VRF-системы Midea - Внутренние блоки V8: MIH15GHN18, MIH22GHN18, MIH28GHN18, MIH36GHN18, MIH45GHN18, MIH56GHN18, MIH71GHN18, MIH80GHN18, MIH90GHN18. Руководство по техническому обслуживанию.
Смотрите также: Руководство по установке →Инструкция по монтажу и эксплуатации → Коды ошибок: 69 кодов →
Загружаем документ…
Текст инструкции
-
‘Mid
-
The AHU kit connects the indoor unit to the outdoor unit
Indoor unit combination Outdoor Unit V6/V6i / Combination Capacity control method V8 V6pro Platform /VX/VXi/ Mini C V6R VXpro / VC Input set Control 1 √ √ 2 / Mini C/ V5X/V4+W AHU kit -F × × × √ √ √ × × series (V8) capacity Control 3 [3] Input set Indoor unit [1] Outdoor unit 100% unit/Outdoor…
-
R32 System Service Indoor units in this manual can be used with both R410A and R32 refrigerant systems. When repairing systems that use R32 refrigerant, the following warnings and operating requirements should be noted. 2.1 Warning about the R32 refrigerant The following information indicates a…
-
– the charge size is in accordance with the room size within which the refrigerant containing parts are installed; – the ventilation machinery and outlets are operating adequately and are not obstructed; – if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for…
-
• • evacuate; purge again with inert gas; open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or…
-
refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions…
-
CN99 After-sale Kit communication port 12VDC Standard Notes: 1. Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump and Humidity sensor etc. Customized: The port is not available on the mainboard. If necessary, you need to customize…
-
Table 3.2: voltage test instructions (continue)
Code Content CN190 Drainage pump port Description Description When the water pump is running, pin 2 and 3 output 12V DC 1 pin CN30 Display panel Using the DC voltage gear of the multimeter connection to test pin 1 and 4, the value should be 12V; GND GND-L Midea V8 Series VRF Indoor Units 1 pin Using…
-
3.2 Four-way Cassette
-
Notes
1. Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump and Humidity sensor etc. Customized: The port is not available on the mainboard. If necessary, you need to customize the port Reserved: This port can not be used. 2. When…
-
3.3 Arc Duct
Figure 3.3: Arc Duct main PCB ports Troubleshooting Guide Table 3.4: Arc Duct main PCB ports Label in Figure 3.3 1 Code CN1(L.N) CN22 2 (ALARM,N,AC2 ) 3 4 CN12(H-L) CN29(H-N) CN100 Content Port voltage Note AC power input 220V AC Standard 220V AC Standard Reserved 220V AC Reserved Power supply for…
-
Table 3.4: Arc Duct main PCB ports (continued)
Label in Code Content 7 CN81 T2 Temperature sensor connection 3.3V DC Standard 8 CN82 T1 Ambient Temperature sensor connection 3.3V DC Standard 9 CN83 T2B Temperature sensor connection 3.3V DC Standard 10 CN-A Sterilization module port 12V DC Standard 11 CN30 Display Panel connection 12V DC[5]…
-
3.4 Medium Static Pressure Duct
Figure 3.4: Medium Static Pressure Duct main PCB ports Troubleshooting Guide Table 3.5: Medium Static Pressure Duct main PCB ports Label in Figure 3.4 1 Code CN1(L.N) CN22 2 (ALARM,N,AC2 ) 3 CN12(H-L) CN29(H-N) Content Port voltage Note AC power input 220V AC Standard 220V AC Standard Reserved 220V…
-
CN80 T2A Temperature sensor connection 3.3V DC Standard Table continued on next page … Table 3.5: Medium Static Pressure Duct main PCB ports (continued) Label in Code Content Port voltage Note 7 CN81 T2 Temperature sensor connection 3.3V DC Standard 8 CN82 T1 Ambient Temperature sensor connection…
-
3.5 Wall Mounted
-
CN25 Program burning port(indoor unit) 22 CN100 Power supply for fan motor 23 CN99 After-sale Kit communication port 3.3V DC Standard Actual voltage Standard 12VDC Standard Notes: 1. Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump…
-
3.6 One-way Cassette
-
CN80 T2A Temperature sensor connection 3.3V DC Standard 19 CN-A Sterilization module port 12V DC Standard 20 CN16 Reserved 3.3V DC Reserved 21 CN25 Program burning port(indoor unit) 3.3V DC Standard 22 CN100 Power supply for fan motor Actual voltage Standard 23 CN99 After-sale Kit communication port…
-
3.7 Two-way Cassette
Figure 3.7: Two-way cassette main PCB ports Troubleshooting Guide Table 3.8: Two-way cassette main PCB ports Label in Figure 3.7 1 Code CN1(L.N) CN22 2 (ALARM,N,AC2 ) 3 CN12(H-L) CN29(H-N) Content Port voltage Note AC power input 220V AC Standard 220V AC Standard Reserved 220V AC Reserved AC power…
-
Table continued on next page …
Table 3.8: Two-way cassette main PCB ports (continued) Label in Code Content Port voltage Note 7 CN81 T2 Temperature sensor connection 3.3V DC Standard 8 CN82 T1 Ambient Temperature sensor connection 3.3V DC Standard 9 CN83 T2B Temperature sensor connection 3.3V DC Standard 10 CN-A Sterilization…
-
CN100 Power supply for fan motor 23 CN99 After-sale Kit communication port Actual voltage Standard 12VDC Standard Notes: 1. Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump and Humidity sensor etc. Customized: The port is not…
-
3.9 High Static Pressure Duct (5.6-16kW)
Figure 3.9: High Static Pressure Duct main PCB ports (5.6-16kW) Troubleshooting Guide Table 3.10: High Static Pressure Duct main PCB ports (5.6-16kW) Label in Figure 3.9 1 Code CN1(L.N) CN22 2 (ALARM,N,AC2 ) Content Port voltage Note AC power input 220V AC Standard 220V AC Standard AC power output…
