14. CEILING RECESSED TYPE
CASSETTERIA MODELS Split system, Air to air heat pump type ( FDR208HEN-SA 258HEN-SA 308HEN-SA 308HES-SA 408HES-SA 508HES-SA ) FDR308HEN-A 308HES-A 408HES-A 508HES-A 527
-
14.1 GENERAL INFORMATION
14.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
14.2 SELECTION DATA
14.2.1 Specifications Model FDR208HEN-SA FDR208HEN-SA Model Item FDR208-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-26W-E (1) W Nominal heating capacity (1) W Nominal cooling capacity _ R-PNLC-26W-E 5000 5400 Power source Operation data(3) FDC208HEN3A _ 1 Phase…
-
Model FDR258HEN-SA
FDR258HEN-SA Model Item FDR258-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-36W-E 5700 6100 Power source Operation data(3) FDC258HEN3A _ 1 Phase, 220/240V, 50Hz Cooling input kW 2.06/2.17 Running…
-
Model FDR308HEN-SA
FDR308HEN-SA Model Item FDR308-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-36W-E 7100 8000 Power source Operation data(3) FDC308HEN3 _ 1 Phase, 220/240V, 50Hz Cooling input kW 3.02/3.22 Running…
-
Model FDR308HES-SA
FDR308HES-SA Model Item FDR308-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-36W-E 7100 8000 Power source Operation data(3) FDC308HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 2.94/3.00 Running…
-
Model FDR408HES-SA
FDR408HES-SA Model Item FDR408-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-46W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-46W-E 10000 11200 Power source Operation data(3) FDC408HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 4.48/4.58…
-
Model FDR508HES-SA
FDR508HES-SA Model Item FDR508-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-46W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-46W-E 12500 14000 Power source Operation data(3) FDC508HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 5.27/5.52…
-
Model FDR308HEN-A
FDR308HEN-A Model Item FDR308-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-36W-E 7100 7300 Power source Operation data(3) FDC306HEN3 _ 1 Phase, 220/240V, 50Hz Cooling input kW 3.11/3.15 Running…
-
Model FDR308HES-A
FDR308HES-A Model Item FDR308-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-36W-E 7100 7300 Power source Operation data(3) FDC306HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 2.87/2.88 Running…
-
Model FDR408HES-A
FDR408HES-A Model Item FDR408-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-46W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-46W-E 10200 10500 Power source Operation data(3) FDC406HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 3.76/3.76 Running…
-
Model FDR508HES-A
FDR508HES-A Model Item FDR508-A Silent panel Canvas panel Decorative panel Panel model (Option) R-PNLS-46W-E Nominal cooling capacity (1) W Nominal heating capacity (1) W _ R-PNLC-46W-E 12500 12800 Power source Operation data(3) FDC506HES3 _ 3 Phase, 380/415V, 50Hz Cooling input kW 4.84/4.84 Running…
-
14.2.2 Range of usage & limitations
Models FDR208~508 (FDC208~508 type) Models Item FDR208, 258 (FDC208, 258 type) FDR308~508 (FDC308~508 type) Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Indoor unit atmosphere (behind ceiling) temperature and humidity…
-
14.2.3 Exterior dimentions
(1) Indoor unit Model FDR208-A Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 57 786 (Suspension bolts pitch) 433 Drain hose (Accessories) 137 (Locality) 353 Fresh air opening (Knock out hole) ↑A 405 650 MIN320 0 φ20 Drain (Natural drainage) (VP20) Hole of wiring (I.D. φ35)…
-
Model FDR208-A
