Инструкция на Кондиционеры серии FDT(N)-H
Кондиционеры серии FDT(N)-H. Инструкция по монтажу и эксплуатации.
Смотрите также: Коды ошибок: 6 кодов →
Загружаем документ…
Текст инструкции
-
8. CEILING RECESSED TYPE
PACKAGED AIR-CONDITIONER Split system, Air to air heat pump type ( ) Refrigerant R22 use models FDTN208HEN-S1 FDT208HEN-SA FDT308HEN-A 308HES-A 258HEN-S1 258HEN-SA 408HES-A 308HEN-SA 308HES-SA 508HES-A 408HES-SA 508HES-SA Alternative refrigerant R407C use models FDTNP208HEN-S 258HEN-S 308HEN-S…
-
GENERAL INFORMATION 8.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer…
-
SELECTION DATA 8.2.1 Specifications (1) Refrgerant R22 use models (a) Wireless remote controller type Model FDTN208HEN-S1 FDTN208HEN-S1 Model Item FDTN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC208HEN3A 5000 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling…
-
Model FDTN258HEN-S1
FDTN258HEN-S1 Model Item FDTN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.05/2.16 Running current (Cooling) A 9.4/9.4 Power factor (Cooling) % 99/96 Heating input kW 1.95/2.10 Running…
-
(b) Wired remote controller type
Model FDT208HEN-SA FDT208HEN-SA Model Item FDT208-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC208HEN3A 5000 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 1.78/1.87 Running current (Cooling) A 8.3/8.1 Power factor (Cooling) % 97/96 Heating input kW…
-
Model FDT258HEN-SA
FDT258HEN-SA Model Item FDT258-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.05/2.16 Running current (Cooling) A 9.4/9.4 Power factor (Cooling) % 99/96 Heating input kW 1.95/2.10 Running…
-
Model FDT308HEN-SA
FDT308HEN-SA Model Item FDT308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.98/3.18 Running current (Cooling) A 13.9/14.4 Power factor (Cooling) % 97/92 Heating input kW 2.84/3.00 Running…
-
Model FDT308HES-SA
FDT308HES-SA Model Item FDT308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC308HES3 7100 8000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 2.90/2.96 Running current (Cooling) A 5.1/5.5 Power factor (Cooling) % 86/75 Heating input kW 2.54/2.60 Running…
-
Model FDT408HES-SA
FDT408HES-SA Model Item FDT408-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC408HES3 10000 11200 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 4.50/4.60 Running current (Cooling) A 7.8/8.1 Power factor (Cooling) % 88/79 Heating input kW 3.88/3.92 Running…
-
Model FDT508HES-SA
FDT508HES-SA Model Item FDT508-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC508HES3 12500 14000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 5.30/5.55 Running current (Cooling) A 9.5/10.3 Power factor (Cooling) % 85/75 Heating input kW 4.85/4.98 Running…
-
Model FDT308HEN-A
FDT308HEN-A Model Item FDT308-A Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC306HEN3 7100 7300 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.07/3.11 Running current (Cooling) A 15.6/16.3 Power factor (Cooling) % 89/79 Heating input kW 2.82/2.86 Running…
-
Model FDT308HES-A
FDT308HES-A Model Item FDT308-A Nominal cooling capacity(1) FDC306HES3 7100/7700 6000 7300/7900 3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz 2.83/2.84/3.35 5.3/5.3/6.0 81/75/85 2.50/2.52/2.90 4.9/5.0/5.6 78/70/79 3.58 6.5 84 43 Hi:41 Lo:35 56 Unit 260 × 840 × 840 844 × 950 × 340 Panel 30…
-
Model FDT408HES-A
FDT408HES-A Model Item FDT408-A Nominal cooling capacity(1) FDC406HES3 10200/11300 9900 10500/11600 3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz 3.78/3.78/4.65 7.5/7.5/8.8 77/70/80 3.48/3.48/4.28 7.2/7.2/8.5 73/67/77 5.15 9.5 82 45 Hi:48 Lo:40 57 Unit 320 × 840 × 840 1250 × 950 × 340…
-
Model FDT508HES-A
FDT508HES-A Model Item FDT508-A Nominal cooling capacity(1) FDC506HES3 12500/14000 11900 12800/14400 3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz 4.87/4.87/5.83 10.0/10.0/11.0 74/68/81 4.49/4.51/5.41 9.2/9.3/10.2 74/67/81 6.43 12.0 81 68 Hi:49 Lo:43 59 Unit 320 × 840 × 840 1250 × 950 ×…
-
(2) Alternative refrigerant R407C use models