-
Table continued on next page …
Table 3.10: High Static Pressure Duct main PCB ports (continued) Label in Code Content Port voltage Note 9 CN81 T2 Temperature sensor connection 3.3V DC Standard 10 CN82 T1 Ambient Temperature sensor connection 3.3V DC Standard 11 CN83 T2B Temperature sensor connection 3.3V DC Standard 12 CN5 Water…
-
3.10 High Static Pressure Duct (20-56kW)
-
Table 3.11: High Static Pressure Duct main PCB ports (continued)
Label in Figure 3.10 10 11 Content Port voltage Note CN30 Display Panel connection 12V DC[5] Standard Humidity sensor connection 3.3V DC[5] Standard Standard CN35 12 CN5 Water level switch port 3.3V DC[5] 13 CN190 Drainage pump port 12V DC[5] Standard 14 CN18 Switch module 5V/12V DC[5] Standard 15…
-
Figure 3.11: Fan module ports (20-56kW)
Troubleshooting Guide Table 3.12: High Static Pressure Duct main PCB ports (continued) Label in Code Content 1 CN1(N) Power input 220V AC Standard 2 CN2(L) Power input 220V AC Standard 3 CN21 Reserved 220V AC Reserved 4 CN22 Reserved 220V AC Reserved 5 CN8 Main control board connection 5V DC…
-
Table 3.13: voltage test instructions
Label Code Content Picture 5V 5 CN8 Main control board connection GND 6 CN25 Program burning port(fan module) Midea V8 Series VRF Indoor Units GND 30 5V
-
3.11 Ceiling&Floor
-
Notes
1. Standard: The port is standard, the customers can connect corresponding device through this port, such as water pump and Humidity sensor etc. Customized: The port is not available on the mainboard. If necessary, you need to customize the port Reserved: This port can not be used. 2. When…
-
3.12 Fresh Air Processing
Figure 3.13: Fresh Air Processing main PCB ports Troubleshooting Guide Table 3.3: Fresh Air Processing main PCB ports Label in Code Content Port voltage Note 1 CN1(L,N) AC power input 220V AC Standard 2 CN22 220V AC Standard 3 CN27 220V AC Standard 4 CN35 Humidity sensor connection 3.3V DC Standard…
-
Label in
Figure 3.2 15 Code Content Port voltage Note CN25 Program burning port (indoor unit) 3.3V DC[5] Standard Standard 16 CN8 EEV drive port 12V DC[5] 17 CN30 Display panel connection 12V DC Standard 18 CN55 Remote on/off switch connection Note 5 Standard CN6(X1X2, X1 X2 communication port (with wire…
-
3.13 Small Airflow Rate Fresh Air Processing
Troubleshooting Guide Table 3.3: Fresh Air Processing main PCB ports Label in Figure 3.2 1 Code CN1(L,N) Content Port voltage Note AC power input 220V AC Standard 220V AC Standard / Standard 3.3V DC Standard Reactor connection 3.3V DC Standard AC power output used for customization function: 2 CN22…
-
Label in
Code Content Port voltage Note 15 CN25 Program burning port (indoor unit) 3.3V DC[5] Standard 16 CN-A Sterilization module port 12V DC Standard Drainage pump port 12V DC[5] Standard Standard Figure 3.2 17 CN190 18 CN8 EEV drive port 12V DC[5] 19 CN30 Display panel connection 12V DC Standard Standard…
-
Table 3.2: voltage test instructions (continue)
Code CN35 Content Humidity sensor connection Description Description Using the DC voltage gear of the multimeter to test pin 4 and 5, the value should be 3.3V GND 3.3V 1 pin The water level is normal, the water level CN5 Water level switch switch is in the channel state; when the port water level is…
-
4 Indoor unit settings
Midea V8 Series VRF Indoor Units 4.1 Parameter settings Taking KJR-86S/BK as an example, the parameters can be set in the power-on or power-off state. ①Hold " " and " " for 3 seconds to enter the parameter setting interface, and the main interface will display "CC" ② Spot check a) Wired controller…
-
Parameter
-
таблицы и схемы — в просмотре
-
Parameter
-
Parameter
Code Parameter Name Parameter Range Default Value 00: Disable Whether energy C17 efficiency attenuation is displayed when Remarks 01: Enable 00/01 00 The setting is valid only when the wired controller is connected to a V8 power off IDU. 00: Disable Whether IDU filter C18 blockage is displayed 01…
-
Table 4.2: Indoor unit Parameter Settings
Paramete r Code Parameter Name Parameter Range Default Value Remarks IDU static pressure level: N00 Static pressure of IDU 00/01/02/03/ The IDU sets the selected corresponding static pressure FF 04/05/06/07/08/ (FF-there may be different default values for different series of indoor units)…
-
Paramete
r Code Parameter Name Parameter Range Default Value Remarks 0-7 3 0-7 indicates 0 - 7°C (The value is accurate to 1°C or 1°F.) 0-10 5 0-10 indicates -4 - 6°C(The value is accurate to 1°C or 1°F.) 00/01 00 T1 temperature N13 difference for auxiliary heat source/alternative heat source to turn on T1…
-
таблицы и схемы — в просмотре
-
Parameter
Code N35 N37 Parameter Name Q4/Q4C air outlet 4 setting One-to-more of wired controller enabled Parameter Range Default Value 00/01 00 00/01 00 Remarks 00 - Free control 01 - Off 00: No 01: Yes 00: Remote off (closed); N38 Remote On/Off port logic of the IDU 01: Remote off (open) 00/01 00 Note: When…
-
Parameter
Code N49 Parameter Name Condensation proof Parameter Range Default Value 00/01 00 Remarks 00: Invalid 01: Valid 00: Invalid N50 Human Detect Sensor 00/01/02 01 01: Used to adjust the set temperature when unattended 02: Used to turn off the unit when unattended 00: 15 min Setting temperature N51…
-
Parameter
