Инструкция на Кондиционеры серии FDEN-H
Кондиционеры серии FDEN-H. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
SRK-H
2. CEILING 10. WALL MOUNTED SUSPENSION TYPE TYPE ROOM AIR-CONDITIONER PACKAGED AIR-CONDITIONER Split Split system, system, Air Air to to air air heat heat pump pump type type ( ) SRK328HENF-L2, SRK408HENF-L2 Refrigerant R22 use models SRK501HENF-L, SRK561HENF-L FDEN 208HEN-S1 258HEN-S1 Alternative…
-
10.1 GENERAL INFORMATION
10.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in…
-
10.2 SELECTION DATA
10.2.1 Specifications (1) Refrigerant R22 use models Model FDEN208HEN-S1 FDEN208HEN-S1 Model Item FDEN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC208HEN3A 5000 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 1.77/1.86 Running current (Cooling) A…
-
Model FDEN258HEN-S1
FDEN258HEN-S1 Model Item FDEN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDC258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.04/2.15 Running current (Cooling) A 9.4/9.4 Power factor (Cooling) % 99/95 Heating input kW 1.94/2.09 Running…
-
(2) Alternative refrigerant R407C use models
Model FDENP208HEN-S FDENP208HEN-S Model Item FDEN208H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP208HEN3A 5000 5400 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.08/2.15 Running current (Cooling) A 9.5/9.6 Power factor (Cooling) % 99/93 Heating input…
-
Model FDENP258HEN-S
FDENP258HEN-S Model Item FDEN258H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP258HEN3A 5700 6100 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 2.35/2.55 Running current (Cooling) A 11.4/12.6 Power factor (Cooling) % 94/84 Heating input kW 2.09/2.34…
-
Model FDENP308HEN-S
FDENP308HEN-S Model Item FDEN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HEN3 7100 8000 Operation data(3) Power source 1 Phase, 220/240V, 50Hz Cooling input kW 3.22/3.37 Running current (Cooling) A 14.9/15.3 Power factor (Cooling) % 98/92 Heating input kW 2.97/3.11…
-
Model FDENP308HES-S
FDENP308HES-S Model Item FDEN308H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP308HES3 7100 8000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 3.14/3.29 Running current (Cooling) A 5.5/5.8 Power factor (Cooling) % 87/79 Heating input kW 2.99/3.13 Running…
-
Model FDENP408HES-S
FDENP408HES-S Model Item FDEN408H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP408HES3 10000 11200 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 4.51/4.63 Running current (Cooling) A 7.8/8.2 Power factor (Cooling) % 88/79 Heating input kW 4.35/4.47 Running…
-
Model FDENP508HES-S
FDENP508HES-S Model Item FDEN508H Nominal cooling capacity(1) W Nominal heating capacity(1) W FDCP508HES3 12500 14000 Operation data(3) Power source 3 Phase, 380/415V 50Hz Cooling input kW 5.36/5.43 Running current (Cooling) A 9.5/9.8 Power factor (Cooling) % 86/77 Heating input kW 5.24/5.31 Running…
-
10.2.2 Range of usage & limitations
Models Item FDENP208, 258 type FDENP308~508 type Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Refrigerant line (one way) length Max. 30 m Max. 50 m Vertical height difference between outdoor unit and indoor unit Max.…
-
10.2.3 Exterior dimensions
(1) Indoor unit Models FDEN208H, 258H, 308H 1244 [984] 15 15 (Holes for suspension bolt) ) 50 1160 [900] 50 Side panel 1200 [940] 1260 [1000] ↑ 135 ) ( Unit: mm Holes for suspension bolts (12 × 17 × 4 pcs.) (Holes for suspension bolt) The brackets face interior When the unit is suspended beneath the…
-
Unit: mm
