTSJ71HKXE2B(3) 1 Nominal cooling capacity* W 4500 7100 Nominal heating capacity*2 W 5000 8000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 43 Me: 40 Lo: 38 Hi: 44 Me: 40 Lo: 38 Exterior dimensions Height Width Depth mm Unit:194 Panel:10 Unit:194 Panel:10 Net…
-
(d) Cassetteria type (FDR)
Models FDRJ22HKXE2, 28HKXE2 Models FDRJ22HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ28HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 2200 2800 Nominal heating capacity*2 W 2500 3200 Power…
-
Models FDRJ45HKXE2, 56HKXE2
Models FDRJ45HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ56HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 4500 5600 Nominal heating capacity*2 W 5000 6300 Power source 1 Phase 220/240V 50Hz…
-
Models
FDRJ71HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ90HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-36W-E R-PNLC-36W-E R-PNLS-36W-E R-PNLC-36W-E Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 Power source 1 Phase 220/240V 50Hz Noise…
-
Models
FDRJ112HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ140HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-46W-E R-PNLC-46W-E R-PNLS-46W-E R-PNLC-46W-E Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz Noise…
-
(e) Satellite ducted type (FDUM)
Models FDUMJ36HKXE2, 45HKXE2 Models FDUMJ36HKXE2(3) Item FDUMJ45HKXE2(3) Nominal cooling capacity*1 W 3600 4500 Nominal heating capacity*2 W 4000 5000 Noise level dB(A) Hi: 34 Me: 32 Lo: 29 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 35 Me: 32 Lo…
-
Models FDUMJ56HKXE2, 71HKXE2, 90HKXE2
Models Item FDUMJ56HKXE2(3) FDUMJ71HKXE2(3) FDUMJ90HKXE2(3) 1 Nominal cooling capacity* W 5600 7100 9000 Nominal heating capacity*2 W 6300 8000 10000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 35 Me: 32 Lo: 29 Exterior dimensions Height Width Depth mm 299 Net weight kg 750 Hi: 35 Me…
-
Models FDUMJ112HKXE2, 140HKXE2
Models FDUMJ112HKXE2(3) Item FDUMJ140HKXE2(3) Nominal cooling capacity*1 W 11200 14000 Nominal heating capacity*2 W 12500 16000 Noise level dB(A) Hi: 38 Me: 35 Lo: 32 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 39 Me: 37 Lo: 34 350 1370 Refrigerant…
-
(f) Ceiling suspension type (FDE)
Models FDEJ36HKXE2B, 45HKXE2B Models Item FDEJ36HKXE2B(3) FDEJ45HKXE2B(3) 4500 Nominal cooling capacity*1 W 3600 Nominal heating capacity*2 W 4000 5000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 43 Me:40 Lo: 38 Exterior dimensions Height Width Depth mm 184 Net weight kg 1000 650 22…
-
Models FDEJ56HKXE2B, 71HKXE2B
Models FDEJ56HKXE2B(3) Item FDEJ71HKXE2B(3) 1 Nominal cooling capacity* W 5600 7100 Nominal heating capacity*2 W 6300 8000 Noise level dB(A) Hi: 43 Me:40 Lo: 38 Hi: 44 Me:40 Lo: 38 Exterior dimensions Height Width Depth mm 184 184 Net weight kg Power source 1 Phase 220/240V 50Hz 1000 650 1260 22…
-
Models FDEJ112HKXE2B, 140HKXE2B
Models FDEJ112HKXE2B(3) Item FDEJ140HKXE2B(3) 1 Nominal cooling capacity* W 11200 14000 Nominal heating capacity*2 W 12500 16000 Noise level dB(A) Hi: 49 Me:46 Lo: 42 Hi: 50 Me:47 Lo: 42 Exterior dimensions Height Width Depth mm 239 239 Net weight kg Power source 1 Phase 220/240V 50Hz 1260 650…
-
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2
Models Item FDKJ22HKXE2(3) FDKJ28HKXE2(3) FDKJ36HKXE2(3) FDKJ45HKXE2(3) Nominal cooling capacity*1 W 2200 2800 3600 4500 Nominal heating capacity*2 W 2500 3200 4000 5000 Noise level dB(A) Hi: 42 Lo: 37 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase 220/240V 50Hz Hi: 42…
-
Models FDKJ56HKXE2, 71HKXE2
Model FDKJ56HKXE2(3) FDKJ71HKXE2(3) W 5600 7100 W 6300 Item 1 Nominal cooling capacity* Nominal heating capacity*2 8000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Hi: 46 Me:43 Lo: 39 Hi: 47 Me:44 Lo: 40 Exterior dimensions Height Width Depth mm 375 1148 375 Net weight kg 20 194 Louver fins…
-
(h) Floor standing exposed type (FDFL)
Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2 Model Item FDFLJ28HKXE2(3) FDFLJ45HKXE2(3) FDFLJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 7100 Nominal heating capacity*2 W 3200 5000 8000 Noise level dB(A) Hi: 41 Me:38 Lo: 36 Exterior dimensions Height Width Depth mm Net weight kg Power source 1 Phase…
-
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Model Item FDFUJ28HKXE2(3) FDFUJ45HKXE2(3) FDFUJ56HKXE2(3) FDFUJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 5600 7100 Nominal heating capacity*2 W 3200 5000 6300 8000 Noise level dB(A) Hi: 41 Me:38 Lo: 36 Exterior dimensions Height Width Depth mm…
-
(2) Outdoor unit
Models FDCP2001HKXRE2, 2501HKXRE2 Models Item FDCP2001HKXRE2(3) Power source FDCP2501HKXRE2(3) 3 Phase 380/415V 50Hz Nominal cooling capacity*1 W 22400 Nominal heating capacity*2 W 25000 Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg 31500 60 1700 Refrigerant equipment…
-
(3) Operation chart
Since the Multi KXR series air conditioner units are free multitype to which the indoor units of different capacity and different model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual operation characteristics of indoor and…
-
FDK, FDFL, FDFU Series