Code Parameter Name Parameter Range Default Value 00/01/02 00 Ambient temperature N60 when preheating is Remarks 00: 5°C turned on 01: 0°C 02: (-5)°C 00: Disconnected N61 Fresh air dry contact 1 00/01 00 01: Connected Note: Applicable to FAPU only 00: Disconnected N62 Fresh air dry contact 2 00/01…
-
Parameter
Code Parameter Name Parameter Range Default Value 00/01/02/03/04 00 Remarks Anti-cold wind N74 temperature setting of 00/01/02/03: corresponds to different values; 04: Anti-cold wind disabled special IDUs 00: After the remote shutdown signal is canceled, the IDU runs in the preset mode or based on…
-
Check No
Parameters Remarks 11 Actual RH indoor humidity Actual value = value displayed 12 [―――] is displayed 13 Air discharge pipe temperature Actual value = value displayed 14 Compressor discharge temperature Actual value = value displayed 15 Target superheat Actual value = value displayed 16 EEV opening…
-
4.3 Function Descriptions
4.3.1 Power failure memory function The power failure memory function can be used to ensure that, in the event of a power outage, the indoor units, which was in operation before, automatically restart once the power returns. When the power returns following a power outage, units with Power failure…
-
Display Panels 5.1 Appearance of Display Panel The appearance of the digital display panel used is shown in Figure 5.1. Figure 5.1: Digital display panel1 Display panel for Compact Four-way Cassette and Four-way Cassette (New 360 degree panel, standard panel) Midea V8 Series VRF Indoor Units LED…
-
5.2 Output under Normal Operating Conditions
Unit state Digital display Standby Cooling and heating : set temperature Normal operation Operating dehumidify mode: set temperature Fan only mode: indoor ambient temperature Special operation1 Mode code Error2 Error code Notes: 1. The special operation modes refer to Table 7.2:Operating Status…
-
Control 6.1 Temperature Compensation Control Because of the installation position of Indoor Unit and different layout, indoor temperature detected by Indoor Unit may not consist with actual temperature. Indoor temperature could be compensated by controller (The parameter code is”N25” “N26”) 6.2 EEV…
-
6.3 Start and Stop Control
⚫ Cooling (Dry) Cooling(Dry) T1 − T𝑠 ≥ (0 + ΔTC)℃ T1 − T𝑠 <( − 1 + ΔTC)℃ ⚫ Enter standby mode when the set temperature is reached Heating T1 − T𝑠 <(0 + ΔTC)℃ Heating T1 − T𝑠 ≥ (1 + ΔTC)℃ Enter standby mode when the set temperature is reached Note: The temperature compensation value (ΔTC) of cooling…
-
6.4 Fan Control
6.4.1 Fan speeds control The IDU can work in seven-speeds or three-speeds. ⚫ Seven-speeds When the Indoor Unit detects seven wind speeds the wind speed is set as follows. Sleep Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Auto ⚫ Three-speeds When the Indoor Unit detects only three wind…
-
⚫ Determine the initial fan speed of auto fan control
The initial fan speed is determined according to the difference between ambient indoor temperature (T1) and set temperature (TS), and it updates in the following situations: 1) The first time enter this mode 2) TS is changed 3) When switching between normal operation and silent operation 6.4.3…
-
6.5 Swing control
-
6.5.2 Vertical swing control
Figure 6.2 Vertical swing control Different IDU series have different adjustable swing angle and default swing angle under different functions. And each operation mode has its default adjustable range of swing angle. P1-P5 values vary because of the different operation modes and IDU series. For…
-
6.5.3 Individual louver control
Four-way Cassette and Compact Four-way Cassette have the individual louver control and the detail according to the following: a) Louver selection: After entering the louver selection operation, all air flap immediately stop at the current spot and record the current spot. If there is no parameter…
-
Outdoor Unit is Heat Pump ①When the mode is set by ODU to VIP priority, Voting priority, Capability requirements priority, Cooling priority, heating priority, the Indoor Unit can be set to cooling, heating, dehumidification, ventilation modes. When the IDU set mode different from the mode of ODU…
-
The Human detect sensor is optional
The operation mode of human detect control can be set by controller (N50). 1) When set the mode "Used to adjust the set temperature when unattended" and enter the unattended state1, the following logic is executed ① When the cooling/automatic cooling mode operates, the correction value2 of the set…
-
2) 3) When the IDU is powered on the first time, the water pump is forced to operate for 5 minutes. When the IDU and ODU are in cooling, dehumidification and self-cleaning mode, the water pump starts immediately and operates continuously. After this mode is stopped (stop or mode switch), the water…
-
For embedded IDU series, such as Compact Four-way Cassette and Four-way Cassette, when the installation exceeds the specified height (default 3 meters), can enter the High ceiling setting ( The parameter code is”N31” ) to change . 3 meters high height, 4 meters high height or 4.5 meters high height…
-
6.13 Dry mode control
There is a difference between the control with humidity sensor and the control without humidity sensor, when the humidity sensor is damaged, the indoor unit automatically switches to the state without humidity sensor. ⚫ Without humidity sensor Related settings: ①The temperature of dry mode;②Maximum…
-
