12. WALL MOUNTED TYPE
PACKAGED AIR-CONDITIONER Split system, Air to air heat pump type ( ) Refrigerant R22 use models FDKN208HEN-S1 258HEN-S1 Alternative refrigerant R407C use models FDKNP208HEN-S 258HEN-S 308HEN-S 308HES-S 469
-
12.1 GENERAL INFORMATION
12.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
12.2 SELECTION DATA
12.2.1 Specifications (1) Refrigent R22 use models Model FDKN208HEN-S1 FDKN208HEN-S1 Model Item FDKN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC208HEN3A 4850 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 1.76/1.85 Running current (Cooling) A…
-
Model FDKN258HEN-S1
FDKN258HEN-S1 Model Item FDKN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.03/2.14 Running current (Cooling) A 9.3/9.3 Power factor (Cooling) % 99/96 Heating input kW 1.93/2.08 Running…
-
(2) Alternative refrigerant R407C use models
Model FDKNP208HEN-S FDKNP208HEN-S Model Item FDKN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP208HEN3A 4850 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.07/2.14 Running current (Cooling) A 9.5/9.6 Power factor (Cooling) % 99/93 Heating input…
-
Model FDKNP258HEN-S
FDKNP258HEN-S Model Item FDKN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.34/2.54 Running current (Cooling) A 11.3/12.5 Power factor (Cooling) % 94/85 Heating input kW 2.08/2.33…
-
Model FDKNP308HEN-S
FDKNP308HEN-S Model Item FDKN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.18/3.33 Running current (Cooling) A 14.8/15.2 Power factor (Cooling) % 98/91 Heating input kW 2.93/3.07…
-
Model FDKNP308HES-S
FDKNP308HES-S Model Item FDKN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HES3 7100 8000 Operation data(3) Power source 3 Phase, 380/415V, 50Hz Cooling input kW 3.10/3.25 Running current (Cooling) A 5.4/5.7 Power factor (Cooling) % 87/79 Heating input kW 2.95/3.09 Running…
-
12.2.2 Renge of usage & limitations
Models Item FDKN (P) 208, 258 type FDKNP308 type Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Refrigerant line (one way) length Max. 30 m Max. 50 m Vertical height difference between outdoor unit and indoor unit Max.…
-
12.2.3 Exterior dimensions
(1) Indoor unit Model FDKN208H Unit : mm Mounting plate Indoor unit 49 Outlet for piping (On both side) Mounting plate Remote controller signal receives Lower piping outlet (Refer to the top view.) A Outer for electric wiring 170 4.5 36 187.5 261.5 Gas piping φ15.88(5/8˝) 390 67 Hole on wall for…
-
Model FDKN258H
Unit: mm Mounting plate Remote controller signal receives Lower piping outlet (Refer to the top view.) A 51 Outlet for piping (On both side) Indoor unit Mounting plate Hole on wall for rear connecting (φ65) Drain hose (VP16) 65 463 Liquid piping φ9.52(3/8˝) 518 600 Gas piping φ15.88(5/8˝) VIEW A…
-
Model FDKN308H
Unit : mm 1145 1155 Mounting plate 54 Remote controller signal receives 1047 282.5 45 Drain hose (VP16) Liquid piping ø9.52 (3/8'') Gas piping ø15.88 (5/8'') 600 Hole on wall for rear connecting (ø65) VIEW A (Rear side) Space for installation and service 90 or more Hole on wall for rear connecting…
-
(2) Wireless remote controller
-
(4) Outdoor unit
Models FDC208HEN3A FDCP208HEN3A Unit : mm Liquid piping φ6.35 (1/4˝) (Flare connecting) 40 53 Gas piping: φ15.88 (5/8˝) (Flare connecting) 40 95 Liquid piping: φ6.35 (1/4˝) (Flare connecting) Terminal block Gas piping: φ15.88 (5/8˝) (Flare connecting) Opening for electric wiring 195 351 Opening for…
-
Models FDC258HEN3A
FDCP258HEN3A, 308HEN3, 308HES3 Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Opening for piping and electric wiring Gas piping: ø15.88 (5/8") (Flare connecting) Opening…
-
12.2.4 Exterior appearance
(1) Indoor unit Models All models Ivory white (Front panel) Ivory white (Air inlet grill) Ivory white (Base) Ivory white (Louver) (2) Outdoor unit Models FDC208HEN3A FDCP208HEN3A Models FDC258HEN3A FDCP258HEN3A, 308HEN3, 308HES3 Polar white Polar white 485
-
12.2.5 Piping system
Models FDKN208HEN-S1, 258HEN-S1, FDKNP208HEN-S, 258HEN-S Cooling cycle Heating cycle Indoor unit Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Gas line (ø15.88) Strainer Service valve (Flare connecting) Thermistor (ThI-A) ( Check joint High pressure…
-
Preset point of the protective devices
Parts name Thermistor (for protection over loading in heating) Mark ThI-R Equipped unit FDKN208, 258 type FDKNP208~308 type OFF ON 68 °C 61 °C OFF ON 2.5 °C 10 °C Indoor unit Thermistor (for frost prevention) Thermistor (for detecting discharge pipe temp.) ThO-D Outdoor unit OFF ON 135 °C 90 °C…
-
12.2.6 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. Cooling operation Heating operation Indoor air W.B.…
-
Table of bypass factor
Model Item Air flow FDKN (P) 208 type FDKN (P) 258 type FDKNP308 type 0.03 0.03 0.04 Hi (2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction of cooling and heating capacity in relation to one way length…
-
12.2.7 Noise level
-
X04
-
Y/GN
-
BL
-
X04
-
BL
-
X08
-
12.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Same as the cooling/heating equipment for FDT (N) heat pump type. Refer to page 317. 12.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two…
-
12.5.1 Installation of indoor unit
NOTICE All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to…
-
(3) Carry-in and installation of unit
(a) Carry-in 1) When carrying in the unit, carry it in as packed to the installation site as near as possible. 2) If you are compelled to carry in the unit unpacked, cover it with a nylon sling so that it is not damaged. Note) Do not carry the unit by holding it at the supply air louver. 3) When…
-
(e)
Installation work procedure Claw (2 places) (FDKN308: 3 places) Indoor unit Installation of unit Mounting plate (1) Hang the upper portion of indoor unit on the mounting plate. Lid (right hand) • To remove the unit from the mounting plate, remove the right and left lids then remove the claw at the…
-
(d)
Removal order of the panel 1) Open the return air grill. (Pull both lower ends of the return air grill, raise the grill until the reaction is felt after disengaging the latch. The return air grill will stop at approx. 60° open position.) 2) Remove the air filter. 3) Remove 2 fixing screws for model…