(220 V/240 V) Models Item FDK Series FDFL, FDFU Series 45,56 71 Power input (kW) 0.05/0.06 0.06/0.07 0.08/0.09 0.09/0.11 0.09/0.10 0.09/0.10 0.09/0.10 Running current (A) 0.26/0.28 0.31/0.33 0.36/0.39 0.41/0.48 0.41/0.42 0.40/0.41 0.40/0.41 Notes (1) This packaged air-conditioner is manufactured and…
-
• Correction factor of compressor power input
Model FDCP2001HKXRE2 Model FDCP2501HKXRE2 1.0 Power consumption correction coefficietnt Power consumption correction coefficietnt 1.0 0.8 0.6 0.4 0.2 Total capacity of indoor units operating simulataneously 45 105 (Below, the coefficients are the same.) 164 224 0.8 0.6 0.4 0.2 Total capacity of…
-
20.2.2 Range of usage & limitations
System FDCP2001HKXRE2 FDCP2501HKXRE2 Item Indoor intake air temperature (Upper, lower limits) Refer to the selection chart. Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination 1 to 8 units Number of connected units Total capacity 11000 to 29200w 13200 to 37100w…
-
20.2.3 Exterior dimensions
(1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2, 45HKXE2, 56HKXE2, 71HKXE2, 90HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid…
-
Models FDTJ112HKXE2, 140HKXE2
Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping φ9.52(3/8") 267 Drain hose (Accessories) (Local setting) D 422 675 (Suspension bolts pitch) Exhaust air…
-
(b) 2-way outlet ceiling recessed type (FDTW)
Models FDTWJ28HKXE2B, 45HKXE2B, 56HKXE2B Unit : mm Drain hose (Accessories) (Local setting) Hole Suspension fitting Fresh air opening for ducting (knock out) 97 50 Holes of tapping screws 5 - φ4 264 91 Center of panel 640 70 Suspension bolts (M10 × 4 pcs.) (Ceiling hole size) 446 Control box…
-
Models FDTWJ71HKXE2B, 90HKXE2B
Unit : mm 1054 295~ 325 Liquid piping φ9.52(3/8") ↑ 240 Holes for tapping screws 8 – φ4 128 Drain (VP25) (condensate pump drain) Hole for wiring 20 Drain (VP20) (Natural drainage) Exhaust air opening for ducting (knock out) Decorative Panel 64 Gas piping φ15.88(5/8") or less Hole A Hole VIEW A 219…
-
Models FDTWJ112HKXE2B, 140HKXE2B
Hole Suspension fitting Fresh air opening for ducting (knock out) 97 Center of panel 640 (Ceiling hole size) Control box Holes for tapping screws 5-ø4 Suspension bolts (M10 × 4 pcs.) (Local setting) 446 (Suspension bolts pitch) 1730 (Ceiling hole size) 1600 (Suspension bolts pitch) 40 278 Drain hose…
-
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B, 45HKXE2B
Panel center Drain hose (Accessories) (Local setting) VIEW A Suspension bolts (M10×4 pcs.) 295~325 ←C or less Max. Drain up 70 710 (Ceiling hole size) B→ 600 (Suspension bolts pitch) 40 555 Holes for tapping screws (φ4-6pcs.) 1230 (Ceiling hole size) 990 (Suspension bolts pitch) Unit : mm 140 Fresh…
-
Model FDTSJ71HKXE2B
Unit : mm 1440 (Ceiling hole size) 1250 (Suspension bolts pitch) Fresh air opening for ducting (Knock out) Holes for tapping screws (φ4-6pcs.) Panel center 200 Suspension bolts (M10×4pcs.) Drain hose(Accessories) (Local setting) 295~325 1200 VIEW A 90 600 or less Max. Drain up ←C 30 70 Fresh air…
-
(d)
Cassetteria type (FDR) Model FDRJ22HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) ↑ 213 MIN95 40 MIN156 MIN81 650 or less MIN320 MIN225 480 A Drain(VP25) (Natural drainage) 460 Holes for tapping screws 4-φ4.0 150 1040 45 φ170 φ170 950 Air inlet 45 75 φ149 90 Fresh air…
-
Model FDRJ22HKXE2
Canvas Panel (Model: R-PNLC -26W-E) 804 (Ceiling hole size) 786 (Suspension bolts pitch) Fresh air opening for ducting (Knock out) Drain (Connectable with VP25) Liquid piping φ6.35(1/4") Gas piping φ12.7(1/2") Control box Panel center 352 525 (Ceiling hole size) 90 ↓ 45 545 (Suspension bolt pitch)…
-
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bols pitch) 137 Fresh air opening for ducting (Knock out) (Local setting) 353 545 (Suspension bolt pitch) 45 panel center 71 Supply air duct (Ceiling hole size) Control box C↓ VIEW C Drain (Connectable with VP25)…
-
Models FDRJ28HKXE2, 45HKXE2, 56HKXE2
Canvas Panel (Model: R-PNLC-26W-E) Unit : mm Drain hose (Accessories) 804 (Ceiling hole size) 9 786 (Suspension bolts pitch) 353 284 Fresh air opening for ducting (Knock out) 45 C↓ Control box Drain (Connectable with VP25) Panel center Liquid piping 28, 45 type: φ6.35 (1/4") 56 type: φ9.52 (3/8")…
-
Unit : mm 1180 (Ceiling hole size) 986 (Suspension bolts pitch) Drain hose (Accessories) (Local setting) Fresh air opening for ducting (Knock out) 545 (Suspension bolts pitch) 45 Panel center 71 465 Drain (VP20) (Natural drainage) ↑A MIN95 40 405 MIN156 MIN320 Hole for wiring (φ35) 1240 150 φ149…
-
Unit : mm Drain hose (Accessories) (Local setting) 1004 (Ceilinghole hole size) 986 (Suspension bolts pitch) 453 69 Drain (Connectable with VP25) Control box Liquid piping φ9.52(3/8") 59 71 Supply air duct B→ 295~325 130 165 VIEW C 299 Suspension bolts (M10 × 4pcs.) 500 Gas piping φ15.88(5/8") Max.…
-
Unit : mm 1600 (Ceiling hole size) 1406 (Suspension bolts pitch) Panerl center Supply air duct Liquid piping φ19.05(3/4") 295~325 320 VIEW C 80 (Max. Drain up) 1370 495 Drain (Connectable with VP25) 76 Gas piping φ19.05(3/4") Suspension bolts (M10 ×4pcs.) φ20 MIN 96 MIN156 MIN206 Drain (VP20)…
-
Unit : mm 1424 (Ceiling hole size) 1406 (Suspension bolts pitch) Drain (Connecteble with VP25) 495 Liquid piping φ9.52(3/8") 59 1370 295~325 or less Max. Drain up 71 Supply air duct VIEW C Gas piping φ19.05(3/4") 310 352 Panel center Control box Suspension bolts (M10 × 4pcs.) Fresh air opening for…