Errors and operation code 7.1 Error Code Table Table 7.1: Error code Error Content code Emergency stop C52 A11 R32 refrigerant leaks, requiring shutdown immediately C61 A51 Outdoor unit fault C71 A72 Midea V8 Series VRF Indoor Units A73 Interlocking control Heat Recovery Ventilation Unit fault(…
-
Table 7.1: Error code(continues)
Error Content code E31 E32 E33 E61 E62 E81 wired controller temperature sensor failure The wireless temperature sensor short-circuits or cuts off The external room temperature sensor short-circuits or cuts off Tcp (pre-cooled fresh air temperature sensor) shortcircuits or cuts off Tph (pre-heated…
-
Troubleshooting Warning Midea V8 Series VRF Indoor Units ▪ All electrical work must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations…
-
8.1.1 A01 – Emergency shutdown
Digital display Display position Error display Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: stop running, displaying code "A01" (V6 platform indoor Error impact unit displays "A0" code) ODU of the same system: stop running, displaying code "A01" (V6…
-
8.1.2 A11 - R32 refrigerant leaks, requiring shutdown immediately
Digital display Display position Error display Panel, display box, and wired controller ◼ Faulty IDU: The fan operates at the highest speed, the EEV is closed (Note: Fault persists after power on again), and buzzer of the display control board of the faulty IDU and buzzer of wired controller…
-
Note 1: Adapter board ENC1 dip switch setting When the function of determining refrigerant
leakage fault is effective, if the communication abnormality between indoor unit main control board, adapter board and R32 refrigerant detection device control board lasts for more than 2 minutes (see "C79" fault handling in this manual for the communication abnormality handling method between…
-
Recharge refrigerant according to the ODU Installation Manual. (2) If the measured refrigerant saturation pressure on the liquid side or gas side is equal to the standard saturation pressure (see Table of Ambient Temperature and Standard Saturation Pressure of R32 attached to this manual), confirm…
-
8.1.3 A51 - ODU fault
Digital display Display position Error display Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: The fan continues running, the EEV is closed, and code "A51" is displayed (V6 platform IDU displays the code "Ed") Error impact ODU of the same system: ◼ stops. ◼…
-
8.1.4 A71 - The error of the linked FAPU is transmitted to the master IDU (series setting)
Note: 1) The type of FAPU may be HRV, VRF fresh air IDU and so on. 2) Series setting: The air supply side of the linked FAPU is directly connected to the air return side of the master IDU through an air duct. A wired controller is used to set this installation method as a series connection. Digital…
-
8.1.5 A72 - The error of the linked humidifying IDU is transmitted to the master IDU
Digital display Error display Display position (master IDU) Panel or display box Wired controller Spot check interface Error code is not query displayed Master IDU: operates normally. Humidifying IDUs: stop. Other IDUs of the same system: operate Error impact normally. ODU of the same system…
-
8.1.6 A73 - The error of the linked FAPU is transmitted to the master IDU (non-series connection)
Note: 1) The type of FAPU may be HRV, VRF fresh air IDU and so on. 2) Series setting: The linked FAPU and the master IDU are connected to the air supply duct and air return duct respectively and separately. A wired controller is used to set this installation method as a non-series connection.…
-
8.1.7 A74 - The error of the AHU Kit slave unit is sent to the master unit
Note: When multiple AHU Kits are connected in parallel, the master AHU Kit (referred to as the master) communicates with the ODU, and the slave AHU Kit (referred to as the slave) communicates with the master unit. When the slave fails, the slave unit sends a fault signal to the master unit, and the…
-
8.1.8 A81 - Self-check fault
Digital display Display position Error display Panel, display box, and wired controller Faulty IDU: stops. Other IDUs of the same system: ◼ IDUs that share the same MS with the faulty IDU will stop operating, while other IDUs remain in operation. ◼ IDUs that share the same MS with the faulty IDU…
-
8.1.9 A82 - MS (refrigerant flow direction switching device) fault
Digital display Display position Faulty IDU Panel, display box, and wired controller Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: ◼ IDUs that share the same MS with the faulty IDU: The fan continues running, and the EEV is closed. Other IDUs remain in…
-
8.1.10 A91 - Mode conflict (V6 communication protocol adopted)
Available when using V6 platform wired controller. Digital display Display position Panel, display box, and wired controller Error display (Note: Error codes are displayed 2 minutes after faults are triggered) Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same…
-
8.1.11 b11, b13 - Error in 1# electronic expansion valve coil, error in 2# electronic expansion valve coil Digital display Display position Error display Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. Error impact Error trigger Error…
-
1. The error code corresponds to the following two situations
a. If there is only one electronic expansion valve port on the main control board of the IDU, when an error occurs in the electronic expansion valve coil connected to the EEV port, the error code is b05. b. If there are two electronic expansion valve ports on the main control board of the IDU named…
