17. FLOOR STANDING TYPE
(CONSOLE TYPE) PACKAGED AIR-CONDITIONER Split system, Air to air heat pump type ( ) FDFL258HEN-SA 308HEN-SA 308HES-SA 655
-
17.1 GENERAL INFORMATION
17.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
17.2 SELECTION DATA
17.2.1 Specifications Model FDFL258HEN-SA FDFL258HEN-SA Model Item FDFL258-A Nominal cooling capacity (1) W Nominal heating capacity (1) W FDC258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.04/2.15 Running current (Cooling) A 9.4/9.4 Power factor…
-
Model FDFL308HEN-SA
FDFL308HEN-SA Model Item FDFL308-A Nominal cooling capacity (1) W Nominal heating capacity (1) W FDC308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.99/3.19 Running current (Cooling) A 13.9/14.4 Power factor (Cooling) % 98/92 Heating input kW 2.85/3.01…
-
Model FDFL308HES-SA
FDFL308HES-SA Model Item FDFL308-A Nominal cooling capacity (1) W Nominal heating capacity (1) W FDC308HES3 7100 8000 Operation data(3) Power source 3 Phase, 380/415V, 50Hz Cooling input kW 2.91/2.97 Running current (Cooling) A 5.1/5.5 Power factor (Cooling) % 87/75 Heating input kW 2.55/2.61…
-
17.2.2 Range of usage & limitations
Models Item FDFL258 type FDFL308 type Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Refrigerant line (one way) length Max. 30m Max. 50m Vertical height difference between outdoor unit and indoor unit Max. 20m (Outdoor…
-
17.2.3 Exterior dimensions
(1) Indoor unit Models FDFL258-A, 308-A Unit: mm 50 1200 Holes for wall mounting bolt (M10 or M8) 7 1160 (Holes for wall mounting bolt) 150 50 Hole for piping & wiring (rear) 17 70 VIEW A Space for installation and service 1000 or more Hole for piping & wiring (Bottom) 100 or more or more Liquid…
-
(2) Outdoor unit
Models FDC258HEN3A, 308HEN3, 308HES3 Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for…
-
17.2.4 Exterior appearance
(1) Indoor unit Models All models Ceramic white (Air outlet grille) Ceramic white (Front panel) Ceramic white (Front panel) Ceramic white (Holder) Ceramic white (Side panel) Gray (Base) (2) Outdoor unit Models FDC258HEN3A, 308HEN3, 308HES3 Polar white 664 Ceramic white (Air inlet grille)
-
17.2.5 Piping system
Model FDFL258HEN-SA Cooling cycle Heating cycle Indoor unit Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Strainer Gas line (ø15.88) Service valve (Flare connecting) Heat exchanger Check joint Check joint Thermistor (ThI-A) Muffler Heat exchanger…
-
Preset point of the protective devices
Parts name Thermistor (for protection overloading in heating) Mark Equipped unit All models OFF 68˚C ON 61˚C ThI-R Indoor unit OFF 2.5˚C ON 10˚C Thermistor (for frost prevention) Thermistor (for detecting discharge pipe temp.) Tho-D Outdoor unit OFF 135˚C ON 90˚C Thermistor (for detecting heat…
-
17.2.6 Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling and heating capacity in…
-
Table of bypass factor
Model FDFL 258 type FDFL 308 type Hi 0.030 0.036 Lo 0.013 0.018 Item Air flow (2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction of cooling and heating capacity in relation to one way length of…
-
17.2.7 Noise level
Notes (1) The data are based on the following conditions. Ambient air tempetature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit Outdoor unit 35˚C DB Measured on JIS B 8616 Mike position: at highest noise level Indoor unit Measured based on JIS B 8616 Mike position as below Indoor unit in position as…
-
RD
-
таблицы и схемы — в просмотре
-
17.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 317. 17.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two…
-
NOTICE
All Wiring of this installation must comply with NATIONAL,STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to Mitsubishi…
-
Mount the unit on the mounting brackets. 4) Fix the unit on the floor by using the fixing brackets. Fixing bracket Fix the bracket on the Base by use of attached screws. [M8 × 8l] After that fix it on the floor by use of flat washers and double nuts. Mounting brackets Unit fixing bolts 5) Fixing…
-
(4) Installation of remote controller (on the main unit)
Attached remote controller may be installed on the main unit as shown below. The work can be done on the spot when the customer asks so or by other reasons. Refer to the next page when it is installed on the wall. necessary parts (Prepare following parts on the spot.) ¡Tapping screw (M4 × L12) × 2…