(a) Wireless remote controller type Model FDTNP208HEN-S FDTNP208HEN-S Model Item FDTN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP208HEN3A 5000 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.09/2.16 Running current (Cooling) A 9.6/9.7 Power…
-
Model FDTNP258HEN-S
FDTNP258HEN-S Model Item FDTN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.36/2.56 Running current (Cooling) A 11.4/12.6 Power factor (Cooling) % 94/85 Heating input kW 2.10/2.35…
-
Model FDTNP308HEN-S
FDTNP308HEN-S Model Item FDTN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.21/3.36 Running current (Cooling) A 14.9/15.3 Power factor (Cooling) % 98/92 Heating input kW 2.96/3.10…
-
Model FDTNP308HES-S
FDTNP308HES-S Model Item FDTN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HES3 7100 8000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 3.13/3.28 Running current (Cooling) A 5.5/5.8 Power factor (Cooling) % 86/79 Heating input kW 2.98/3.12 Running…
-
Model FDTNP408HES-S
FDTNP408HES-S Model Item FDTN408H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP408HES3 10000 11200 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 4.55/4.67 Running current (Cooling) A 8.0/8.4 Power factor (Cooling) % 86/77 Heating input kW 4.39/4.51 Running…
-
Model FDTNP508HES-S
FDTNP508HES-S Model Item FDTN508H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP508HES3 12500 14000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 5.41/5.48 Running current (Cooling) A 9.7/10.0 Power factor (Cooling) % 84/76 Heating input kW 5.29/5.36…
-
Range of usage & limitations Models FDTN208, 258 (FDC208, 258 type), FDTNP208~508 (FDCP208~508 type) FDT208~508 (FDC208~508 type) Models Item FDTN208, 258 (FDC208, 258 type) FDT208, 258 (FDC208, 258 type) FDTNP208, 258 (FDCP208, 258 type) FDT308~508 (FDC308~508 type) FDTNP308~508 (FDCP308~508 type)…
-
Exterior dimensions (1) Indoor unit Models FDTN208H, FDT208-A Unit : mm 740 (Ceiling hole size) Decorative Panel 430 Fresh air opening for ducting 800 (Suspension bolts pitch) C 515 → 680 (Suspension bolts pitch) Exhaust air opening for ducting → D 570 B→ Indication board (Only case of FDTN type)…
-
FDT258-A, 308-A Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 Indication boad…
-
FDT408-A, 508-A Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 Indication board…
-
(2) Remote controller
(a) Wireless remote controller AUTO COOL DRY FAN HEAT FAN HI LO Unit: mm FILTER ¡ °C ON AM PM TEMP ON/OFF 161.5 MODE Indcation board of indoor unit OFF AM PM 20.5 60 (b) Wired remote controller Unit: mm Remote controller mounting dimensions Wall 2 0.3mm , 3cores (O.D.φ5.6) 120 Wire (Recessed) LCD…
-
(3) Outdoor unit
Models FDC208HEN3A FDCP208HEN3A Unit: mm Liquid piping: φ 6.35 (1/4") (Flare connecting) Gas piping: φ 15.88 (5/8") (Flare connecting) 95 Liquid piping: φ 6.35 (1/4") (Flare connecting) Terminal block Gas piping: φ 15.88 (5/8") (Flare connecting) 110 Opening for electric wiring Opening for piping…
-
Models FDC258HEN3A, 308HEN3, 308HES3
FDCP258HEN3A, 308HEN3, 308HES3 Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for electric…
-
Models FDC408HES3, 508HES3
FDCP408HES3, 508HES3 Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 (1050) Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and…
-
Models FDC306HEN3, 306HES3
580 380 Unit: mm Anchor bolts (M10 × 4 pcs) Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type 1 2 L1 Open Open 500 L2 300 0 Open L3 Mark 3 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet.…
-
Models FDC406HES3, 506HES3
Unit: mm 380 580 Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type L1 Open Open 500 L2 300 0 Open L3 Mark Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit must…
-
Exterior appearance (1) Indoor unit Models All models Item Type Panel model FDTN208H FDTNP208H TN-PSC-22W-E remote controller FDTN258H~508H FDTNP258H~508H TN-PSC-32W-E For wired FDT208-A T-PSA-22W-E FDT258~508-A T-PSA-32W-E For wireless remote controller Pearl white Remarks With Auto swing…
-