-
8.1.12 b12, b14 - Error in 1# electronic expansion valve body, error in 2# electronic expansion valve body Digital display Display position Panel or display box Error display Spot check interface query Error impact Wired controller Error code is not displayed The faulty IDU and other IDUs of the…
-
8.1.13 b34, b35 - Stall protection for 1# water pump, stall protection on 2# water pump
Digital display Display position Error display Error impact The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger The main control board of the IDU detects the pump rotation speed ≤ 100 rpm for 10 seconds Error recovery…
-
8.1.14 b36 - Water level switch alarm error
Digital display Display position Error display Error impact Error trigger Error recovery Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. The water level switch alarm is triggered when the…
-
1. The plug attached to the WATER port of the main control board corresponds to the following two cases: a. The factory default of IDUs without a water level switch uses a short-circuit plug to seal the WATER port. b. IDUs with a water level switch use a water level switch plug to seal the WATER…
-
8.1.15 C11 - Duplicate IDU address code
Digital display Display position Panel or display box Error display Error code and address code are displayed alternately (2) Wired controller Error code and address code flash simultaneously Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: The fan…
-
1. The following table shows the number of addresses and address codes for any indoor unit (AHU kit/direct expansion unit not applicable) with different capacities (HP) Address code to be Nominal capacity capacity (HP) (kW) Number of Number of IDUs (N) addresses (N) queried at the Address code…
-
★Example: If one IDU is 5 HP and the address code is set to 1, then the query address at the centralized controller side or wired controller side is 1. If one IDU is 20 HP and the address code is set to 5, then this IDU has four address codes, which are 5, 6, 7, and 8, but the query address at the…
-
8.1.16 C21 - Abnormal communication between IDU and ODU
Digital display Error display Display position Panel, display box, and wired controller Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: The fan continues running, the EEV is closed, and error code "A51" is displayed (V6 platform IDU displays the code…
-
If the indoor and outdoor units communicate via HyperLink (M1M2): Properly connect the cable Cause 2: The repeater UP and DOWN ports are not connected to the corresponding indoor unit (2) Properly connect the cable Cause 3: The power supply of repeater is cut off Check the power supply of the…
-
Figure 1 Schematic diagram of HyperLink communication cable connection
Upstream IDU and ODU of repeater 1# (including master ODU) Master ODU IDU 10# IDU 1# Repeater 1# Repeater 2# IDU 11# IDU 20# IDU 21# Downstream IDUs of repeater 1# Upstream IDUs of repeater 2# IDU 30# Downstream IDUs of repeater 2# 1) The UP communication port of 1# repeater is connected to the…
-
8.1.17 C41 - Abnormal communication between IDU main control board and fan drive board
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the main control board of an IDU has lost communication with the fan…
-
8.1.18 C51: communication exception between the IDU and wired controller
Note: The error code C51 can be triggered either at the IDU side or the wired controller side. LED display Display position If a powered-on IDU does not receive any message from the wired controller: 1) Wired controller: "C51" is displayed; 2) Panel or display box: The LED display and the error code…
-
Troubleshooting
Cause 1: The communication wire does not meet antiinterference requirements Replace the communication wire that meets antiinterference requirements Cause 2: The communication wire is bonded and connected or the wire end metal oxidation exists, leading to the connection failure Reconnect the signal…
-
8.1.19 C61 - Abnormal communication between the IDU main control board and display control board
Note: The error code C61 can be triggered either at the IDU side or at the panel or display box side. Digital display Display position After power on, normal communication was not established between the indoor unit and the wired controller: 1) The wired controller does not display fault code; Error…
-
C61
Cause 1:Unplug the display box or panel communication wire from the main control board of powered indoor unit. Reconnect the communication cable or re-power the IDU Cause 2:Use a wrong port Use correct port by referring to the w7iring diagram Cause 3:The communication wire between the display…
-
8.1.20 C71 - Abnormal communication between AHU Kit slave unit and master unit
Note: When multiple AHU Kits are connected in parallel, the master AHU Kit (referred to as the master) communicates with the ODU, and the slave AHU Kit (referred to as the slave) communicates with the master AHU Kit. Digital display Display position (master) Error display Error impact Error trigger…
-
8.1.21 C72 - Number of AHU Kits is not the same as the set number
Note: When multiple AHU Kits are connected in parallel, the master AHU Kit (referred to as the master) communicates with the ODU, and the slave AHU Kit (referred to as the slave) communicates with the master AHU Kit. Digital display Error display Display position (master) Master AHU Kit: Display box…
