Инструкции на Модульные VRF-системы Midea - Наружные блоки V8S
Модульные VRF-системы Midea - Наружные блоки V8S: MV8S-252WV2GN1, MV8S-280WV2GN1, MV8S-335WV2GN1, MV8S-400WV2GN1, MV8S-450WV2GN1, MV8S-500WV2GN1, MV8S-560WV2GN1, MV8S-615WV2GN1, MV8S-670WV2GN1. Руководство по техническому обслуживанию.
Смотрите также: Инструкция по монтажу и эксплуатации → Коды ошибок: 71 код →
Загружаем документ…
Текст инструкции
-
R410A
-
idea
-
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units 1.1.1 Standard indoor units Table 1-1.1: Standard indoor unit abbreviation codes Abbreviation Type code Q1 One-way Cassette Type High Static Pressure Duct Q2 Two-way Cassette G Wall-mounted Q4C Compact Four-way Cassette DL Ceiling & Floor Q4 Four-way Cassette F Floor Standing…
-
1.3 Outdoor Units
-
2 External Appearance
2.1 Indoor Units 2.1.1 Standard indoor units Midea V8S Series Service Manual Table 1-2.1: Standard indoor unit appearance One-way Cassette Two-way Cassette Q1 Q2 Compact Four-way Cassette Four-way Cassette Q4C Q4 Arc Duct Medium Static Pressure Duct T3 T2 High Static Pressure Duct Floor Standing T1…
-
2.3 Outdoor Units
2.3.1 Single units Table 1-2.4: Single outdoor unit appearance 8/10/12/14HP 16/18/20/22/24HP 2.3.2 Combinations of units Table 1-2.5: Combination outdoor unit appearance 30/32/38HP 34/36/40/42/44/46/48HP 52HP 50/56HP 54/58/60/62/64/66/68/70/72HP 74HP 76/78/80/82/84/86/88/90/92/94/96HP Part 1…
-
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations Midea V8S Series Service Manual System capacity kW HP 25.2 8 28.0 10 33.5 12 40.0 14 45.0 16 50.0 18 56.0 20 61.5 22 67.0 24 73.5 26 80.0 28 85.0 30 90.0 32 95.0 34 100.0 36 106.0 38 112.0 40 117.5 42 123.0 44 128.5 46 134.0 48 140.0 50 145.0 52 150.0 54 156.0…
-
4 Nomenclature
4.1 Indoor Units 4.1.1 Standard indoor units V8 indoor units M IH 18 Q1 H N18 ○ ○ ○ ○ ○ ○ Legend No. Code Remarks 1 M Midea 2 IH V8 VRF indoor unit 3 22 Capacity index (the capacity in kW multiplied by 10) Indoor unit type Q1: One-way Cassette Q2: Two-way Cassette Q4C: Compact Four-way Cassette Q4…
-
DC Indoor Units
M I 2 - 22 Q1 D H N1 ○ ○ ○ ○ ○ ○ ○ ○ Midea V8S Series Service Manual Legend No. Code Remarks 1 M Midea 2 I VRF indoor unit Capacity index (the capacity in kW multiplied by 10) 5 Q1 Indoor unit type Q1: One-way Cassette Q2: Two-way Cassette Q4C: Compact Four-way Cassette Q4: Four-way Cassette T2…
-
4.1.2 Fresh air processing unit
V8 Fresh air processing unit M IH 224 FA H N18 ○ ○ ○ ○ ○ ○ Legend No. Code Remarks 1 M Midea 2 IH V8 VRF indoor unit 3 22 Capacity index (the capacity in kW multiplied by 10) Indoor unit type 4 FA FA: Fresh Air Processing Unit FAS: Small Air Flow Fresh Air Processing Unit Power supply 5 H Omit: 1…
-
DC Series
HRV - D ○ ○ ○ Legend No. Code Remarks 1 HRV Heat recovery ventilator 2 D Series category (D: DC series) 3 200 Airflow in m3/h 4.2 Outdoor Units M V8S - 252 W V2 G N1 1 ○ ○ ○ ○ ○ ○ ○ Midea V8S Series Service Manual Legend No. Code Remarks 1 M Midea 2 V8S The 8th generation Side Flow VRF 3 252…
-
Sum of capacity indexes of connected indoor
-
6 Selection Procedure
6.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Step 2: Select indoor units Decide indoor unit safety factor Midea…
-
6.2 Example
The following is a selection example based on total heat load for cooling. Figure 1-6.1: Room plan Room A Room B Room H Room G Room C Room D Room F Room E Step 1: Establish design conditions Indoor air temperature 25.8°C DB, 18°C WB; outdoor air temperature 33°C DB. Determine peak load of each…
-
Table 1-6.2: Extract from medium static pressure duct (T2) cooling capacity table
-
Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
-
c)
Find the correction factor for piping length and level difference (“K1”) 0.93 0.81 0.83 0.86 1.0 10 0.94 0 0.98 30 0.97 K1=0.927 40 10 0.90 0.94 50 20 0.93 Figure 1-6.3: V8S rate of change in cooling capacity 0.81 0.83 0.86 0.90 40 0.97 30 0.98 Midea V8S Series Service Manual 20 1.0 10 Notes: 1. The…
-
Part 2
Component Layout and Refrigerant Circuits Part 2 - Component Layout and Refrigerant Circuits 1 Layout of Functional Components 20 2 Piping Diagrams 22 3 Refrigerant Flow Diagrams 25 19
-
1 Layout of Functional Components
1.1 8-14HP layout of functional components Figure 2-1.1: 8-14HP layout of functional component 7 6 Midea V8S Series Service Manual Legend No. 20 Parts name No. Parts name 1 Inverter compressor 11 Stop valve (liquid side) 2 Oil separator 12 Electronic expansion valve (EEVC) 3 High pressure switch 13…
-
1.2 16-24HP layout of functional components
Figure 2-1.2: 16-24HP layout of functional components Part 2 - Component Layout and Refrigerant Circuits Legend No. Parts name No. Parts name 1 Inverter compressor 11 Stop valve (liquid side) 2 Oil separator 12 Electronic expansion valve (EEVC) 3 High pressure switch 13 Electronic expansion valve…
