02_NVspec_ver202e_pdf.xls cover
Version2.02 2001.02.06 AIR CONDITIONER INTERFACE MODEL: LMAP02-E PAC-YV02LMAP Network Variables Specification Specification Object Details SNVT Table Network Variables Configuration Properties Node Object AppendixA: Communication timing when power supply of LM-AP is turned on. ProgramID…
-
02_NVspec_ver202e_pdf.xls 1_Object Model
1.Specification 1-1.Object Model LMAP can be connected with the following models made by MITSUBISHI ELECTRIC CORPORATION. <Model name> 1. Multiple split type air conditioners CITY MULTI 2. Split-type air conditioners Mr.SLIM NOTE:Mr.SLIM is necessary for A-M Converter(PAC-SF48MA-E) 3. Heat recovery…
-
2 .Object Details
2-1.Overview Node Object Object Type #0 Network Variables Indoor[0] Network Variables Configuration Properties Indoor[1] Network Variables Indoor[50] Network Variables Indoor[0]: The indoor all unit common item Indoor[1]~Indoor[50]: indoor unit(01~50) WLN01-1023(Ver2.02) -3-
-
2-2.indoor unit
-
2-3.Mr.SLIM
Indoor[1]-[50] Network Variables nv1n nviOnOff_n SNVT switch nv2n nvoOnOff_n SNVT switch nv3n nviMode_n SNVT hvac mode nv4n nvoMode_n SNVT hvac mode nv5n nviSetPoint_n SNVT temp p nv6n nvoSetPoint_n SNVT temp p nv7n nviFanSpeed_n SNVT switch nv8n nvoFanSpeed_n SNVT switch nv10n nvoThermo_n SNVT…
-
2-4.LOSSNAY
(1)LOSSNAY interlocks with the indoor unit.(note 1,3) Indoor[1]-[50] Network Variables nv14n nvoLCMode_n SNVT switch nv16n nvoAlarm_n SNVT switch (note.4) (2)LOSSNAY is operation from LONW ORKS.(note 5,6) Indoor[1]-[50] Network Variables nv1n nviOnOff_n SNVT switch nv2n nvoOnOff_n SNVT switch nv13n…
-
2-5.Common ( note 1 )
Indoor[0] Network Variables nv11 nviAllOff_n SNVT switch Configuration Properties nciSndHrtBt_1 Send Heartbeat_1 nciSndHrtBt_2 Send Heartbeat_2 nciMinOutTm Minimum Send Time nciInitStartTm Initialize Start Time nciInitOutTm_1 Initialize Send Time_1 nciInitOutTm_2 Initialize Send Time_2 nciStartHrtBt…
-
3.SNVT Table
02_NVspec_ver202e_pdf.xls 3_SNVT Table Model nv No. Name (note 1) (note 1) CITY LOSSNAY Mr.SLIM interlocks with the indoor unit MULTI SNVT Type input operation from LONWORKS output Transmitted when changing Auto update Initialize (note 2) Request On/Off 1n nviOnOff_n X X X SNVT_switch value state…
-
4. Network Variables
1n Request On/Off network input SNVT_switch nviOnOff_n; This input network variable is used for ON or OFF request of the indoor unit or ventilator (in case of independent operation) . When the ventilator(LOSSNAY) is registered interlocking with the indoor unit, it will ON (for high speed) and OFF…
-
3n Request mode
network input SNVT_hvac_mode nviMode_n; This input network variable is used to change the operation mode of the indoor unit. This nv is not required to use when setting the operation mode only from the local side such as the local remote controller. Valid Range HVAC_AUTO:0 = Auto mode HVAC_HEAT:1 =…
-
13n Request LOSSNAY Mode
network input SNVT_switch nviLCMode_n; This input network variable is used to change the operation mode of the ventilator (at independent operation without interlocking) . This nv is not required to use when setting the operation mode only from the local side such as the local remote controller.…
-
5n Setpoint from network (Both cool and heat)
network input SNVT_temp_p nviSetPoint_n; This input network variable is used to change the temperature setpoint of the indoor unit. * The set temperature applied is used for cool/dry/heat/auto modes and not for fan mode operation. This nv is not required to use when setting the temperature only from…
-
7n Request Fan Speed
network input SNVT_switch nviFanSpeed_n; This input network variable is used to change the fan speed of the indoor unit or Ventilator (in case of independent operation). This nv is not required to use when setting the airflow rate only from the local side such as the local remote controller. Valid…