-
(e) Satellite ducted type (FDUM)
Models FDUMJ36HKXE2, 45HKXE2, 56HKXE2 Unit : mm 786 (Suspension bolts pitch) B 205 Hole of tapping screws (4-φ4) Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) 284 A→ 213 φ149 Control box φ170 Liquid piping 36, 45 type: φ6.35(1/4") 56 type: φ9.52(3/8") 118 472 (Suspension…
-
Models FDUMJ71HKXE2, 90HKXE2
Unit : mm 986 (Suspension bolts pitch) (Suspension bolts pitch) 45 ↑ 18 80 B A→ Holes of tapping screws 4-φ4 φ149 Control box Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) φ170 Liquid piping φ9.52(3/8") Fresh air opening Gas piping for ducting φ15.88(5/8") (Knock out) φ170…
-
Models FDUMJ112HKXE2, 140HKXE2
Unit : mm 1406 (Suspension bolts pitch) 1370 472 ↑ B Holes of tapping screws (4-φ4) 213 φ149 Control box 284 A→ Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) Liquid piping φ9.52(3/8") 58 76 Supply air duct 320 320 295~325 235 φ170 Fresh air opening for ducting (Knock out)…
-
(f)
Ceiling suspension type (FDE) Models FDEJ36HKXE2B, 45HKXE2B, 56HKXEB2 Unit : mm 984 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4 pcs. Not included) The brackets face out When the unit is half recesed a bove the ceiling The brackets face interior When the unit is suspended…
-
Model FDEJ112HKXE2B
Unit : mm 1244 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4pcs. Not included) The brackets face out When the unit is half recesed a bove the ceiling 66 50 1200 30 Liguid piping 584 135 Gas piping 185 Drain hole connection (1) The brackets face interior When the unit is…
-
Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2
Unit : mm 7.7 77.5 77.5 65 155 Space for installation and service 200 Mounting plate φ8 × 48 pcs. (Holes on mounting plate) 150 200 or more or more Available space for rear connection 45 Hole on wall for rear connection 55 105 φ70 Detail of mounting plate Outlet for piping (On both side) or more ←A…
-
Model FDKJ71HKXE2
23 Unit : mm 1436 7.7 Outlet for piping (On both side) 65 377.5 155 108 Space for installation and service Mounting plate 377.5 Detail of mounting plate 150 200 or more or more 45 φ8 × 48 pcs. (Holes on mounting plate) or more 155 108 1306 1196 Outlet for electric wiring 375 280 ←A Piping cover Hole…
-
(i) Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2 Note (1) Value in ( Unit : mm ) indicates 71 type. Slotted hole for wall mounting 4-12 x 24 Space for installation and service 1000 (1071) Peri cover Peri cover 810(1095) 722(1007) Expansion valve box Control box Drain piping Flexible tube PT20A female…
-
(2) Remote controller (Optional parts)
Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 83.5 For the passage after wiring ♦ Usable JIS box, JIS C 8336 ⋅ Switch box for 1 piece (without cover) (use of the mark hole as illustrated on the left) ⋅ Switch…
-
(3) Individual flow divide controller (Optional Part)
HPFD01R-E 117.5 Indoor refrigerant piping connection pipe Liquid pipe φ9.52 (3/8") flare. with included different diameter adapter coupling φ6.35 (1/4") pipe Hanging bolt position (M10 provided at site) 61 Indoor connection wire (length 200) (with insert terminal) Outdoor refrigerant piping…
-
Wire entry hole
(φ50) pass-through hole (φ100) Back 50 Piping and wiring bottom 118 Drain waste water hole (6-φ20) 170 φ19.05 (3/4") Refrigerant discharge gas piping connection pipe Anchor bolt hole (4 locations for M10) Power supply entry hole (φ50) ( Installation example L4 L3 2001: with φ25.4 (1") pipe 2501…
-
20.2.4 Exterior appearance
(1) Indoor unit (a) Ceiling recessed type (FDT) ● Decorative panel Pearl white (b) 2-way outlet ceiling recessed type (FDTW) Air outlet Air inlet ● Decorative panel (i) Standard type Panel part No. Type Panel color With Auto swing Pearl white TW-PSA-22W-E TW-PSA-32W-E Applicable model FDTW28, 45, 56…
-
Panel
Ceramic white Air inlet grille Ceramic white ● Decorative panel Panel part No. TS-PSA-26W-E TS-PSA-36W-E Type Panel color With Auto swing Misty white Applicable model FDTS22, 28, 36, 45 type FDTS71 type (d) Cassetteria type (FDR) Silent panel type Canvas-duct panel type Ceramic white Ceramic white…
-
2 No. Parts name 1 Side plate 2 Front panel 3 Air inlet grill 4 Air outlet louver 5 Bottom plate 6 Right and Left louvers Color Ceramic white Light gray (h) Floor standing exposed type (FDFL) Dark gray (Air outlet grill) Ceramic white (Body) Black (Bottom plate) (i) Floor standing hidden type (FDFU)…
-
FDE series have external installation
as the expansion valve box. Indoor unit B Intake Thermistor (Th1-A) ø9.52 (3/8") - Note (1) The solenoid valve is open during magnetic inductance and closed when there is not magnetic inductance. Open - Closed Open Closed 20VF Open - 20VU - Partial load During discharge temperature and dome bottom…
-
20.2.6 Selection chart
(1) Correct the cooling and heating capacity in accordance with the conditions as follows.The net cooling and heating capacity can be,obtained in the following way. Indoor unit Each indoor unit = System performance Indoor unit capacity Indoor unit capacity when operating simultaneously. Outdoor unit…
-