Models FDEN408H, 508H 15 1451 [1244] The brackets face out (Holes for suspension bolt) Holes for suspension bolts ) (Holes for suspension bolt) ) 135 ( 15 The brackets face interior When the unit is suspended beneath the ceiling (12 × 17 × 4pcs.) 50 1370 [1160] 50 20 Side panel 10 10 1410 [1200]…
-
(2) Remote controller
(a) Wireless remote controller Unit: mm AUTO COOL DRY FAN HEAT FAN HI LO FILTER °C ON AM PM TEMP ON/OFF 161.5 MODE OFF AM PM 60 20.5 (b) Indication board of indoor unit Remote controller signal receiver 419
-
(3) Outdoor unit
Models, FDC208HEN3A, FDCP208HEN3A Unit: mm Liquid piping:ø6.35 (1/4") (Flare connecting) Gas piping:ø15.88 (5/8") (Flare connecting) 95 Liquid piping:ø6.35 (1/4") (Flare connecting) Terminal block Gas piping:ø15.88 (5/8") (Flare connecting) A Opening for piping and electric wiring 50 50 Opening for…
-
Models FDC258HEN3A, FDCP258HEN3A, 308HEN3, 308HES3
Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening for electric wiring Opening for piping and…
-
Models FDCP408HES3, 508HES3
Unit: mm Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 (1050) Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and electric wiring Opening…
-
10.2.4 Exterior appearance
(1) Indoor unit Model All models Gray (Vertical lins) Ceramic white (Front panel) Gray (Frame) (2) Outdoor unit Models FDC208HEN3A FDCP208HEN3A Ceramic white (Air inlet louver) Models FDC258HEN3A FDCP258HEN3A 308HEN3 308HES3 Ceramic white (Side panel) Ceramic white (Front panel) Models FDCP408HES3…
-
10.2.5 Piping system
Models FDEN208HEN-S1, 258HEN-S1 FDENP208HEN-S, 258HEN-S Cooling cycle Indoor unit Heating cycle Outdoor unit High pressure switch (63H2) (For fan motor control) Thermistor (ThO-A) 4way valve Gas line (ø15.88) Strainer Service valve (Flare connecting) Thermistor High pressure switch (63H1) (Only case…
-
Model FDENP508HES-S
High pressure switch (63H2) (For fan motor control) Indoor unit Cooling cycle 4 way valve Strainer Gas line (ø19.05) Service valve (Flare connecting) High pressure switch (63H1) Thermistor (ThO-A) Check joint Heat exchanger Capillary tube Thermistor (ThI-A) Check joint Oil separator Thermistor…
-
10.2.6 Selsction chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in the following way. Net capacity = Capacity shown on specification ¥ Correction factors as follows. (1) Coefficient of cooling and heating capacity in…
-
Table of bypass factor
Model FDEN (P) 208 type FDEN (P) 258 type FDENP308 type FDENP408,508 type Hi 0.031 0.030 0.036 0.018 Lo 0.016 0.013 0.018 0.010 Item Air flow (2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction of…
-
10.2.7 Noise level
-
Model FDCP208HEN3A
-
BL
-
WH
-
X05
-
RD
-
таблицы и схемы — в просмотре
-
10.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 317. 10.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautions” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two…
-
NOTICE
All Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to Mitsubishi…
-
(3) Installation of indoor unit
(a) Detach the inside panel and suspension bracket. 2 1 Remove a fixing bolt of the side panel. 2 Unhook four hooks (marked ) by sliding the side panel in front side about 10 mm, and detach the side panel from the unit. 1 about m 10 m 3 Position of hooks Rear Front Side for front side about 10 mm…
-
Mount the unit using suspension bolts. Suspension bolts Flat washer (accessory parts) Hexagonal nuts (accessory parts) 4) Securely tighten the nuts and fix the indoor unit in place. 5) Attach the side panels and fit in ceiling board in the space around the unit and the work is finished. Fit in…
-
10.5.2 Installation of outdoor unit
This is same as FDT(N) heat pump series. Refer to page 338. 10.6 MAINTENANCE DATA This is same as FDT(N) heat pump series. Refer to page 348. 439