Piping system Models FDTN208HEN-S1, 258HEN-S1, FDTNP208HEN-S, 258HEN-S FDT208HEN-SA, 258HEN-SA Cooling cycle Indoor unit Heating cycle Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Strainer Gas line (ø15.88) Service valve (Flare connecting) High…
-
Models FDTNP508HES-S, FDT508HES-SA
High pressure switch (63H2) (For fan motor control) Indoor unit Cooling cycle 4way valve Gas line (ø19.05) Strainer Thermistor (ThO-A) Service valve (Flare connecting) High pressure switch (63H1) (Only case of FDTNP type) Check joint Heat exchanger Capillary tube Thermistor (ThI-A) Check joint Heat…
-
Models FDT408HES-A, 508HES-A
Indoor unit Service valve (Flare connecting) Check joint Strainer Gas line (ø19.05) Cooling cycle Heating cycle Outdoor unit High pressure switch (For fan motor control) Strainer 4way valve Check joint Thermistor (ThI-A) Heat exchanger Accumlator Heat exchanger Check joint Thermistor (ThI-R) Defrost…
-
Selection chart Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and heating…
-
Cooling operation
Heating operation Indoor air D.B. temperature (˚CD.B.) Outdoor air D.B. temperature (˚CD.B.) Coefficient of cooling and heating capacity in relation to temperatures (C) Only case of ISO-T3 and SASO models Indoor air W.B. temperature (˚CW.B.) ISO-T1 Standard condition ISO-T1 Standard condition…
-
(3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor and outdoor units. 50/60Hz (1) 1.0 1.0 1.0 1.0 1.0 0.995 0.995 0.99 0.99 0.985 0.985 FDTN (P), FDT208 type 1.0 0.995 0.995 0.99 0.985 0.985 0.98 FDTN (P), FDT258…
-
Model FDC306HEN3
Model FDC306HES3 Noise level 56 dB (A) Models FDC408HES3 FDCP408HES3 Noise level 56 dB (A) N60 50 50 N50 40 40 N N50 40 40 N N30 0 1000 2000 4000 N2 63 125 Mid octave band frequency (Hz) 250 500 Noise level 57 dB (A) 1000 2000 4000 N50 40 40 N40 30 30 4000 Mid octave band frequency (Hz) 1000 2000…
-
S
-
таблицы и схемы — в просмотре
-
S
-
V
-
таблицы и схемы — в просмотре
-
N
-
L2
-
таблицы и схемы — в просмотре
-
X05
-
S
-
X05
-
V
-
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Wireless remote controller Models FDTN (P), FDEN (P), FDKN (P) series (a) Remote controller Signal sender OPERATION MODE indicator Signals are sent to the air conditioner from here. Indicates selected operation mode CAUTION Cooling only…
-
Model FDEN (P) series
Heavy Duty RUN CHECK ON/OFF Remote controller signal receiver RUN LAMP (GREEN) BACK UP SWITCH When the remote controller is missing or defective, this switch can start and stop the air conditioner. Use the back up switch when the battery is exhausted, or when the remote controller is missing or…
-
(3) Outline of microcomputer control function
(a) Operation control function by the indoor controller 1) Automatic operation (Only heat pump type) If the Auto mode is selected on the remote control device, the selection of cooling or heating can be made automatically depending on the room temperature (and the temperature of indoor heat…
-
Dehumidifying operation (“THERMAL DRY”)
The compressor, the indoor fan motor and the outdoor fan motor Operation block are operated intermittently under thermistor (ThI-A) control according to the appropriate operation block, to provide cooling operation for the dehumidifying. D C B -2 Low A +3 High Pattern of operation Set temp. by…
-
FM control with the heating thermostat turned off (For cold draft prevention) (Only heat pump type) In order to prevent a cold draft while the heating thermostat is turned off, the indoor blower is controlled in response to the temperature of the indoor heat exchanger as illustrated below. It should…
-
Condensate pump motor (DM) control (Only FDTN (P), FDT, FDR models) During the cooling or Dehumidifying operation, the condensate pump motor (DM) is synchronized with the start of compressor operation. If the operation is switched from the operation stop, error stop, thermostat stop and the cooling…
-
13) Compressor inching prevention control