(c) When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when the outdoor unit is located at a higher height than the indoor unit in heating operation, the following values should be subtracvted from the values in the above table. Height difference between…
-
(3) Sensible heat capacity
(a) FDT Series Model FDTJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.89 2.83 2.76 2.68 2.60 2.53 2.46 TC 2.98 2.91 2.85 2.77 2.70 2.63 2.56 TC 3.05 2.99 2.92 2.86 2.80 2.72 2.64 TC 3.13 3.07 3.01 2.95 2.88…
-
Model FDTJ71KHXE2
Air flow 3 (m /min) 16 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 7.33 7.18 7.00 6.80 6.60 6.42 6.23 TC 7.55 7.39 7.22 7.04 6.85 6.67 6.48 TC 7.75 7.58 7.41 7.26 7.10 6.90 6.70 TC 7.94 7.78 7.63 7.47 7.31 7.13 6.94 TC 8.13 7.99 7.83 7.66…
-
(b) FDTS Series
Model FDTSJ22HKXE2B Air flow 3 (m /min) 11 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.27 2.22 2.17 2.11 2.05 1.99 1.93 TC 2.34 2.29 2.24 2.18 2.12 2.07 2.01 TC 2.40 2.35 2.30 2.25 2.20 2.14 2.08 TC 2.46 2.41 2.36 2.31 2.27 2.21 2.15 TC…
-
Model FDTSJ71HKXE2B
Air flow 3 (m /min) 18 Indoor air temperature Outdoor air temp. (°CDB) 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 TC 8.14 7.97 7.82 7.70…
-
Model FDRJ56HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 5.80 5.67 5.53 5.39 5.21 5.07 4.91 TC 5.97 5.84 5.70 5.57 5.43 5.25 5.11 TC 6.13 6.00 5.87 5.73 5.60 5.47 5.30 TC 6.25 6.15 6.04 5.90 5.77 5.63 5.50 TC 6.42 6.28 6.17 6.07…
-
Model FDRJ140HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB TC 14.50 14.17 13.83 13.47 13.02 12.68 12.26 SHC 10.78 10.63 10.48 10.31 10.12 9.97 9.78 18.0°CWB TC 14.92 14.59 14.25 13.92 13.58 13.13 12.77 SHC 10.84 10.69 10.55 10.40 10.26 10.07 9.91 19.0°CWB TC 15.32 15.01 14.67 14.34…
-
Model FDUMJ71HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 TC 8.14 7.97 7.82 7.70…
-
(e) FDE Series
Model FDEJ36HKXE2B Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 TC 4.13…
-
Model FDEJ112HKXE2B
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB TC 11.60 11.33 11.07 10.77 10.42 10.15 9.81 SHC 8.72 8.60 8.48 8.35 8.20 8.08 7.93 18.0°CWB TC 11.94 11.67 11.40 11.13 10.86 10.51 10.21 SHC 8.77 8.66 8.54 8.42 8.31 8.16 8.04 19.0°CWB TC 12.25 12.01 11.74 11.47 11.20 10.93…
-
Model FDKJ36HKXE2
Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 TC 4.13 4.04 3.97 3.90…
-
(g) FDFL, FDFU Series
Models FDFLJ28HKXE2, FDFUJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) Indoor air temperature 17.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 21.0°CWB 22.0°CWB TC 2.90 2.83 2.77 2.69 2.60 2.54 2.45 TC 2.98 2.92 2.85 2.78 2.72 2.63 2.55 TC 3.06 3.00 2.93 2.87 2.80 2.73 2.65 TC 3.12 3.07 3.02 2.95 2.88…
-
20.2.7 Characteristics of fan
(1) Cassetteria type (FDR) How to interpret the blower characteristics table ● External static pressure table Duct specs. Example : Case of FDRJ71HKXE2 1 2-spot blowout Square duct (3) 40(4) 45(4.5) 85(8.5) 45(4.5) 85(8.5) FDR45 56 type FDR71 type 14 - - 50(5) 85(8.5) 50(5) 18 30(3) 65(6.5) 45(4.5)…
-
Models FDRJ45HKXE2, 56HKXE2
-
Model FDRJ140HKXE2
-
(2) Satellite ducted type (FDUM)
● External static pressure table Duct specs. 1 spot closing Standard Square duct How to interpret the blower characteristics table Example : Case of FDUMJ71HKXE2 40(4) 90(9) 50(5) 90(9) 18 35(3.5) 70(7) 50(5) 85(8.5) 55(5.5) 90(9) FDUM90 type 20 30(3) 65(6.5) 50(5) 85(8.5) 55(5.5) 90(9) FDUM112 type…
-
Model FDUMJ71HKXE2
-
20.2.8 Noise level
-
Model FDTWJ90HKXE2B
-
(d) Cassetteria type (FDR)
Unit 1.5m Measured based on JIS B 8616 Mike position as below Mike (center & low points) Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Model FDRJ28HKXE2 Models FDRJ45HKXE2, 56HKXE2 Noise level 43 dB (A) at HIGH Noise level 44 dB (A) at HIGH 41 dB (A) at MEDIUM 41 dB…
-
Mid octave band frequency (Hz)
-
1m
-
Model FDKJ56HKXE2
Noise level 46 dB (A) at HIGH 43 dB (A) at MEDIUM 39 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Model FDKJ71HKXE2 Noise level 47 dB (A) at HIGH 44 dB (A) at MEDIUM 40 dB (A) at LOW Mid octave band frequency (Hz) Mid octave band…
-
BL
-
FMI
-
FMI1,2
-
BL
-
Mark
-
B
-
FMI
-
Parts name
-
(2) Individual flow divide controller
Power source (between indoor unit) Power source 1 phase 220/240V 50Hz Notes (1) This illustration shows the circuit diagram for when 1 indoor unit is connected with a central flow divide controller and relay kit (flow divide controller accessory). (2) “ ” denotes the local wiring. (3) The option…
-
CM
FM1,2 IM 52C 49F1,2 CH CF1,2 X1 X2 X3 X4 X7 X8~10 X11 X12 X13 X14 X20 20SS Mark Parts name Compressor motor Fan motor (outdoor unit) Motor for cooling inverter Magnetic contactor for CM Internal thermostat for FMo Crankcase heater Capacitor for FMo Auxiliary relay (for 52C) Auxiliary relay (for…
-
20.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
(1) Remote controller (Optional parts) FDR,FDUM,FDFL and FDFU series are not provided with AUTO SWING switch. Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for the purpose of explanation. Pull the knob on the cover to this side…
-
(2) Automatic Operation
