Инструкция на Кондиционеры серии FDT(N)-C
Кондиционеры серии FDT(N)-C. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
9. CEILING RECESSED TYPE
PACKAGED AIR-CONDITIONER Split system, Air cooled Cooling only type ( ) Refrigerant R22 use models FDT208CEN-SA 258CEN-SA 308CEN-A 308CES-A 408CES-A 508CES-A Alternative refrigerant R407C use models FDTNP208CEN-S 258CEN-S 308CEN-S 308CES-S 408CES-S 508CES-S 363
-
GENERAL INFORMATION 9.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer…
-
SELECTION DATA 9.2.1 Specifications (1) Refrigerant R22 use models (a) Wired remote controller type Model FDT208CEN-SA FDT208CEN-SA Model Item FDT208-A Nominal cooling capacity(1) FDC208CEN3 5000 W Power source 1 Phase, 220/240V, 50Hz kW 1.78/1.87 Running current (Cooling) A 8.3/8.1 Power factor…
-
Model FDT258CEN-SA
FDT258CEN-SA Model Item FDT258-A Nominal cooling capacity(1) FDC258CEN3 5700 W Power source 1 Phase, 220/240V, 50Hz kW 2.05/2.16 Running current (Cooling) A 9.4/9.4 Power factor (Cooling) % 99/96 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDT308CEN-A
FDT308CEN-A Model Item FDT308-A Nominal cooling capacity(1) ISO-T1 ISO-T3 W ISO-T1 kW A % kW A % A dB(A) ISO-T3 Operation data(3) Power source Cooling input Running current (Cooling) Power factor (Cooling) Cooling input Running current (Cooling) Power factor (Cooling) Inrush current (L.R.A) Noise…
-
Model FDT308CES-A
FDT308CES-A Model Item FDT308-A Nominal cooling capacity(1) ISO-T1 ISO-T3 W ISO-T1 kW A % kW A % A dB(A) ISO-T3 Operation data(3) Power source Cooling input Running current (Cooling) Power factor (Cooling) Cooling input Running current (Cooling) Power factor (Cooling) Inrush current (L.R.A) Noise…
-
Model FDT408CES-A
FDT408CES-A Model Item FDT408-A Nominal cooling capacity(1) ISO-T1 ISO-T3 W ISO-T1 kW A % kW A % A dB(A) ISO-T3 Operation data(3) Power source Cooling input Running current (Cooling) Power factor (Cooling) Cooling input Running current (Cooling) Power factor (Cooling) Inrush current (L.R.A) Noise…
-
Model FDT508CES-A
FDT508CES-A Model Item FDT508-A Nominal cooling capacity(1) ISO-T1 ISO-T3 W kW A % kW A % A dB(A) ISO-T3 ISO-T1 Operation data(3) Power source Cooling input Running current (Cooling) Power factor (Cooling) Cooling input Running current (Cooling) Power factor (Cooling) Inrush current (L.R.A) Noise…
-
(2) Alternative refrigerant R407C use models
(a) Wireless remote controller type Model FDTNP208CEN-S FDTNP208CEN-S Model Item FDTN208C Nominal cooling capacity(1) FDCP208CEN3 5000 W Power source 1 Phase, 220/240V, 50Hz kW 2.05/2.11 Running current (Cooling) A 9.5/9.6 Power factor (Cooling) % 98/92 Inrush current (L.R.A) A Noise level(4)…
-
Model FDTNP258CEN-S
FDTNP258CEN-S Model Item FDTN258C Nominal cooling capacity(1) FDCP258CEN3 5700 W Power source 1 Phase, 220/240V, 50Hz kW 2.36/2.55 Running current (Cooling) A 11.3/12.4 Power factor (Cooling) % 95/86 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDTNP308CEN-S
FDTNP308CEN-S Model Item FDTN308C Nominal cooling capacity(1) FDCP308CEN3 7100 W Power source 1 Phase, 220/240V, 50Hz kW 3.21/3.36 Running current (Cooling) A 14.9/15.3 Power factor (Cooling) % 98/92 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDTNP308CES-S
FDTNP308CES-S Model Item FDTN308C Nominal cooling capacity(1) FDCP308CES3 7100 W Power source 3 Phase, 380/415V, 50Hz kW 3.13/3.28 Running current (Cooling) A 5.5/5.8 Power factor (Cooling) % 86/79 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDTNP408CES-S
FDTNP408CES-S Model Item FDTN408C Nominal cooling capacity(1) FDCP408CES3 10000 W Power source 3 Phase, 380/415V, 50Hz kW 4.55/4.67 Running current (Cooling) A 8.0/8.4 Power factor (Cooling) % 86/77 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDTNP508CES-S
FDTNP508CES-S Model Item FDTN508C Nominal cooling capacity(1) FDCP508CES3 12500 W Power source 3 Phase, 380/415V, 50Hz kW 5.41/5.48 Running current (Cooling) A 9.7/10.0 Power factor (Cooling) % 85/76 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Range of usage & limitations Models FDT208, 258 (FDC208, 258 type), FDTNP208~508 (FDCP208~508 type) Models Item FDT208, 258 (FDC208, 258 type) FDTNP208, 258 (FDC208, 258 type) FDTNP308~508 (FDC308~508 type) Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air…