-
8.1.22 C73 - Abnormal communication between the linked humidifying IDU and master IDU
Digital display Display position (master IDU) Error display Panel or display box Wired controller Spot check interface Error code is not query displayed Master IDU: operates normally. Humidifying IDUs: stop. Other IDUs of the same system: operate Error impact normally. ODU of the same system…
-
8.1.23 C74 - Abnormal communication between the linked FAPU and master IDU (series setting)
Note: 1) The type of FAPU may be HRV, VRF fresh air IDU and so on. 2) Series setting: The air supply side of the linked FAPU is directly connected to the air return side of the master IDU through an air duct. A wired controller is used to set this installation method as a series connection. Digital…
-
8.1.24 C75 - Communication fault between linked FAPU and master IDU (non-series setting)
Note: 1) The type of FAPU may be HRV, VRF fresh air IDU and so on. 2) Series setting: The linked FAPU and the master IDU are connected to the air supply duct and air return duct respectively and separately. A wired controller is used to set this installation method as a non-series connection.…
-
8.1.25 C76 - Abnormal communication between the main wired controller and secondary wired controller
Note: The error code C51 can be triggered either at the IDU side or at the wired controller side. Digital display Error display Display position The error code "C76" is displayed only on the secondary wired controller Error impact The faulty IDU and other IDUs of the same system: operate normally.…
-
8.1.26 C77, C78 - Abnormal communication between IDU main control board and 1# Expansion Board,
abnormal communication between IDU main control board and 2# Expansion Board Digital display Display position Error display Panel, display box, and wired controller Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: Error impact operate normally. ODU of the…
-
8.1.27 C79 - Abnormal communication between the IDU main control board and Switch module
Digital display Display position Error display Panel, display box, and wired controller Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: operate Error impact normally. ODU of the same system: operate normally. Error trigger If the main control board of an…
-
8.1.28 C81—The indoor unit is in a power-off state
Digital display Display position Central controller or various types of control terminal Error display software Midea V8 Series VRF Indoor Units ◼ Error impact The faulty indoor unit and the panels, display boxes, and wired controllers connected to it will stop running, and the central controller or…
-
8.1.29 d16 - Air inlet temperature of IDU is too low in heating mode
Digital display Display position Error display Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. Error impact Error trigger ODU of the same system: operate normally. If the air inlet temperature of the IDU is lower than the set value (See…
-
8.1.30 d17 - Air inlet temperature of IDU is too high in cooling mode
Digital display Error display Display position Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. Error impact Midea V8 Series VRF Indoor Units Error trigger ODU of the same system: operate normally. If the air inlet temperature of the IDU…
-
8.1.31 d50 - AHU kit fan running status input signal exception
LED display Display position Fault Display Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. Fault Impact ODU of the same system operates normally. The V8 series AHU kit fan runs normally, but the fan ON/OFF input port on the main control…
-
8.1.32 dE1 - Sensor control board fault
Digital display Display position Error display Midea V8 Series VRF Indoor Units Error impact Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the main control board of an IDU has…
-
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the main control board of an IDU has lost communication with PM2.5…
-
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the main control board of an IDU has lost communication with CO2 sensor…
-
8.1.35 dE4 - Formaldehyde sensor fault
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the main control board of an IDU has lost communication with…
-
8.1.36 dE5 - Human Detect sensor fault
Note: The human detector sensor on the smart panel is used to detect the location of the human body. Digital display Display position Error display Error impact Midea V8 Series VRF Indoor Units Error trigger Panel, wired controller The faulty IDU and other IDUs of the same system: operate normally.…
-
8.1.37 E21, E24, E81 - T0 (fresh inlet air temperature sensor) short-circuits or cuts off, T1 (IDU return air temperature sensor) short-circuits or cuts off, and TA (outlet air temperature sensor) short-circuits or cuts off Digital display Display position Error display Error impact Panel, display…
-
sensors are short-circuited or open-circuited, but it is not able to determine if the T1 sensor is short-circuited or open-circuited. 4) Only the master unit needs to be connected to the T1/T0/TA sensors when the AHU kit is Midea V8 Series VRF Indoor Units installed in parallel. 116
-
8.1.38 E31: wired controller temperature sensor failure