Once the [Auto] mode is selected by remote control, the operating mode is automatically selected according to the setting temperature and the intake air temperature of the indoor unit and cooling or heating operation is performed. The determination is performed when the thermostat has been in the…
-
Dehumidifying (Thermal dry) D C Low -2 B A +2 ▲ High Room temperature setting point • Indoor unit fan will be operated in D block as shown below. 20 sec. Lo OFF 4 min. Temperature check (6) 22 model 28 model 36 model 45 model 56 model 71 model 90 model 112 model 140 model Compressor Indoor unit…
-
(7) Value shift adjustment of room air temperature detection in heating
Under the standard specifications, the room temperature is adjusted at the setting temperature by controlling the indoor unit capacity based on the setting temperature of thermostat and the suction air temperature. However, where the unit is installed in the ceiling and warm air tends to stay around…
-
(10) Condensate pump motor (DM) control (Only FDT, FDTW, FDTS, FDR, FDUM models)
(a) Drain motor is started no sooner than the compressor is turned ON during cooling or dehumidifying operation. The drain motor continues to operate for 2 minutes after the stop of unit operation, stop with the error stop, thermostat stop and at switching from cooling or dehumidifying operation to…
-
(11) Defrosting
(a) Conditions for starting defrosting When all the following conditions are met, the defrosting operation will start: -2°C Outdoor unit heat exchanger temp. (ThO-R) 1) The cumulative operating time of the compressor comes up to 45 minutes after completion of a defrosting operation, or it comes up…
-
(12) Multiple Units Control-Simultaneous Control of 16 unit with one remote controller
(a) Function Multiple units (even of outdoor different systems, 16 units maximum) can be simultaneously controlled by using a remote control switch (a special order item). The remote control switch is used to set the “operation mode”, and all the unit can be operated and stopped at intervals of 0.5…
-
Input signal to CnT becomes valid at OFF → ON only and the motion of air conditioner [ON/OFF] is inverted. ON CnT Input OFF A Unit OFF ON OFF OFF ON OFF OFF B Unit ON OFF (14) Snow Fan Control Set the dip switch SW3-3 (See page 1075) on the outdoor unit control circuit board to ON, and the outdoor…
-
Under these controls, the high and low level pressures are controlled with the solenoid valves, outdoor fan and other so as to operate the outdoor unit in the optimum condition in accordance with changing load on the indoor unit. Operation patterns consist of the following 12 types and respective…
-
(17) Compressor operating frequency increase control
(a) In the case that at least one in-door unit requires the maximum frequency supply during cooling or heating operation for 6 minutes continuously, the compressor operating frequency is increased by 10 Hz. After that, the maximum frequency is increased by 10 Hz every continuous 6 minutes; however…
-
(19) Devices related to unit protection and maintenance
(a) Test Run Mode The test run mode can be set from the outside by using the switch SW3-4,5 on the outdoor unit control circuit board (i) Switch function Switch SW3-4 SW3-5 Function ON • To operate all connected indoor units. • Indoor units demands the maximum frequency and outdoor units are…
-
(iii) Three minutes delay timer
The compressor (inverter) will remain in stop state for 3 minutes, when the compressor is stopped by thermostat, ON/OFF swich, and /or by occurrence of trouble. When the power source is turned ON, the 3-minutes delay timer is cancelled. (f) Detection Control of Electricity Supply to Crank Case…
-
(k) Protection of Power Transistor from Overheat
When the temperature of the power transistor increases to the set temperature, stop the inverter immediately and let is reset by itself 3 minutes later. If the power transistor is overheated again within 2 hours, turn off 52C, bring it to an abnormal stop and the inspection displays (Remote…
-
20.5 APPLICATION DATA
SAFETY PRECAUTIONS • Please read these “Safety Precautios” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in…
-
20.5.1 Installation of indoor unit
This is same as multi KX series. Refer to page 841~881. 20.5.2 Installation of the remote controller (Optional parts) This is same as multi KX series. Refer to page 882. 20.5.3 Installation of outdoor unit (1) Selection of installation location (a) A palce where air will not be stagnant. (b) A place…
-
When there is an obstacle above the unit
Note (1) The side air outlet indicates that a wind direction variable adapter available on the optional parts is fitted to the unit. 3) When there is an obstacle (are obstacles) on the side (in front side of and at the rear side) of the unit 4) When there is an obstacle above the unit as well 5)…
-
Installation where there is obstacle on all four sides. Note (1) The up air outlet indicates that a wind direction variable adaptor available on the optional parts is fitted on the unit. (b) Installation of multiple units 1) Continuous installation on side-to-side [The front side is open] [Keep a…
-
3) Face-to-face installation