Canvas Panel (Model: R-PNLC-26W-E) Drain hose (Accessories) 804 (Ceiling hole size) 9 Unit : mm 786 (Suspension bolts pitch) (Local Locality) 9 45 Panel center 150 193 Drain (Connectable with VP25) Control box 352 525 (Ceiling hole size) 90 Fresh air opening (Knock out hole) 69 Liquid piping φ6.35…
-
Unit : mm Silent Panel (Model: R-PNLS-36W-E) 1180 (Ceiling hole size) 986 (Suspension bolts pitch) Drain hose (Accessories) (Locality) Fresh air opening (Knock out hole) 70 45 Air outlet duct Suspension bolts (M10 × 4pcs.) 295~325 VIEW C 71 (Max. Drain up) 270 Control box Panel center (Suspension…
-
Canvas Panel (Model: R-PNLC-36W-E) Unit : mm Drain hose (Accessories) (Locality) 1004 (Ceiling hole size) 9 Fresh air opening (Knock out hole) 284 45 C↑ Panel center 352 Control box 500 VIEW C 59 Suspension bolts (M10 × 4pcs.) Hole for humidifier piping (I.D.φ14) Drain (Connectable with VP25) 199…
-
Unit : mm Silent Panel (Model: R-PNLS-46W-E) 1600(Ceiling hole size) Drain hose(Accessories) 1406(Suspension bolts pictch) (Locality) 663 Fresh air opening 284 Control box Panel center 70 150 690(Ceiling hole size) 58 545 (Suspension bolts pictch) 275 45 C 270 (Knock out hole) 69 495 Air outlet duct…
-
Unit : mm Canvas Panel (Model: R-PNLC-46W-E) Drain hose(Accessories) 1424(Ceiling hole size) 1406(Suspension bolts pictch) 9 Fresh air opening (Locality) 9 (Knock out hole) 150 45 C 193 69 Panel center 352 Control box 495 VIEW C 59 71 Suspension bolts 80 1370 (M10 × 4 pcs.) B→ 635 405 (I.D.ø14) 200…
-
(2) Remote controller (Optional parts)
Unit : mm Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 83.5 For the passage after wiring ♦ Usable JIS box, JIS C 8336 ⋅ Switch box for 1 piece (without cover) (use of the mark hole as illustrated on the left)…
-
(3) Outdoor unit
Model FDC208HEN3A Liquid piping: φ 6.35 (1/4") Unit: mm (Flare connecting) Gas piping: φ 15.88 (5/8") (Flare connecting) 95 Liquid piping: φ 6.35 (1/4") (Flare connecting) Terminal block Gas piping: φ 15.88 (5/8") (Flare connecting) 110 Opening for electric wiring Opening for piping and electric…
-
Models FDC258HEN3A, 308HEN3, 308HES3
Liquid piping: ø9.52 (3/8") (Flare connecting) Unit: mm 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for electric wiring Opening for piping and…
-
Models FDC408HES3, 508HES3
Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 (1050) Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and electric wiring Opening…
-
Models FDC306HEN3, 306HES3
580 380 Unit: mm Anchor bolts (M10 × 4 pcs) Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type 1 2 L1 Open Open 500 L2 300 0 Open L3 Mark 3 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet.…
-
Models FDC406HES3, 506HES3
Unit: mm 380 580 Required space for maintenance and air flow Minimum allowable space to the obstacles Unit:mm Installation type L1 Open Open 500 L2 300 0 Open L3 Mark 552 Notes (1) Fix the unit with anchor bolts. (2) Strong wind must not be directed to the air outlet. (3) Free space over the unit…
-
14.2.4 Exterior appearance
(1) Indoor unit (Operation panel): All Models Silent panel type Canvas-duct panel type Ceramic White Ceramic White (2) Outdoor unit Model FDC208HEN3A Models FDC258HEN3A, 308HEN3, 308HES3 Polar white Polar white Models FDC408HEN3, 508HES3 Models FDC306HEN3, 306HES3 Models FDC406HES3, 506HES3 Polar…
-
14.2.5 Piping system
Models FDR208HEN-SA, 258HEN-SA Cooling cycle Indoor unit Outdoor unit Heating cycle High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Gas line (ø15.88) Strainer Service valve (Flare connecting) Heat exchanger Check joint Check joint Thermistor (ThI-A) Muffler Heat…
-
Model
