Инструкция на Кондиционеры серии FDKN-C
Кондиционеры серии FDKN-C. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
13. WALL MOUNTED TYPE
PACKAGED AIR-CONDITIONER Split system, Air cooled cooling only type ( ) Alternative refrigerant R407C use models FDKNP208CEN-S 258CEN-S 308CEN-S 308CES-S 503
-
13.1 GENERAL INFORMATION
13.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
13.2 SELECTION DATA
13.2.1 Specifications Model FDKNP208CEN-S FDKNP208CEN-S Model Item FDKN208C Nominal cooling capacity(1) FDCP208CEN3 4850 W Power source 1 Phase, 220/240V, 50Hz kW 2.03/2.09 Running current (Cooling) A 9.4/9.5 Power factor (Cooling) % 98/92 Inrush current (L.R.A) A Noise level(4) Exterior dimensions…
-
Model FDKNP258CEN-S
FDKNP258CEN-S Model Item FDKN258C Nominal cooling capacity(1) FDCP258CEN3 5700 W Power source 1 Phase, 220/240V, 50Hz kW 2.34/2.53 Running current (Cooling) A 11.2/12.3 Power factor (Cooling) % 95/86 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Hi:45 Lo:38…
-
Model FDKNP308CEN-S
FDKNP308CEN-S Model Item FDKN308C Nominal cooling capacity(1) FDCP308CEN3 7100 W Power source 1 Phase, 220/240V, 50Hz kW 3.18/3.33 Running current (Cooling) A 14.8/15.2 Power factor (Cooling) % 98/91 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Hi:46 Lo:40…
-
Model FDKNP308CES-S
FDKNP308CES-S Model Item FDKN308C Nominal cooling capacity(1) FDCP308CES3 7100 W Power source 3 Phase, 380/415V, 50Hz kW 3.10/3.25 Running current (Cooling) A 5.4/5.7 Power factor (Cooling) % 87/79 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Hi:46 Lo:40…
-
13.2.2 Range of usage & limitations
Models Item FDKNP208, 258 type FDKNP308 type Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Refrigerant line (one way) length Max. 30m Max. 50m Vertical height difference between outdoor unit and indoor unit Max. 20m…
-
13.2.3 Exterior dimensions
(1) Indoor unit Model FDKN208C Unit: mm Mounting plate Outer for electric wiring A Remote controller signal receives Lower piping outlet (Refer to the top view.) Indoor unit 15 Outlet for piping (On both side) Mounting plate 4.5 36 187.5 261.5 Gas piping φ15. 88(5/8˝) 67 Hole on wall for rear…
-
Model FDKN258C
Unit: mm Mounting plate 55 298 A 9 Remote controller signal receives Lower piping outlet (Refer to the top view.) Outer for electric wiring 51 Outlet for piping (On both side) Indoor unit Mounting plate Hole on wall for rear connecting (φ65) 72 Drain hose (VP16) Liquid piping φ9.52(3/8˝) 518 600 Gas…
-
Model FDKN308C
Unit : mm 1145 1155 A Outlet for electric wiring Lower piping outlet (Refer to the top view) Mounting plate Remote controller signal receives 51 Outlet for piping (On both side) Indoor unit 54 Mounting plate 1047 Drain hose (VP16) Liquid piping ø9.52 (3/8'') 72 245 282.5 Gas piping ø15.88 (5/8'')…
-
(2) Wireless remote controller
-
(4) Outdoor unit
Model FDCP208CEN3 Unit: mm Liquid piping: φ6.35 (1/4˝) (Flare connecting) 40 53 Gas piping: φ15.88 (5/8˝) (Flare connecting) 40 95 Liquid piping: φ6.35 (1/4˝) (Flare connecting) Terminal block Gas piping: φ15.88 (5/8˝) (Flare connecting) 690 Opening for electric wiring 195 351 Opening for piping and…
-
Models FDCP258CEN3, 308CEN3, 308CES3
Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Opening for piping and electric wiring 110 A Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening…
-
13.2.4 Exterior appearance
(1) Indoor unit Models All models Ivory white (Front panel) Ivory white (Air inlet grill) Ivory white (Base) Ivory white (Louver) (2) Outdoor unit Model FDCP208CEN3 Models FDCP258CEN3, 308CEN3 308CES3 Polar white Polar white 517
-
13.2.5 Piping system
Models FDKNP208CEN-S, 258CEN-S Check joint Service valve Indoor unit Outdoor unit (Flare connecting) Thermistat (Tho-A) High pressure switch (63H1) Gas line (φ15.88) Thermistor (ThI–A) Thermistat (Tho-D) Heat exchanger Heat exchanger Caillary tabe Thermistor (ThI–R) Solenoid valve Compressor SV…
-
Preset point of the protective devices
Parts name Mark Equipped unit All models Thermistor (for frost prevention) ThI-R Indoor unit OFF 2.5˚C ON 10˚C Thermistor (for detecting discharge pipe temp.) Tho-D Outdoor unit OFF 135˚C ON 90˚C Thermistor (for detecting heat exchanger temp.) Tho-R Outdoor unit OFF 70˚C ON 60˚C High pressure switch…
-
13.2.6 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling capacity in relation to temperatures Coefficient of…
-
Table of bypass factor
Model Item Air flow FDKN208C FDKN258C FDKN308C 0.03 0.03 0.04 Hi (2) Correction of cooling capacity in relation to flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction of cooling capacity in relation to one way length of refrigerant piping It is necessary to correct…
-
13.2.7 Noise level
Notes (1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27°C DB, 19°C WB Outdoor unit 35°C DB, 1m Indoor unit Measured based on JIS B 8616 Mike position as below Unit 1m Outdoor unit Measured based on JIS B 8616 Mike position: at highest noise level in position…
-
Y/GN
-
S
-
13.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 317. 13.5 APPLICATION DATA The application data for the cooling only models are similar to those for the heat pump models. (See page 497.) 13.6 MAINTENANCE DATA Same as the cooling/heating equipment for…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.