Dimension Distance L1 Item Diagonal 1500 or more 1000 or more 500 or more 500 or more Up air outlet Unit: mm L2 Note (1) Make the air outlet the diagonal air outlet (standard) or the up air outlet (option). 4) Side-to-side & face-to-face installation [Keep a space of more than 10 mm between the…
-
(3) Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following. (a) Fix the unit to the foundation with anchor bolts. Unit: mm 1050 (b) When installing the unit, be sure to fix the pedestal of the unit with bolts. (c) Install the unit securely…
-
20.5.4 Refrigerant piping
(1) Precautions no refrigerant piping work for prevention against compressor lock Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant piping conditions, The precautions for refrigerant piping are as belows. (a) Be sure to…
-
(2) Refrigerant piping size selection
-
(Example)
Outdoor unit Discharge gas piping Liquid piping Intake gas piping Flow divider pipe set for vertical divides Indoor unit Individual flow divide controller (DIS-V1KXR3E) Indoor unit Individual flow divide controller When the outdoor unit are installed at a higher level than the individual flow divide…
-
Good
Note 1: When making branch connections (for both gas and liquid lines), be sure that the proper horizontal branches and vertical branches are used. No No Vertically Good Floor Floor Horizontally Floor Floor • Selection piping size Item Piping size(mm) Selection procedure A Same as the outdoor unit…
-
(3) Specification of unit piping (Pipe diameter. Connecting method)
(a) Unit 1) Outdoor unit Unit: mm (in) Item 2) Gas line Model Pipe diameter FDCP2001HKXRE2 φ25.4 (1") FDCP2501HKXRE2 φ28.58 (1 1/8") Pipe diameter Connecting method φ12.7 (1/2") Brazing Brazing φ12.7 (1/2") Indoor unit Unit: mm (in) Gas line Item Pipe diameter Model 3) Liquid line Connecting method…
-
(c) How to connect piping
1) Connection to front directions. a) Remove the front hall blank, pass through he hole the intake gas side, gas side and liquid pipes. and then connect then to the service valves and the on-site piping. (Because the liquid side pipe is on-site piping, bend it to the dimensions shown in the…
-
(4) Heat insulation
(i) There is a need to insulate both gas and liquid piping with heat insulation for protection against heat and condensation. 1) Always use heat insulation to prevent condensation on the gas piping from becoming drain water and causing leakage during cooling and to prevent people from being burned…
-
(7) Refrigerant charge amount
(a) Additional; charge amount Item Additional charge amount per 1 m of liquid pipe Factory charge amount at time of shipment Indoor unit φ12.7 φ9.52 φ6.35 Outdoor unit Model FDCP2001HKXRE2 0.12 kg/m 0.06 kg/m 0.03 kg/m 11.0 kg Holding charged FDCP2501HKXRE2 Remarks Additional refrigerant Charge is…
-
(c) Individual flow divide controller (Same power supply with the indoor units)
Power supply wiring thickness (mm2 × number of wires) Item Power supply Supported model Signal wire thickness (mm2 × number of wires) 1-phase 2.0/2.0 × 2 220/240V 50Hz Note (1) Do not misconnect the central flow divide controller signal wire. 2.0 × 2 HPFD1R-E (2) Precaution in electric wiring. (a)…
-
Outdoor/Indoor units connection procedures
Outdoor unit AB Individual flow divide controllor Power source (indoor unit side) Power source wire [Individual flow divide controller accessory wire (2m) To next units by turn L • N C N U Individual flow divide controller accessory wire (2m) Cn Cn B T4 Cn T L • N AB XYZ C N U Cn Cn B T4 1 Relay kit…
-
(b) If plural outdoor units are used
1) A maximum of 48 indoor units can be connected by using the crossover wiring method, with 2 wires for each side of the outdoor and indoor units. Outdoor unit Outdoor unit AB AB Outdoor unit Outdoor unit AB AB Double cores 0.75 ~ 2 mm2 Total length of signal wires: 1000 m or less AB AB AB AB Indoor…
-
(b) When controlling plural units
1) Use the same procedure shown in the drawing above for the wiring of the power supply, both indoor and outdoor units and remote controller When the wiring length for the remote controller exceeds 100 m, use the wiring procedure shown in the drawing below. 2) Connect each of the indoor units for…
-
(6) Setting of unit address
Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning power on. Indoor unit Outdoor unit…
-
2) 3) Set the address switch of outdoor unit at 49. (This is set at 49 at shipment from factory.) Set the address switch of indoor unit at 49. (This is set at 49 at shipment from factory) Turn power on for the indoor and outdoor units. Addresses are set automatically. (No. in a range of 0 - 11.) For…
-
Detail of setting from the remote controller
1) If the power switch is turned on, the outdoor No. on the display flashes, and "--" on the return air temperature display section and "U--" on the time display section are lit. If power is not supplied to the outdoor unit, the outdoor No. only lights and you cannot set the address. In such…
-
20.5.6 Test run
(1) Before starting operation (a) Measure resistances between the electrical parts terminal block and grounded area using a 500 V Megger, insulator. Resistance must be higher than 1 MΩ. (b) Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hours to…
-
(3) Cooling test run operation (Cooling test run can be performed in winter.)