FDR508HES-SA High pressure switch (63H2) (For fan motor control) Indoor unit Cooling cycle 4way valve Gas line (ø19.05) Strainer Outdoor unit Heating cycle Thermistor (ThO-A) Service valve (Flare connecting) Check joint Check joint Thermistor (ThI-A) Oil separator Thermistor (ThO-D) Heat exchanger…
-
Models FDR408HES-A, 508HES-A
Service valve (Flare connecting) Indoor unit Check joint Strainer Gas line (ø19.05) Cooling cycle Heating cycle Outdoor unit High pressure switch (For fan motor control) Strainer 4way valve Check joint Thermistor (ThI-A) Heat exchanger Accumlator Heat exchanger Check joint Thermistor (ThI-R)…
-
14.2.6 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and heating capacity in…
-
Table of bypass factor
Model FDR 208 type FDR 258 type FDR 308 type FDR 408 type FDR 508 type Hi 0.035 0.032 0.039 0.085 0.035 Lo 0.021 0.020 0.023 0.060 0.023 Item Air flow (2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction…
-
14.2.7 Characteristics of fan
(1) Cassetteria type (FDR) How to interpret the blower characteristics table • External static pressure table Unit: Pa (mmAq) Duct specs. 1 spot closing(1) Square duct(3) Example : Case of FDR308-A 30(3) 65(6.5) 45(4.5) 80(8) 50(5) 85(8.5) FDR308-A 20 25(2.5) 60(6) 45(4.5) 80(8) 50(5) 85(8.5)…
-
Model FDR308-A
-
14.2.8 Noise level
-
Model FDR408-A
-
Y/GN
-
BL
-
X08
-
X05
-
C
-
BL
-
WH
-
14.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 317. 14.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two…
-
NOTICE
All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to Mitsubishi Heavy…
-
(4) Preparation for suspending the unit
(a) Selection of hanging pattern When the unit is hanged from ceiling, select one of following patterns depending on the dimensions of the ceiling. < Combination with silent panel > Unit: mm A Dimentions A 56 ~ 70 Models FDR208,258,308 365 or over FDR408,508 416 or over < Combination with canvas…
-
Hanging bolt
(5) Installation of indoor unit M10 nut M10 washer ¡ Fix the indoor unit to the hanger bolts. If required, it is possible to suspend the unit to the beam, etc. M10 spring washer Main unit Directly by use of the bolts without using the hanger bolts. Note When the dimensions of main unit and ceiling…
-
(d) When constructing drain piping for several units, posi-
Secure the elevation as high as possible (approx. 100 mm) tion the common pipe about 100mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4˝) or thicker pipe for this purpose. A downhill grade of 1/100 or less VP30 (e) Be sure to provide heat insulation to hard PVC pipes of…
-
(7) Installation work for air outlet ducts
Air conditioner main unit. Canvas duct (Option) Heat insulation Suction hole (Silent panel) Ceiling surface B Special blowout (Option) A Blowout duct Suction hole (Canvas panel) (Optional or marketed item) Calculate the draft and external static pressure and select the length, shape and blowout. A…
-
(9) Installation of ornament panel
<Case of silent panel> Name Q'ty Round head set screw (M5 × 35) i) Accessory Position 4 pcs. Securing the panel ii) Installation procedures (a) Remove the inner frame of panel ¡ How to remove the panel inner frame 1 Detach from pins (A) in the order of arrow 1→2. 2 Open slightly as the arrow 3 and…
-
Attachment of ceiling material
Ceiling material can be attached to the panel inner frame. (Plate thickness max. 15mm) Ceiling material Ornament panel Panel inner frame Stopper Attachment procedures 1 Remove the stopper. 2 Remove the ornament plate and attach the ceiling material. 3 Hold down the ceiling material and return the…