LED display Display position Panel or display box Fault Display Wired controller Panel, display box, and wired controller Fault Impact The faulty IDU and other IDUs of the same system operate normally. ODU of the same system operates normally. When the V8 series FAPU uses room temperature control…
-
8.1.39 EA2 - Return air humidity sensor fault
Digital display Error display Error impact Error trigger Error recovery Possible cause Display position Panel or display box Wired controller Spot check interface Error code is not query displayed The faulty IDU and other IDUs of the same system: operate normally. ODU of the same system: operate…
-
8.1.40 EC1: R32 refrigerant leakage sensor fault
LED display Display position Fault Display Panel, display box, and wired controller Faulty IDU: stops. Other IDUs of the same system: operate normally. Fault Impact ODU of the same system operates normally. Fault Trigger The IDU main control board receives sensor module fault signal from the R32…
-
Figure 1 Schematic diagram of the R32 refrigerant leakage detection system D-D: Common terminal A-A: Transmit R32 refrigerant leakage alarm signal B-B: Transmit R32 refrigerant detection device fault signal Connect an alarm or a fan Output 220VAC A-A/B-B/D-D three-core communication wire (configured…
-
8.1.41 F01, F11, F21 - T2A (heat exchanger liquid pipe temperature sensor) short-circuits or cuts off, T2 (heat exchanger middle temperature sensor) short-circuits or cuts off, and T2B (heat exchanger gas pipe temperature sensor) short-circuits or cuts off Digital display Display position Error…
-
8.1.42 P31/P34 - Fan drive board AC side overcurrent protection
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. ◼ Error trigger Error recovery P31: The current value detected on the AC side of the…
-
8.1.43 P52 - The voltage of the power supply is too low
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger ◼ Power supply voltage is below the programmed protection threshold…
-
8.1.44 P71 - Main control board EEPROM fault
Digital display Display position Error display Error impact Error trigger Error recovery Possible cause Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. When the master chip cannot receive data…
-
8.1.45 P72 - IDU display control board EEPROM fault
Digital display Display position Error display Panel or display box The faulty IDU operates normally, and the error code is displayed on the panel or display box only. Other Error impact IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger Error recovery…
-
8.1.46 U01 - Locked (electronic lock)
Digital display Display position Error display Error impact Panel, display box, and wired controller All IDUs of the same system: stop running, displaying code "U01" ODU of the same system: stops running, displaying code "U01" Error trigger When detecting that the ODU is locked Error recovery…
-
8.1.47 U11 - Unit model code not set
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system: ◼ If the address for the faulty IDU has been set, other IDUs will operate normally. ◼ If the address of the faulty IDU was not set, other IDUs…
-
8.1.48 U12 - Capacity(HP) code not set
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system: Error impact ◼ If the address for the faulty IDU has been set, other IDUs will operate normally. ◼ If the address of the faulty IDU was not set…
-
8.1.49 U14 - The capacity value of the AHU Kit DIP switch does not match the model
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. Error impact 2) Other IDUs of the same system: operate normally ODU of the same system: operate normally Error trigger Error recovery The capacity value of the AHU Kit DIP switch…
-
8.1.50 U15 - The DIP value of AHU Kit's fan speed output voltage is incorrect
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. Error impact 2) Other IDUs of the same system: operate normally ODU of the same system: operate normally The voltage values corresponding to the high/medium/low speed of the AHU…
-
8.1.51 U26 - Mismatch between indoor unit model and outdoor unit model
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system will operate normally Error impact Error trigger ODU of the same system: ◼ If there is one IDU in the system is operating normally, the ODU will…
-
8.1.52 U38 - Address code not detected
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system: The fan continues running, the EEV is closed, and ODU error code "A51" Error impact is displayed (V6 platform IDU displays the code "Ed"). ODU of…
-
8.1.53 J01 - Motor failed more than once
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If fan control faults have occurred 10 times in 120 min (1) Error…
-
Fault Impact
ODU of the same system operates normally. The fault is triggered if one of the following conditions is met: 1) The current value (AC) detected for any phase line of U/V/W on the IPM exceeds the set Fault Trigger overcurrent protection value of the IPM. 2) A fault signal output by the IPM protection…
-
The current value (AC) detected for any phase line of U/V/W on the IPM exceeds the set overcurrent
Fault Trigger protection value of the driver. Fault Recovery Automatic recovery ◼ ◼ Possible Cause ◼ ◼ There is no fan wheel installed on the motor. Motor coils are short-circuited, or the motor bearing is worn, resulting in an abnormal increase of motor current. The fan drive board is damaged. The…
-
8.1.56 J3E - Low bus voltage fault