(a) Operation method ● In the normal cooling mode, hold down the “Temperature Set” switch while pushing the “Set” switch. ● Setting temperature is changed at 5˚C and the cooling test run is operated for 30 minutes. It stops after 30 minutes. (b) During cooling test run operation ● If ON/OFF switch…
-
20.6. MAINTENANCE DATA
20.6.1 Diagnosis of Microcomputer circuit (1) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs of indoor/ outdoor units The microcomputer detects errors on electrical components, whitch include the…
-
1 time flash
Stays OFF 2 time flash Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing E10 E11 E12 Keeps flashing 1 time flash Keeps flashing E9 E28 Stays OFF Keeps flashing E7 Stays OFF Stays OFF 1 time flash 1 time flash 1 time flash Keeps flashing E6 2 time flash Keeps…
-
Keeps flashing
Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing…
-
3) Display sequence of error, inspection display lamp
a) One kind error Display corresponding to the error is shown. b) More than one errors. Section Error code of remote controller Display section • Displays the error of higher prority (When plural errors are persisting.) Inspection LED(red) of indoor unit PCB Inspection LED (red) of outdoor unit PCB…
-
• Outdoor unit side
Error detail Error code Timing of error detection 52C secondary side L3-phase wiring is open. An abnormal stop occurs when the L3-phase voltage is 0 V for 5 seconds running. (Detected with 52C ON only) Discharge temperature abnormality A stop occurs when this abnormality occurs for 2 seconds running…
-
(a) Diagnosis by the power supply reset
When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc. Check at the indoor unit side. Error Are the return air temperature and Center/ Remote displayed on the remote controller? YES Is any error code display? NO NO YES Check the error…
-
Reference Effect of noise
• When noises inturude into the remote controller. Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote controller and…
-
(ii) Parts layout on the outdoor unit PCB
Operation output • Function of DIP switch CNH 2 Name CNY(White) 2 CNI(White) L6 7 2 L9 ON IC4 SW2 CNE(White) X1 9 83 ON External input SW3-2 Outdoor unit number address setting switch (SW: Order of 1) OFF ON SW3-3 OFF Outdoor unit number address setting switch (SW: Order of 10) Name ON Checker 6 IC3…
-
(iii) Check procedure depending on indication lamps (For the outdoor unit)
1 [Error on the outdoor unit signal line] Error display: (Detected during operation only) Indoor unit Red LED 2 time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF Power supply checked between R~N or terminal block YES Is there AC 17V checked between CNA2 (blue) ~…
-
[Outdoor unit signal line error, power supply error]
Error display: Indoor unit Red LED 2time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF (1) Did turn off the power of outdoor unit during operation? YES Power supply ON NO(1) • Blown fuse? • Broken or loose wire at L1, L2 or N Phase? • Was not there the power…
-
[Duplicated unit No. of outdoor units] Error display: Indoor unit Stays OFF Keeps flashing Red LED Green LED Red LED Green LED Is the unit No. duplicated on outdoor units? YES Outdoor unit 8 time flash Keeps flashing Correction NO Defective outdoor unit PCB Replacement (Defective unit No. read…
-
[Defective outdoor unit heat exchanger thermistor] Error display: Outdoor unit Indoor unit Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Keeps flashing Is the outdoor unit heat exchanger hermistor connector OK? YES Are the outdoor unit heat exchnger thermistor…
-
[Defective discharge gas thermistor]
Error display: Outdoor unit Red LED Stays OFF Red LED Keeps flashing Green LED Keeps flashing Green LED Keeps flashing Is the discharge gas thermistor connector connection OK? Are thr discharge gas thermistor characteristics OK, is there no broken wire? YES NO NO Defective discharge gas thermistor →…
-
[Power transistor overheating] Error display: Outdoor unit Indoor unit Red LED Stays OFF Red LED 4 time flash Green LED Keeps flashing Green LED Keeps flashing Does the FMO rotate? YES Power transistor overheating(1) Is the outdoor unit installation space proper? YES NO Does the IM (Inverter cooling…
-
Current cut is indicated and the compressor cannot operate
Is the insullaiton resistance of the compressor(1) proper? Disconnect the compressor wiring NO Defective compressor YES The compressor can operate Is the current cut function activated? Notes (1) When a short-circuit or ground-fault occurs in the compressor motor, the current cut function is also…
-
[Excessive number of indoor units connected] Error display: Outdoor unit Indoor unit Red LED Stays OFF Red LED 7 time flash Green LED Keeps flashing Green LED Keeps flashing (1) Doesn't the number of indoor unit connected exceed the specified value? YES Repair Notes (1) The maximum number of…
-
• When communication is checked by the connector CnI, each value will be as follows
Contents of communication Connector CnI 14 Common 2 12V power supply 3 Transmission from outdoor unit Swings at 11~11.5V 4 Reception from outdoor unit Swings at 4.5~5V 5 Watch dog (communication from inverter PCB to outdoor unit PCB) Swings at 2~4V 6 Inverter overheat 7 Current cut 5V: normal 0V…
-
Louver motor does not operate
Inspect at the indoor unit side. Does the louver operate at power on? Operate more than 1 min. later NO Is LM wire bloken? NO Is LM locked? YES YES Repair the wire Replace LM YES Is the louver YES operated with the remote controller NO Defective indoor unit PCB Normal NO Note (1) LM:Louver motor…
-
Heating operation does not start NO Is heat outputted? Defective indoor unit PCB → Replace. YES (1) Are solenoid valve control relays OK? NO Defective relay → Replace. YES Is AC 200V applied at shunt controller connector CnB? YES Defective SVH (high pressure gas side solenoid valve) → Replace. 1086…
-
(3) When the remote controller indication is nomal but the compressor cannot operate
(No check indication) • Give instructions so that the requested best frequency may be output, irrespective of the thermostat condition, from outdoor to indoor. A ccordingly, if the indoor/outdoor transmission is faulty, the compressor cannot operate. • When the SW3-4 is turned on, error indication…
-
(4) Proceduer for checking the outdoor unit irrespective of indoor/outdoor transmission
Turn off the outdoor unit power supply (Or pull out the connector CnA2 on the outdoor unit PCB) Set 45 in outdoor unit No. Turn ON the outdoor unit PCB(SW3-7) Turn ON the outdoor unit power supply Open the 63H1 Is the 52C turnd ON? (When connecting the CnA2 on the outdoor unit PCB) (Pull out Faston…
-
(5) Procedure for checking the inverter (No output is provided at the compressor (U,V and W).)