a) Compressor 3 minutes delay control The compressor will remain in stop state for three minutes. When the compressor is stopped by thermostat, ON/OFF switch, and/or by occurrence of trouble. When the power source is turned ON, the three-minute delay timer is cancelled. b) Compressor 3 minutes…
-
17) Drain detection
a) (Only FDTN(P), FDT, FDR models) If there is detection of a drain abnormality during cooling operation, the drain pump goes ON for 5 minutes and the compressor which had been running comes to a stop. Overflow detection is carried out at all times with the float switch regardless of operational…
-
¡ At shipping from factory [FDTN (P), FDEN (P), FDKN (P) models : J3 (SW5-3), FDT, FDR, FDU, FDFL models : J5 (SW5-2) ] on PCB OFF] ¡ Input signal to CnT OFF → ON [Edge input] Air conditioner ON ¡ Input signal to CnT ON → OFF [Edge input] Air conditioner OFF ON CnT input ON OFF ON OFF OFF ON ON OFF…
-
¡ Keeping the louvers horizontal during heating (Only heat pump type)
While HOT KEEP is displayed (during hot start operation or when the thermostat has turned off during heating operation), the louvers stay in the horizontal position to prevent cold drafts, independent of the setting of the AUTO SWING key (auto swing or stop). The louver position display of LCD…
-
(b) Operation control function by the wired remote controller
(i) The following is the sequence of operation for the remote controller operation mode switch. DRY (ii) COOL FAN HEAT AUTO CPU reset This functions when the " inspection " and " filter reset switch " on the remote controller are pushed simultaneously. It operates in the same manner as the power…
-
(c) Operation control function by the outdoor controller (Only FDC(P)208~508 type, FDC808, 1008 type) 1) Control for outdoor unit fan a) Cooling Operation The speed of the fan for the outdoor unit is controlled by the temperature of the heat exchanger (Tho-R detection) and the outdoor air…
-
Control of fan for outdoor unit for de-icing If DIP switch SW5-2 on the printed circuit board for the outdoor unit is set to on, the Outdoor fan operates at Hi speed fan on the outdoor unit which has been stopped will operate for 10 seconds at Hi speed Outdoor fan stopped every 10 minutes when the…
-
Compressor protecting function (Microcomputer and phase protection relay) a) Overcurrent control (i) When a 52C secondary L1-phase continues for 0.5 seconds and when it is more than the set value (detection at current sensor CT), the compressor is stopped. The compressor is restarted after a…
-
High-pressure protection by high-pressure make-or-break device (63H1) (Only case of FDCP208~508 and FDC808, 1008 type) a) If the pressure rises and 63H1 is operated (opened), the compressor is stopped. After a 3-minute delay, the compressor is restarted. An abnormal stop is performed when 63H1 is…
-
APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings. WARNING and CAUTION , those points which are related to the strong possibility of an…
-
Installation of indoor unit NOTICE All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter…
-
(3) Hanging
¡ Arrange four sets of a hang bolt (M10 or M8) , a nut for it, a plain washer and a spring washer on site. When there is the ceiling 1. Make an 860 to 890 mm-square cutout on the ceiling. Refer to the outside dimensions of packing cardboard container. s Align the center of ceiling cutout and the…
-
Drainage Test
1 Conduct a drainage test after completion of the electrical work. 2 During the trial, make sure that drain flows properly through the piping and that no water leaks from connections. 3 In case of a new building, conduct the test before it is furnished with the ceiling. 4 Be sure to conduct this…
-
(6) Cautions for wireless remote conntroller operation
As wireless remote controller is operated by infrared rays as a signal, make sure to explain to customers the following matters regarding the operating distance and protection from jamming. ¡ Operate it by directing the remote controller switch correctly to the receiver amp section. ¡ Operating…
-