-
10n Thermo On/Off state
network output SNVT_state nvoThermo_n; This output network variable indicates the On/Off state of the indoor unit, the thermostat (compressor command signal) and the auxiliary heater for heating. This nv is used to calculate the electric charge. Valid Range bit[0] : 0 = Indoor Off bit[0] : 1 =…
-
16n Alarm state
network output SNVT_switch nvoAlarm_n; This output network variable indicates the abnormality of the indoor unit. If the outdoor unit is in alarm state, the indoor unit also stops urgently. Therefore all indoor units in a same refrigerant system will transmit alarm state when the outdoor unit is…
-
19n Request Local Prohibit On/Off
network input SNVT_switch nviProOnOff_n; This input network variable is used to prohibit the On/Off operation of the local remote controller connected to the indoor unit or ventilator (under independent operation without interlocking). When the ventilator is registered to be interlocked with the…
-
21n Request Local Prohibit mode
network input SNVT_switch nviProMode_n; This input network variable is used to prohibit the mode change operation of the local remote controller connected to the indoor unit. Valid Range value field : not used state field : 0 = Permit mode change operation of local remote controller state field : 1…
-
23n Request Local Prohibit SetPoint
network input SNVT_switch nviProSetP_n; This input network variable is used to prohibit the temperature setpoint change of the local remote controller connected to the indoor unit. Valid Range value field : not used state field : 0 = Permit temperature setpoint change for local remote controller…
-
11 Request All Off
network input SNVT_switch nviAllOff; This input network variable is used for the emergency Off of the indoor unit and all ventilation. Valid Range value field : not used state field : 0 = Emergency Off of indoor unit and ventilator : Else = not used Default Value The default value is determined by…
-
5.Configuration Properties
(1) Send Heartbeat_1 network input config SNVT_time_sec nciSndHrtBt_1; This network configuration defines the time between the previous and next updating. When the set time is elapsed from the automatic update or change output of the previous nvoOnOff_n (On/Off Run State), automatic updating will be…
-
Minimum Send Time network input config SNVT_time_sec nciMinOutTm; This configuration property defines the minimum send time between the output network variables. The objective network variables are given below. nvoOnOff_n(On/Off Run State ) nvoMode_n(Mode State) nvoLCMode_n(LOSSNAY Mode State)…
-
Initialize Send Time_1 network input config SNVT_time_sec nciInitOutTm_1 This configuration property defines the minimum send time between the output network variables at initial output. This configuration is valid when setting the Initialize Start Time to other values than 0.0 second. The objective…
-
Send Heartbeat Start Time network input config SNVT_time_sec nciStartHrtBt This configuration property defines the start time of automatic updating at the powering of the LM-AP. The objective network configurations are given below. nciSndHrtBt_1(Send Heartbeat_1) nciSndHrtBt_2(Send Heartrbeat_2)…
-
02_NVspec_ver202e_pdf.xls 6_node_object
6. Node Object 1n Object Request network input SNVT_obj_requst nviRequest; Valid Range object_id :0 =valid request :Else =invalid request object_request :2(RQ_UPDATE_STATUS) :Else =valid request =invalid request Default Value The default value is 0. 2n Object Status network output SNVT_obj_status…
-
02_NVspec_ver202e_pdf.xls AppendixA
Communication timing when power supply of LM-AP is turned on Power Supply Initialized Processing t Usually Processing 0 (7)nciStartHrtBt (1)nciSndHrtBt_1 (8)nciStartOutTm (6)nciInitOutTm_2 (6)nciInitOutTm_2 Initialization of LM-AP (15 minutes or more) (4)nciInitStartTm (3)nciMinOutTm…