NO Is the 52C ON? Check the control PCB on the outdoor unit side NO Power line failure NO Does the LD1 (green) on the inverter PCB flash? Does DC280V appear at the connector Cn2 on the inverter PCB NO (3) The remote controller error code E45 is indicated (See page 1083) YES YES Turn OFF the power…
-
◆ Troubleshooting on the inverter side
(1) Troubleshooting procedure (For the details of 1 to 7, refer to Outfoor Unit Check Pointd on the next page.) NO Check the outdoor unit control PCB. NO Is DC280V is YES provided at the Cn2 on the inverter PCB? Is 52C turned ON? Does the LD1 (green) on the inverterYES PCB flashing YES Defective…
-
N
L3 L2 L1 TB Red Green LED1 LED2 Control board the microcomputer is normal. LED2 check: If this * Normality LED flashing, the operation of CNA2 CNA1 52C Noise filter When the tester bars are reversed, the resistance value is about 10 ~ 20 Ω 8 ~ ~ ~ Cn1 Inverter overheating Current cut Reception from…
-
19.2.1 Specifications
(1) Indoor unit FDTJ28HKXE2 36HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDTWJ28HKXE2B 45HKXE2B 56HKXE2B 71HKXE2B 90HKXE2B 112HKXE2B 140HKXE2B FDTSJ22HKXE2B 28HKXE2B 36HKXE2B 45HKXE2B 71HKXE2B FDRJ22HKXE2 28HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDUMJ36HKXE2 45HKXE2…
-
19.2.3 Exterior dimensions
(1) Indoor unit FDTJ28HKXE2 36HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDTWJ28HKXE2B 45HKXE2B 56HKXE2B 71HKXE2B 90HKXE2B 112HKXE2B 140HKXE2B FDTSJ22HKXE2B 28HKXE2B 36HKXE2B 45HKXE2B 71HKXE2B FDRJ22HKXE2 (Silent Panel) (Canvas Panel) FDUMJ36HKXE2 28HKXE2 (Silent Panel) (Canvas Panel)…
-
19.2.6 Selection chart
(1) Correct the cooling and heating capacity in accordance with the conditions as follows. (2) Correction Correction of of outdoor outdoor unit unit capacity capacity according according to to capacity capacity of indoor unit to be operated simultaneously FDCJ/FDCP140HKXE2B 224HKXE2B 280HKXE2B…
-
19.3.1 Electrical wiring
(1) Indoor unit (a) Ceiling recessed type(FDT) Modles All models (b) 2-Way outlet ceiling recessed type(FDTW) Models All models (c) 1-Way outlet ceiling recessed type(FDTS) Models All models (d) Cassetteria type(FDR) Models All models (e) Satellite ducted type(FDUM) Models All models (f) Ceiling…
-
APPLICATION DATA SAFETY PRECAUTIONS 19.5.1 Installation of indoor unit (1) Ceiling recessed type(FDT) (2) 2-Way outlet ceiling recessed type(FDTW) (3) 1-Way outlet ceiling recessed type(FDTS) (4) Cassetteria type(FDR) (5) Satellite ducted type(FDUM) (6) Ceiling suspension type(FDE) (7) Wall mounted…
-
19.6 MAINTENANCE DATA
-
20.2.1 Specifications
(1) Indoor unit FDTJ28HKXE2 36HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDTWJ28HKXE2B 45HKXE2B 56HKXE2B 71HKXE2B 90HKXE2B 112HKXE2B 140HKXE2B FDTSJ22HKXE2B 28HKXE2B 36HKXE2B 45HKXE2B 71HKXE2B FDRJ22HKXE2 28HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDUMJ36HKXE2 45HKXE2…
-
20.2.3 Exterior dimensions
(1) Indoor unit FDTJ28HKXE2 36HKXE2 45HKXE2 56HKXE2 71HKXE2 90HKXE2 112HKXE2 140HKXE2 FDTWJ28HKXE2B 45HKXE2B 56HKXE2B 71HKXE2B 90HKXE2B 112HKXE2B 140HKXE2B FDTSJ22HKXE2B 28HKXE2B 36HKXE2B 45HKXE2B 71HKXE2B FDRJ22HKXE2 (Silent Panel) (Canvas Panel) FDUMJ36HKXE2 28HKXE2 (Silent Panel) (Canvas Panel)…
-
20.2.6 Selection chart
(1) Correct the cooling and heating capacity in accordance with the conditions as follows. (2) Correction Correction of of outdoor outdoor unit unit capacity capacity according according to to capacity capacity of indoor unit to be operated simultaneously Alternative refrigerant R407C use models…
-
20.3.1 Electrical wiring
(1) Indoor unit (a) Ceiling recessed type(FDT) Modles All models (b) 2-Way outlet ceiling recessed type(FDTW) Models All models (c) 1-Way outlet ceiling recessed type(FDTS) Models All models (d) Cassetteria type(FDR) Models All models (e) Satellite ducted type(FDUM) Models All models (f) Ceiling…
-
APPLICATION DATA SAFETY PRECAUTIONS 20.5.1 Installation of indoor unit (1) Ceiling recessed type(FDT) (2) 2-Way outlet ceiling recessed type(FDTW) (3) 1-Way outlet ceiling recessed type(FDTS) (4) Cassetteria type(FDR) (5) Satellite ducted type(FDUM) (6) Ceiling suspension type(FDE) (7) Wall mounted…
-
20.6.1 Diagnosis of Microcomputer circuit
(1) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs of indoor/ outdoor units (P1068 ~ P1072) (2) Procedures of trouble diagnosis (P1072 ~ P1087) (3) When the remote controller indication is nomal…