1) Set necessary functions in accordance with the model of indoor
unit. 5) Couple the upper case with the lower case as it was to finish up the installation. Refer to (c) for the setting of functions. 2) Couple the upper case with the lower case as they were. 3) Secure the remote controller cords on the wall or other using cord clamps. Embedded installation 1)…
-
Installation of outdoor unit OWARNING BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/ OR PROPERTY DAMAGE. Models : FDC(P)208~508 type, FDC808, 1008 type (1) Installation…
-
(d) Location where strong wind blows against the unit
1) Install the unit directing the 2) discharge air port to the wall. (Only case of FDC(P)208~508 type) Install the unit directing the 3) Where the foundation is not stable, secure the discharge air port at a right unit with wire, etc. angle to the wind direction. Models FDC(P)208~508 type Models…
-
(3) Refrigerant piping work
Select the piping specification to fit the specification of Indoor unit and installation location. (a) Decision of piping specification Piping specification Indoor unit Outdoor unit model FDC(P)208 FDC(P)258, 308 FDC408, 508 FDCP408,508 FDC808 FDC1008 Outdoor unit Unit : mm Gas pipe ø 15.88 × t1.0 ø…
-
IMPORTANT
¡ Take care so that the piping to be worked does not contact the parts contained in the unit. If it contacts the inner parts, abnormal sound or vibration may occur. (c) Leak test and air purge Perform the procedure according to the following instructions. Request ¡ Perform the air purge of Indoor…
-
(e) Refrigerant charge
1) Outdoor unit is pre-charged R-22 and R407C refrigerant at a factory as shown in Table 1. 2) Indoor unit is pre-charged only a small amount of nitrogen gas for prevention of the air entry. 3) Additional charge on site is required when the pipe length is longer than that of restricted value (Which…
-
Following precautions must be observed when the model is adapted to R407C
(1) Tools and related components should be changed when handling a different kind of refrigerant in order to prevent mixing of different oils. Gauge manifold and charge hose, particularly, should never be used after using them for R22. (2) Charge cylinder should not be used. Otherwise, the…
-
Power source and ground terminal block
Wiring clamp ™ Secure the wiring so that no external force is applied to the connecting portion of terminal. Take out direction of wiring ™ Same as the refrigerant piping, 4 directions are allowed, which are right, front, rear and down. Wiring diagram ™ Wiring diagram is fixed at the backside of…
-
b)
Installation where the area with strong winds. Install the unit so that the air outlet section of the unit must not be faced toward wind direction. (c) Installation of outdoor unit 1) Installation Fix the unit in a proper way according to the condition of a place where it is installed by referring…
-
(e)
Air purge Carry out the air purge of the indoor unit and refrigerant piping by vacuuming. Procedures. 1) Tighten all the flare nuts of the piping on the side of indoor and outdoor units so that there is no leakage. 2) Carry out vacuuming from the service valve charge port with the service valves…
-
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.) Item Circuit breaker Switch breaker (A) Phase Model FDC306EN type Overcurrent Protector rated capacity (A) 1 FDC306ES type FDC406 type 30 3 FDC506 type (b) 30 8 mm2 15 φ1.6…
-
MAINTENANCE DATA 8.6.1 Servicing (1) Evacuation The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigerant equipment by using a vacuum pump. Since the refrigerant R22 and R407C is very insoluble in water, even a small amount of moisture left in…
-
(2) Refrigerant charging
(a) After the evacuation shown in the above, change the connection of the charge hose A to the refrigerant cylinder. (b) Purge air from the charge hose A . First loosen the connecting portion of the charge hose at the gauge manifold side and open valve 3 for a few seconds, and then immediately…
-
