15. HIGH STATIC PRESSURE,
DUCT TYPE PACKAGED AIRCONDITIONER Split system, Air to air heat pump type ( FDU308HEN-SA 308HES-SA 408HES-SA 508HES-SA 808HES-SA 1008HES-SA ) FDU308HEN-A 308HES-A 408HES-A 508HES-A 508HEM-A 579
-
15.1 GENERAL INFORMATION
15.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
15.2 SELECTION DATA
15.2.1 Specifications Model FDU308HEN-SA FDU308HEN-SA Model Item FDU308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.20/3.40 Running current (Cooling) A 14.8/15.4 Power factor (Cooling) %…
-
Model FDU308HES-SA
FDU308HES-SA Model Item FDU308-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Noise level Exterior dimensions Height × Width ×…
-
Model FDU408HES-SA
FDU408HES-SA Model Item FDU408-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Noise level Exterior dimensions Height × Width ×…
-
Model FDU508HES-SA
FDU508HES-SA Model Item FDU508-A Nominal cooling capacity(1) Nominal heating capacity(1) Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Inrush current (L.R.A) Noise level Exterior dimensions Height × Width ×…
-
Model FDU808HES-SA
FDU808HES-SA Model Item FDU808-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC808HES3 20000 21200 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 9.1/9.2 Running current (Cooling) A 16.2/15.5 Power factor (Cooling) % 85/83 Heating input kW 7.1/7.3 Running…
-
Model FDU1008HES-SA
FDU1008HES-SA Model Item FDU1008-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC1008HES3 25000 28000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 12.8/12.9 Running current (Cooling) A 22.7/21.7 Power factor (Cooling) % 86/83 Heating input kW 10.6/10.8…
-
Model FDU308HEN-A
FDU308HEN-A Model Item FDU308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC306HEN3 7100 7300 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.29/3.33 Running current (Cooling) A 16.5/17.3 Power factor (Cooling) % 91/80 Heating input kW 3.04/3.08 Running…
-
Model FDU308HES-A
FDU308HES-A Model Item FDU308-A Nominal cooling capacity(1) (1) FDC306HES3 7100/7700 6000 7300/7900 3 Phase, 380-415V 50Hz, 380V 60Hz 3.05/3.06/3.64 5.9/6.0/7.1 79/71/78 2.72/2.74/3.19 5.5/5.7/6.7 75/67/72 3.87 7.6 77 43 41/43 56 W W ISO-T1 kW A % kW A % kW A % A dB(A) ISO-T3 Operation data(3)…
-
Model FDU408HES-A
FDU408HES-A Model Item FDU408-A Nominal cooling capacity(1) (1) FDC406HES3 10200/11300 9900 10500/11600 3 Phase, 380-415V 50Hz, 380V 60Hz 3.96/3.96/4.88 7.8/7.8/9.4 77/71/79 3.66/3.66/4.51 7.5/7.5/9.1 74/68/75 5.38 10.1 81 45 44/46 57 W W ISO-T1 kW A % kW A % kW A % A dB(A) ISO-T3 Operation data(3)…
-
Model FDU508HES-A
FDU508HES-A Model Item FDU508-A Nominal cooling capacity(1) (1) FDC506HES3 12500/14000 11900 12800/14400 3 Phase, 380-415V 50Hz, 380V 60Hz 5.01/5.03/6.03 10.3/10.3/11.5 74/68/80 4.63/4.67/5.61 9.5/9.6/10.7 74/68/80 6.63 12.5 81 68 45/47 59 W W ISO-T1 kW A % kW A % kW A % A dB(A) ISO-T3 Operation…
-
Model FDU508HEM-A
FDU508HEM-A Model Item FDU508-A Nominal cooling capacity(1) (1) ISO-T1 ISO-T3 Operation data(3) Nominal heating capacity Power source Cooling input Running current (Cooling) Power factor (Cooling) Heating input Running current (Heating) Power factor (Heating) Cooling input Running current (Cooling)…
-
15.2.2 Range of usage & limitations
Models FDU308~1008, (FDC308~1008 type) Models Item FDU308~1008(FDC308~1008 type) Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Indoor unit atmosphere (behind ceiling) temperature and humidity Dew point temperature: 28˚C…
-
15.2.3 Exterior dimensions
(1) Indoor unit Models FDU308-A, 408-A Unit : mm 138 138 Return air duct (M5 × 12 pcs.) Holes for screws (Duct for dimension) 35 VIEW A Control box Liquid piping Gas piping ø9.52 (3/8") 308 type : ø15.88 (5/8") 408 type : ø19.05 (3/4") Suspension bolts (M10 × 4 pcs.) 13 13 Hole for wiring Supply air…
-
Model FDU508-A
Unit : mm 138 138 Return air duct (M5 × 16 pcs.) × 200 = 1100 (Duct for dimension) 1200 250 13 Holes for screws 13 18 (Duct for dimension) 60 794 (Suspension bolts pitch) 18 1270 (Suspension bolts pitch) 1320 25 830 ø9.52 (3/8") ø19.05 (3/4") 250 (Duct for dimension) Control box Gas piping 60 Liquid…
-
Unit : mm 60 138 Holes for screw (M5 × 20 pcs.) × 200 = 1200 1500 (Duct for dimension) 163 25 Return air duct 1570 250 (Duct for dimension) 18 1640 (Suspension bolts pitch) 1690 (Suspension bolts pitch) 18 Liquid piping Gas piping 808: ø12.7 (1/2") 1008: ø15.88 (5/8") 808: ø25.4 (1") 1008: ø28.58 (1…
-
(2) Remote controller (Optional parts)
Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 83.5 For the passage after wiring ♦ Usable JIS box, JIS C 8336 ⋅ Switch box for 1 piece (without cover) (use of the mark hole as illustrated on the left) ⋅ Switch…
-
(3) Outdoor unit
Models FDC308HEN3, 308HES3 Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for electric…
-
Models FDC408HES3, 508HES3
Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 (1050) Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and electric wiring Opening…
-
Unit: mm
Models FDC808HES3, 1008HES3 600 50 1350 1450 Opening for exit wiring (ø50) ( ) Power supply connecting terminal block 291.5 Opening for exit piping (ø88) 80 A Connect of liquid piping 808: ø12.7 (1/2") 1008: ø15.58 (5/8") 80 Connect of gas piping 170 ø25.4 (1") ( 1008:808:ø28.58 (1 1/8") ) Downward…
-
Models FDC306HEN3, 306HES3
580 380 Unit: mm Anchor bolts (M10 × 4 pcs) Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type 1 2 L1 Open Open 500 L2 300 0 Open L3 Mark 3 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet.…
-
Models FDC406HES3, 506HES3, 506HEM3
Unit: mm 380 580 Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type L1 Open Open 500 L2 300 0 Open L3 Mark 602 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit…
-
15.2.4 Exterior appearance
(1) Indoor unit Zinc steel plate (2) Outdoor unit Models FDC308HEN3, 308HES3 Models FDC408HES3, 508HES3 Polar white Polar white Models FDC808HES3,1008HES3 Polar white Models FDC306HEN3, 306HES3 Models FDC406HES3, 506HES3 506HEM3 Polar white Polar white 603
-
15.2.5 Piping system
Models FDU308HEN-SA, 308HES-SA, 408HES-SA Cooling cycle Heating cycle Indoor unit Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Gas line Strainer Service valve (Flare connecting) 308:ø15.88 ( 408:ø19.05 ) Heat exchanger Check joint Thermistor (ThI-A)…
-
Models FDU808HES-SA, 1008HES-SA
Cooling cycle Indoor unit Outdoor unit Heating cycle Service valve High pressure switch(63H2) (Brazing) (For fan motor control) Thermistor (ThO-A) Brazing Strainer Gsa line 808 : ø25.4 1008 : ø28.58 ( ) 4way valve High pressure switch(63H1) Thermistor (ThI-A) Lower Heat exchanger Upper (For…
-
Models FDU408HES-A, 508HES-A, 508HEM-A
Cooling cycle Heating cycle Service valve (Flare connecting) Indoor unit Check joint Strainer Gas line (ø19.05) Outdoor unit High pressure switch (For fan motor control) Strainer 4way valve Check joint Thermistor (ThI-A) Heat exchanger Accumlator Heat exchanger Check joint Thermistor (ThI-R) Defrost…
-
15.2.6 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and heating capacity in…
-
Cooling operation
Heating operation Indoor air D.B. temperature (˚CD.B.) Outdoor air D.B. temperature (˚CD.B.) Coefficient of cooling and heating capacity in relation to temperatures (C) Only case of ISO-T3 and SASO models Indoor air W.B. temperature (˚CW.B.) ISO-T1 Standard condition ISO-T1 Standard condition…
-
(3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor and outdoor units. 50/60Hz (1) Equivalent piping length m Heating Cooling FDU308 type (FDC308 type) FDU408 type (FDC408 type) FDU508 type (FDC508 type) FDU808, 1008 type…
-
15.2.7 Characteristics of fan
How to interpret the blower characteristics table Example ¡What is the Fan Controller’s Volume Number setting if, at the high operation speed of FDU308-A (60Hz), it is required to have 140Pa (14mmAq) outside static pressure at 24m3/min airflow volume as the operation point? Move the 140Pa (14mmAq)…
-
High Low 200 (20) Model FDU408-A (60Hz) • Condition of standard rating (Air flow : 100 (10) Pa (mmAq) 200 (20) High Low • Condition of standard rating (Air flow : 100 (10) Pa (mmAq) Example of duct (15) Outside static pressure Pa (mmAq) 150 (15) Outside static pressure Pa (mmAq) (10) (10) (5) 50 (5)…
-
Model FDU808-A
High Low • Condition of standard rating (Rated air volume : 100 (10) Pa (mmAq) 200(20) 8 7 Example of duct Static pressure Pa(mmAq) 150(15) 100(10) 50(5) 5 4 0(0) Lower limit 60 65 Upper limit Standard Air flow (m3/min) Model FDU1008-A High Low • Condition of standard rating (Rated air volume : 100…
-
15.2.8 Noise level
-
(2) Outdoor unit
Models FDC308HEN3, 308HES3 Noise level 52 dB (A) N50 40 40 N40 N60 50 50 N50 40 40 N40 30 30 1000 2000 4000 N50 40 40 N40 30 30 1000 2000 N2 20 8000 4000 N30 1000 2000 Mid octave band frequency (Hz) Model FDC408HES3 Model FDC406HES3 Model FDC508HES3 70 N70 50 N50 40 N40 N50 40 40 N40 30 30 N30 1000…
-
RD
-
CT1
-
таблицы и схемы — в просмотре
-
RD
-
(49C)
-
BL
-
WH
-
T
-
15.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 317. 15.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two…
-
NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATION. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to Mitsubishi…
-
(3) Duct work
1 Air filter is not installed in the main unit of air conditioner. Air filter should be installed in the suction grill 3A 3 Canvas coupling 3 Canvas coupling which allows an ample access for cleaning. 2 Silencer chamber(s) may be necessary depending on the OA noise level allowed in the room where…
-
(d) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30 (11/4˝) or thicker pipe this purpose. (e) Be sure to provide heat insulation to hard PVC pipes of indoor placement. (f) Do not ever…