Digital display Display position Panel or display box Wired controller Spot check interface query Error code is not displayed Error display Error impact The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger When the bus voltage…
-
8.1.57 J31 - High bus voltage fault
Digital display Display position Error display Panel, display box Wired controller Error impact The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger When the bus voltage (DC voltage) is greater than the threshold value of the…
-
8.1.58 J43 - Phase current sample bias error
Digital display Display position Error display Panel, display box Wired controller Error impact The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger When detecting that the current sample is 50% greater than 2.5 V Error…
-
8.1.59 J45 - Motor and IDU unmatched
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger If the motor code sent by the IDU main control board is not found in the…
-
8.1.60 J47 - IPM (fan module) and IDU unmatched
Digital display Display position Error display Error impact Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger When detecting that the fan drive board does not match the set value of…
-
8.1.61 J5E - Motor startup failure
Digital display Error display Display position Panel, display box Wired controller Error impact The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. Error trigger Motor startup failure Error recovery Automatic recovery Possible cause ◼…
-
Panel, display box, and wired controller
Fault Impact ODU of the same system operates normally. Fault Trigger The motor is blocked. Fault Recovery Automatic recovery Possible Cause Midea V8 Series VRF Indoor Units The faulty IDU stops. Other IDUs of the same system: operate normally. ◼ ◼ ◼ ◼ There is no fan wheel installed on the motor.…
-
8.1.63 J55 - Speed control mode setting error
Digital display Display position Error display Panel, display box Wired controller Error impact Error trigger Error recovery Possible cause The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. The IDU is non constant air flow control, but…
-
Digital display Display position Error display Panel, display box Wired controller Error impact ODU of the same system: operate normally. Error trigger When the motor phase lacks protection Error recovery Automatic recovery Possible cause Midea V8 Series VRF Indoor Units The faulty IDU stops. Other…
-
Appendix 9.1 Temperature Sensor Resistance Characteristics Table 9.1: Indoor temperature sensors resistance characteristics R25=10KΩ±3% B25/50=4100K±3% Resistance Resistance Resistance Temperature Resistance Resistance Resistance (°C) min(kΩ) Normal(kΩ) max(kΩ) (°C) min(kΩ) Normal(kΩ) max(kΩ) -40…
-
Table 9.1: Indoor temperature sensors resistance characteristics(continues)
Resistance Resistance Resistance Temperature Resistance Resistance Resistance (°C) min(kΩ) Normal(kΩ) max(kΩ) (°C) min(kΩ) Normal(kΩ) max(kΩ) 40 4.926 5.179 5.441 80 1.060 1.166 1.281 41 4.718 4.968 5.225 81 1.025 1.128 1.240 42 4.521 4.766 5.019 82 0.990 1.091 1.201 43 4.333 4.573 4.822 83 0.958…
-
Table 9.1: Indoor temperature sensors resistance characteristics(continues)
Resistance Resistance Resistance Temperature Resistance Resistance Resistance (°C) min(kΩ) Normal(kΩ) max(kΩ) (°C) min(kΩ) Normal(kΩ) max(kΩ) 120 0.308 0.351 0.400 121 0.299 0.342 0.389 122 0.291 0.332 0.379 123 0.283 0.324 0.370 124 0.276 0.315 0.360 125 0.268 0.307 0.351 126 0.261 0.299 0.342 127…
-
9.2 Ambient Temperature and Standard Saturation Pressure of R410A
Table 9.2: Ambient Temperature and Standard Saturation Pressure of R410A (saturated vapor state) Midea V8 Series VRF Indoor Units Ambient Saturated gauge Saturated Ambient Saturated gauge Saturated Ambient Saturated gauge Saturated gauge Temperature pressure gauge pressure Temperature pressure gauge…
-
Table 9.2: Ambient Temperature and Standard Saturation Pressure of R410A (saturated vapor state)-continue 50 2961.7 429.55 57 3487.2 505.78 64 4083.4 592.25 51 3032.8 439.87 58 3567.8 517.47 65 4175 605.54 52 3105.2 450.36 59 3649.9 529.38 66 4268.3 619.07 53 3178.9 461.05 60 3733.5 541.5 67 4363.5…
-
Table 9.3: Ambient Temperature and Standard Saturation Pressure of R410A (Saturated liquid state) -continue 1739.6 252.31 43 2505.8 363.44 57 3495.4 506.96 30 1787.8 259.3 44 2568.5 372.54 58 3575.9 518.64 31 1837 266.43 45 2632.4 381.8 59 3657.9 530.53 32 1887.1 273.7 46 2697.5 391.24 60 3741.3…
-
9.3 Ambient Temperature and Standard Saturation Pressure of R32
Table 9.4: Ambient Temperature and Standard Saturation Pressure of R32 Ambient Saturated gauge Saturated Ambient Saturated gauge Saturated Ambient Saturated gauge Saturated gauge Temperature pressure gauge pressure Temperature pressure gauge pressure Temperature pressure pressure (°C) (kPa) (psi)…
-
Table 9.4: Ambient Temperature and Standard Saturation Pressure of R32 (continue)
53 3263.1 473.27 59 3746.3 543.36 65 4282.9 621.19 54 3340.1 484.45 60 3831.9 555.77 66 4378 634.97 55 3418.6 495.82 61 3919 568.4 67 4474.7 649 56 3498.4 507.39 62 4007.6 581.25 68 4573.2 663.29 57 3579.6 519.17 63 4097.8 594.33 69 4673.4 677.82 58 3662.2 531.16 64 4189.6 607.64 70 4775.5 692.63…
-
S-V8IN
Ver. 2023-12 Troubleshooting Guide Midea Building Technologies Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 mbt.midea.com / global.midea.com / tsp.midea.com Midea reserves the right to change the specifications of the…