-
Exterior dimensions (1) Indoor unit Models FDTN208C FDT208-A Unit : mm 740 (Ceiling hole size) Fresh air opening for ducting Decorative Panel 430 800 (Suspension bolts pitch) C 515 → 680 (Suspension bolts pitch) Exhaust air opening for ducting → D 570 B→ Indication board (Only case of FDTN type) Air…
-
FDT258-A, 308-A Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 Indication boad…
-
FDT408-A, 508-A Unit : mm Decorative Panel ↑ Fresh air opening for ducting C 860~890 (Ceiling hole size) 950 780 (Suspension bolts pitch ) D→ 422 675 (Suspension bolts pitch) Exhaust air opening for ducting B→ Air inlet grille 267 Drain hose (Accessories) (Connectable with VP25) 332 Indication boad…
-
(2) Remote controller
(a) Wireless remote controller AUTO COOL DRY FAN HEAT FAN HI LO Unit: mm FILTER °C ON AM PM TEMP Indication board of indoor unit ON/OFF 161.5 MODE OFF AM PM RUN 20.5 60 Unit: mm (b) Wired remote controller(Optional parts) Wall 0.3mm2, 3cores (O.D.φ5.6) Remote controller mounting dimensions Wire…
-
(3) Outdoor unit
Models FDC208CEN3, FDCP208CEN3 Unit: mm Liquid piping: φ6.35 (1/4˝) (Flare connecting) Gas piping: φ15.88 (3/8˝) (Flare connecting) 95 Liquid piping: φ6.35 (1/4˝) (Flare connecting) Terminal block Gas piping: φ15.88 (3/8˝) (Flare connecting) Opening for electric wiring Opening for piping and…
-
Models FDC258CEN3, FDCP258CEN3, 308CEN3, 308CES3
Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for electric wiring Opening for piping and…
-
Models FDCP408CES3, 508CES3
Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 [1050] Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and electric wiring Opening…
-
Models FDC306CEN3, 306CES3
580 380 Unit: mm Required space for maintenance and air flow Unit:mm Air inlet L3 L2 Air inlet 500 mm Obstacles Air Maintenance outlet space L1 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit must be larger than 1 m. (4)…
-
Models FDC406CES3, 506CES3
Unit: mm 380 580 1250 950 Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm L2 L3 Installation type L1 Open Open 500 L2 300 0 Open L3 Mark L1 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space…
-
Exterior appearance (1) Indoor unit Models All models Item Type Panel model For wireless remote controller FDTN208C TN-PSC-22W-E FDTN258C~508C TN-PSC-32W-E For wired remote controller FDT208-A T-PSA-22W-E FDT258-A~508-A T-PSA-32W-E Remarks Without swing Pearl white (Decorative panel) (2) Outdoor…
-
Piping system Models FDT208CEN-SA, 258CEN-SA FDTNP208CEN-S, 258CEN-S Check joint Service valve Indoor unit Outdoor unit (Flare connecting) Thermistat (Tho-A) High pressure switch (63H1) Gas line (φ15.88) Only case of Thermistor FDTNP type (ThI–A) Thermistat (Tho-D) Heat exchanger ( Thermistor…
-
Models FDT308CEN-A, 308CES-A, 408CES-A, 508CES-A
Indoor unit Outdoor unit ø15.88 (308: 408, 508: ø19.05) (ø9.52) Model FDTNP508CES-S Indoor unit Outdoor unit High pressure switch (63H1) Check joint Gas line ( ø19.05) Thermistor (ThI-A) Heat exchanger Thermistor (ThI-R) Oil separator Service valve (Flare connecing) Caillary tube Heat exchanger…
-
Selection chart Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling capacity in relation to temperatures…
-
(b) Only case of ISO-T3 and SASO models
ISO-T1 Standard condition Indoor air W.B. temperature (˚CW.B.) Table of bypass factor Item Air flow Model 208 type 258 type 308 type 508 type Hi 0.112 0.050 0.065 0.076 0.025 Lo 0.073 0.030 0.030 0.050 0.013 (2) Correction of cooling capacity in relation to air flow rate control (fan speed)…
-
(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor and outdoor units. 50/60Hz (1) m FDTNP, FDT208 type 1.0 0.995 0.995 0.99 0.985 0.985 0.98 FDTNP, FDT258 type 1.0 0.995 0.99 0.985 0.98 0.975 0.97 FDTNP308 type 1.0…
-
FDC306CES3
-
WH
-
таблицы и схемы — в просмотре
-
BL
-
Y/GN
-
таблицы и схемы — в просмотре
-
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER Except for function relating to heating, same at the unit for FDT(N) heat pump type. See page 317. 9.5 APPLICATION DATA The application data for the cooling only models are similar to those for the heat pump models. (See page 332.) 9.6 MAINTENANCE DATA…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.