Diagnosing of microcomputer circuit (1) Selfdiagnosis function (a) Indoor unit side (i) Only case of wireless remote control model. Check indicator table Failure mode on the indoor unit indicated by flashing Yellow LED and Green LED. Indoor unit LED Yellow Green 1 time flash – 2 time flashes – 4…
-
(3) Error diagnosis procedures at the indoor unit side
To diagnose the error, measure the voltage (AC, DC), resistance, etc. at each connector around the circuit board of indoor unit based on the inspection display or the operation state of unit (no operation of compressor or blower, no switching of 4-way valve, etc.). If any defective parts are…
-
• Function of jumper wires
Name J1(SW5-1) J2(SW5-2) J3(SW5-3) J4(SW4-1) J5(SW4-2) J6(SW4-3) J7(SW4-4) *1 J7(SW4-4) • Function of DIP switched (SW3) Function 1 Phase model 3 Phase model Cooling only type Heat pump type Pulse input Step input With None With None With None With None With None With None With None With None Switch…
-
(c) Inspection method when there are fault lamps (display lamps on indoor unit)
(i) Return air thermistor (ThI-A) Indoor unit heat exchanger thermistor (ThI-R) Resistance temperature characteristics Defective indoor unit heat exchanger thermistor Indoor unit Check Lamp (yellow) Defective indoor unit PCB Replacement (Defective indoor unit heat exchanger thermistor input circuit)…
-
Abnormality casued by insufficient refrigerant
Are the characteristic values for the heat exchanger thermistor OK? Indoor unit Check Lamp (yellow) 5 time flashes NO Replace heat exchanger thermistor. YES Is the amount of refrigerant circulation good? (If refrigerant is insufficient, the capillary tubes may be plugged.) NO Charge with…
-
Error display : e6 [Defective indoor unit heat exchanger thermistor] Return air thermistor (ThI-A) Indoor unit heat exchanger thermistor (ThI-R) Resistance temperature characteristics Defective indoor unit PCB Replacement (Defective indoor unit heat exchanger thermistor input circuit) Resistance…
-
Error display : e 9 [Failure in drainage] Defective indoor unit PCB Replacement (Defective condensate motor output circuit) NO (1) YES Is there any overflow? Is the angle of drain piping good. Is there any problem? NO YES Is there output for condensate motor (DM)? Repair YES Is the float switch…
-
(4) Outdoor unit side (FDC(P)208~508 type, FDC808, 1008 type)
Check Indicator Table Failure mode on the outdoor unit is indicated by flashing both Green LED (LED-G) and Red LED (LED-R) on the printed circuit board. Outdoor unit LED Failure at: Contents of the failure Green Red Keeps flashing Stays OFF Stays OFF 1 time flash Power wiring • The outdoor power…
-
PCB power supply connector
-
(b) Inspection method when there are fault lamps (outdoor unit LED)
1 Open phase at L3 phase (Primary side) Outdoor unit Red LED 1 time flash Green LED Stays OFF Is L3 phase at primary side at open phase YES Correction NO Defective outdoor unit PCB Replacement 2 Overcurrent of the compressor motor Outdoor unit Red LED 2 time flashes Green LED Stays OFF Power supply…
-
The outdoor heat exchanger temperature is too high (70°C or over)
(1) Are the heat exchanger thermistor Charateristisc Normal? Outdoor unit Red LED 4 time flashes Green LED Stays OFF Check the unit side closely (1) YES Cooling, overload operation? NO Heart exchanger thermistor replacement • Is outdoor fan motor operating? • Is the outdoor unit shortcircuited? • Is…
-
Defective outdoor temperature thermistor Outdoor unit 2 time flashes Green LED 1 time flash Is the outdoor air temperature thermistor connector connection OK? YES Is the outdoor temperature thermistor characteristics OK, is there no broken wire? Defective outdoor unit PCB Replacement (Defective…
-
High pressure error [63H1] (Only case of FDCP208~508 type) Outdoor unit Red LED 4 time flashes Green LED 1 time flash YES Did 63H1 operate? At 63H1 opration • Is the outdoor unit fan motor operating? • Is there no shortcircuit in the outdoor unit? • Is sufficient space reserved for suction or…