11. CEILING SUSPENSION TYPE
PACKAGED AIR-CONDITIONER Split system, Air cooled cooling only type ( ) Alternative refrigerant R407C use models FDENP208CEN-S 258CEN-S 308CEN-S 308CES-S 408CES-S 508CES-S 441
-
GENERAL INFORMATION 11.1.1 Specific features (1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been reduced by more than 50%. (2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer…
-
11.2 SELECTION DATA
11.2.1 Specifications Model FDENP208CEN-S FDENP208CEN-S Model Item FDEN208C Nominal cooling capacity(1) FDCP208CEN3 5000 W Power source 1 Phase, 220/240V, 50Hz kW 2.04/2.10 Running current (Cooling) A 9.4/9.5 Power factor (Cooling) % 99/92 Inrush current (L.R.A) A Noise level(4) Exterior dimensions…
-
Model FDENP258CEN-S
FDENP258CEN-S Model Item FDEN258C Nominal cooling capacity(1) FDCP258CEN3 5700 W Power source 1 Phase, 220/240V, 50Hz kW 2.35/2.54 Running current (Cooling) A 11.3/12.4 Power factor (Cooling) % 95/85 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Hi:44 Lo:39…
-
Model FDENP308CEN-S
FDENP308CEN-S Model Item FDEN308C Nominal cooling capacity(1) FDCP308CEN3 7100 W Power source 1 Phase, 220/240V, 50Hz kW 3.22/3.37 Running current (Cooling) A 14.9/15.3 Power factor (Cooling) % 98/92 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDENP308CES-S
FDENP308CES-S Model Item FDEN308C Nominal cooling capacity(1) FDCP308CES3 7100 W Power source 3 Phase, 380/415V, 50Hz kW 3.14/3.29 Running current (Cooling) A 5.5/5.8 Power factor (Cooling) % 87/79 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDENP408CES-S
FDENP408CES-S Model Item FDEN408C Nominal cooling capacity(1) FDCP408CES3 10000 W Power source 3 Phase, 380/415V, 50Hz kW 4.51/4.63 Running current (Cooling) A 7.8/8.2 Power factor (Cooling) % 88/79 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
Model FDENP508CES-S
FDENP508CES-S Model Item FDEN508C Nominal cooling capacity(1) FDCP508CES3 12500 W Power source 3 Phase, 380/415V, 50Hz kW 5.36/5.43 Running current (Cooling) A 9.5/9.8 Power factor (Cooling) % 86/77 Inrush current (L.R.A) A Noise level(4) Exterior dimensions Height × Width × Depth dB(A) Net weight…
-
11.2.2 Range of usage & limitations
Models Item FDENP208, 258 type FDENP308, 408, 508 type Indoor return air temperature (Upper, lower limits) Refer to the selection chart Outdoor air temperature (Upper, lower limits) Refrigerant line (one way) length Max. 30m Max. 50m Vertical height difference between outdoor unit and indoor unit…
-
11.2.3 Exterior dimensions
(1) Indoor unit Models FDEN208C, 258C, 308C 1244 [984] 15 (Holes for suspension bolt) The brackets face out 50 1160 [900] 50 (Holes for suspension bolt) The brackets face interior 135 the unit is suspended ) (When beneath the ceiling 10 20 Side panel 10 1200 [940] 30 ↑ ) Holes for suspension bolts…
-
15 1451 [1244] The brackets face out (Holes for suspension bolt) Holes for suspension bolts ) (Holes for suspension bolt) ) 135 ( 15 The brackets face interior When the unit is suspended beneath the ceiling (12 × 17 × 4pcs.) 50 1370 [1160] 50 20 Side panel 10 10 1410 [1200] 1470 [1260] 30 ↑ When the…
-
(2) Remote controller
(a) Wireless remote controller COOL DRY FAN FAN HI LO FILTER °C ON AM PM TEMP ON/OFF 161.5 MODE OFF AM PM 60 20.5 (b) Indication board of indoor unit Remote controller signal receiver 453
-
(3) Outdoor unit
Model FDCP208CEN3 Unit: mm Liquid piping: φ 6.35 (1/4") (Flare connecting) Gas piping: φ 15.88 (5/8") (Flare connecting) 95 Liquid piping: φ 6.35 (1/4") (Flare connecting) Terminal block Gas piping: φ 15.88 (5/8") (Flare connecting) 110 Opening for electric wiring Opening for piping and electric…
-
Models FDCP258CEN3, 308CEN3, 308CES3
Unit: mm Liquid piping: ø9.52 (3/8") (Flare connecting) 53 40 Gas piping: ø15.88 (5/8") (Flare connecting) 40 95 Terminal block Liquid piping: ø9.52 (3/8") (Flare connecting) Opening for piping and electric wiring 110 A Gas piping: ø15.88 (5/8") (Flare connecting) Opening for electric wiring Opening…
-
Models FDCP408CES3, 508CES3
Liquid piping: ø 9.52 (3/8") (Flare connecting) Gas piping: ø 19.05 (3/4") (Flare connecting) Terminal block Liquid piping: ø 9.52 (3/8") (Flare connecting) 1250 [1050] Gas piping: ø 19.05 (3/4") (Flare connecting) Opening for electric wiring A Opening for piping and electric wiring Opening for…
-
11.2.4 Exterior appearance
(1) Indoor unit Models All models Gray (Vertical lins) Gray (Frame) (2) Outdoor unit Model FDCP208CEN3 Ceramic white (Front panel) Ceramic white (Air inlet grill) Ceramic white (Side panel) Ceramic white (Front panel) Models FDCP258CEN3, 308CEN3, 308CES3 Models FDCP408CES3, 508CES3 Polar white Polar…
-
11.2.5 Piping system
Models FDENP208CEN-S, 258CEN-S Check joint Service valve Indoor unit Outdoor unit (Flare connecting) Thermistat (Tho-A) High pressure switch (63H1) Gas line (φ15.88) Thermistor (ThI–A) Thermistat (Tho-D) Heat exchanger Heat exchanger Caillary tabe Thermistor (ThI–R) Solenoid valve Compressor SV…
-
Model
FDENP508CES-S Otutdoor unit Indoor unit High pressure switch (63H1) Check joint Gas line ( ø19.05) Thermistor (Tho-A) Oil separator Service valve (Flare connecing) Thermistor (ThI-A) Heat exchanger Thermistor (ThI-R) Caillary tube Thermistor (Tho-R) Accumulator Capillary tube Compressor Solenoid…
-
11.2.6 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following way. Net capacity = Capacity shown on specification × Correction factors as follows. (1) Coefficient of cooling capacity in relation to temperatures Coefficient of…
-
Table of bypass factor
Model FDEN208C FDEN258C FDEN308C FDEN408,508C Hi 0.031 0.030 0.036 0.018 Lo 0.016 0.013 0.018 0.010 Item Air flow (2) Correction of cooling capacity in relation to flow rate control (fan speed) Coefficient: 1.00 at High, 0.95 at Low (3) Correction of cooling capacity in relation to one way length of…
-
11.2.7 Noise level
-
Y/GN
-
таблицы и схемы — в просмотре
-
52C
-
WH
-
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 317. 11.5 APPLICATION DATA The application data for the cooling only models are similar to those for the heat pump models. (See page 435.) 11.6 MAINTENANCE DATA…