Safety Precautions
• Before instralling this unit,make sure you read all the “Safety Precautions”. • This manual describes the installation of LM-AP and wiring to the outdoor unit. • Please look at the installation manual of an air-conditioning unit about the installation method of an air-conditioning unit. • The…
-
CAUTION
Do not install the unit where combustible gas may leak. If the gas leaks and accumulates around the unit, an explosion may result. When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise. The inverter equipment, private power…
-
1. Parts Include
Verify that the following parts are appended to the product. Name Main Unit Installation manual Binding band Shape Quantity · The external interface file (XIF) is necessary for the product. Upon verifying the 16-digit program ID (PID) which is bonded on the board, please contact your dealer. 2.…
-
2-3 Connected Air Conditioning Equipment
Item Description Connected Equipment MITSUBISHI ELECTRIC Multiple split type air conditioners CITY MULTI Split-type air conditioners Mr.SLIM Heat recovery ventilators LOSSNAY (* For details of the connected models, please contact the dealer.) Number of Units LM-AP can control 50 indoor units…
-
The following are applied to the CITY-MULTI type indoor unit of the Multiple split type air conditioners CITY MULTI. If Mr.SLIM or LOSSNAY is used, refer to the technical guide for the details of the network variables. Network Variables Request On/Off nv1n nviOnOff_n nv2n nvoOnOff_n On/Off run state…
-
3. Installation
<Notes> Read and understand the contents of Chapter 1 “Safety Precautions ” before performing the installation. 3-1 Locally Procured Parts Prepare the following prior to installing the unit. Locally procured parts Contents Power wire and ground wire Use the sheathed vinyl cord or wire. Wire type …………
-
3-2 Securing the Unit
• When installing the product, assure a space enough to install and remove the cover of the main body. • Use M4 screws as shown in Fig. below to fix the product. To prevent the product from dropping, make sure to fix four places. 20 Installation space CAUTION • This unit does not have a…
-
3-3 Connection Methods
Use wire clamps provided to secure the wires and prevent external force from being conveyed by the wire to the wire connections. * External force could cause deformation or damage to the terminal blocks. Note1 R S UP Connect the power supply wires and ground wire to “L”, “N” and ground of terminal…
-
3-4 Electrical Wiring
TB1 T2 CN71 F AC250V 2A F Unit Body 1 2 P.B. CN21 ZNR1 1 3 CN32 CN40 8 7 ON OFF SW3 ON OFF 1 6 LED009 (WDT) LED201 (18007RST) CN41 CNL12 LED502 (3150RST) LEDL (Service LED) SWL (Service Switch) 1 3 CN65 ON OFF M-NET Power Supply DSA1 CN45 ZNR2 4 T1 SW2 SW1 L.B. CN605 CN31 CN33 SWU1 (1st digit) SWU2…
-
4. System Settings
This chapter only addresses the system settings of this product. For the installation work and electrical work, refer to the last chapter “ 3. Installation ”. <Notes> Read and understand the contents of Chapter 1 “Safety Precautions ” before performing the installation. The system setting is…
-
4-2 If used together with MELANS
Power supply unit E Shielded wire ground ❇ OC : Outdoor Unit : Switch Position Centralized controller (MELANS) as is as is OC LM-AP SW2-1 [OFF] M-NET transmission line (Centralized control line) TB2 CN41 ON CN41 OFF TB7 SW1-2 [ON] TB3 M-NET transmission line (Indoor/outdoortransmission line) ON OFF…
-
4-3 Initialization Settings of LONWORKS® Network
(1) Termination of LONWORKS® The product can be set with the termination of LONWORKS® . Termination Switch (SW71) SW71-1 OFF ON OFF ON SW71-2 OFF OFF ON ON Termination Resistance Value – ( Factory setting) 100Ω ± 1% 50Ω ± 1% For details, refer to “ FTT-10A Free Topology Transceiver User's Guide ” of…
-
5. Confirming Operation
5-1 Pre-operation preparations and settings (1) Perform the previous operations described in Chapter 3 “ Installation” , Chapter 4 “ System Settings” . (2) Perform a test operation of indoor units. If being used together with MELANS, perform the installation and electrical installation for MELANS.…
-
6. Troubleshooting
6-1 Abstract If LM-AP does not properly operate, first check the following contents. Item Normal state Contents to check LED009 ON Check for turn-off on the power supply (TB1) of LM-AP, disconnection on the connectors (CN605, CN65, CN32, CN33, CN31, CN71) and blown fuse (F). LED402 ON Check for…
-
6-2 Troubleshooting
No. Error content 1 Even if it is in testoperation with LM-AP, the air conditioner does not run. Even if the operation is tested on LM-AP, the LOSSNAY does not operate. Cause Checking method and remedy (1)The LM-AP is not completely initialized. Turn off all SW2. After verifying that LED002 is OFF…
-
Error content
5 6 Independent/combi ned LOSSNAY can not be operated from the LON side. Air conditioner can not be operated from the LON side. Cause Checking method and remedy (1)The LM-AP is not completely initialized. Refer to 1-(1). (2)Setting on M-NET side is not properly completed. Refer to 1-(2). (3)If…
-
6-3 Error code list
Error code Error content Symptom Cause Countermeasure 6600 M-NET duplex error • If it has been confirmed that a unit with the same M-NET address is transmitting. • If there is two or more units with the same M-NET address at the unit and controller. • Check that there are no duplicate addresses.…
-
This product is designed and intended for use in the residential,
commercial and light-industrial environment. The product at hand is based on the following EU regulations: • Low Voltage Directive 78/23/EEC • Electromagnetic Compatibility Directive 89/336/EEC HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO 100-0005 TELEX J24532 CABLE MELCO TOKYO WT03223X02