-
2 Piping Diagrams
2.1 8-14HP piping diagram Figure 2-2.1: 8-14HP piping diagram 8-14 HP 7 Tg 7 T3 T8 21 T4 ST1 6 E S C 10 EEVA 9 TL SV5 5 SV7 PH 14 T6B HPS PL MHE T6A 1 20 ACC INV1 13 19 Heat SV8A 15 Customized EEVE T7C1 T 71 Midea V8S Series Service Manual O/S EEVC T5 11 17 Legend 22 No. Parts name No. Parts name 1…
-
2.2 16-24HP piping diagram
Figure 2-2.2: 16-24HP piping diagram 7 Tg 7 T3 T8 21 T4 ST1 6 E S C 10 EEVA 9 TL SV5 5 SV7 PH 14 T6B HPS PL T6A ACC INV1 13 19 Heat SV8A 15 Customized EEVE 1 20 T 71 T7C1 8 Part 2 - Component Layout and Refrigerant Circuits MHE O/S 2 12 EEVC T5 11 17 Legend No. Parts name No. Parts name 1 Inverter…
-
Midea V8S Series Service Manual
2.3 Key components 1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Gas-liquid separator: Separates liquid refrigerant from gas refrigerant, stores liquid refrigerant and oil to protect…
-
Refrigerant Flow Diagrams 3.1 Cooling operation Figure 2-3.1: 8-24HP refrigerant flow during cooling operation Part 2 - Component Layout and Refrigerant Circuits Note: There is no SV8A for 20/22/24HP outdoor units. High temperature, high pressure gas High temperature, high pressure liquid Low…
-
3.3 Oil return operation in cooling mode
Midea V8S Series Service Manual Figure 2-3.3: 8-24HP refrigerant flow during oil return operation in cooling mode Note: There is no SV8A for 20/22/24HP outdoor units. High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure gas 3.4 Oil return operation…
-
1 General Control Scheme Flowchart
Sections 2 to 8 on the following pages detail when each of the controls in the flowchart below is activated. 2 Stop operation Abnormal shutdown System stops A unit stops when the load demanded decreases 3 Standby control Crankcase heater control 7 Special control Midea V8S Series Service…
-
2 Stop Operation
The stop operation occurs for one of the three following reasons: 1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs,the system will makes a 'stop with thermos-off' operation and an error code will be displayed on the outdoor unit digital displays. 2. The system…
-
3 Standby Control
3.1 Crankcase Heater Control The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped. The crankcase heater is controlled mainly according to the minimum of discharge temperatures. When the minimum of discharge temperatures is above 45°C…
-
4.3 Startup Control for Cooling Operation
Table 3-4.1: Component control during startup in cooling mode Component Wiring diagram label Inverter INV1 compressor Inverter fan 1 ODU FANB Four way valve ST1 Electronic expansion valve IDU Ending conditions 0Hz 0Hz 0 Step If T4 exceeds the operating range, off 2min after the 12th gear is operated…
-
4.4 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode Component Wiring diagram label Startup control Before startup STEP1 STEP2 STEP3 0Hz 0Hz 0Hz 0Hz Inverter fan 1 Inverter fan 2 0 Step 0 step 0 step 0 step Start: 0 step, then adjust by the high pressure and PI control low pressure…
-
5 Normal Operation Control
5.1 Component Control during Normal Operation Table 3-5.1: Outdoor unit component control during normal operation Wiring diagram label Component Inverter compressor COMP(A) Inverter fan 1 FANA Inverter fan 2 FANB Cooling Heating PI control, High pressure protection, Low pressure protection…
-
5.2 Compressor Control
Cooling operation Compressor frequency is PI controlled to keep low pressure at target temperature. Te: Low pressure equivalent saturation temperature (°C) Tes: Target Te value. Tes will be decided by Te setting, if you choose Auto that means except Te setting, the Tes would be adjusted according to…
-
5.3 Rotation of outdoor units
In order to make operating time equal for each outdoor unit, outdoor units are used in rotation. Figures 3-5.1 to 3-5.2 show the compressor rotation in systems with two and three units. The master unit and slave units 1 and 2 are shown from left to right in that order, and the circled numbers…
-
5.5 Electronic Expansion Valve Control
5.5.1 EEVA control The positions of electronic expansion valves EEVA are controlled in steps from 0/0 (fully closed) to 480/2880 (fully open). 5.5.1.1 Outdoor unit heat exchanger is performed via the evaporator Midea V8S Series Service Manual when outdoor temperature ≥- 8°C: This function is used to…
-
5.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-5.9 Table 3-5.9: Outdoor fan speed steps Fan speed (rpm) Fan speed 8-14HP 16-24HP index FANA FANB FANA FANB 1030 1090 1160 1030 1090 1160 1000 1050 1090 1020 1070 1110 16 18/20 8/22 10/12/14/24 heating Startup or defrosting…
-
Table 3-5.10 Upper limit fan step in static pressure mode
cooling Outdoor unit/HP Static Pressure mode 0Pa 20Pa 40Pa 60Pa 80Pa Heating Outdoor unit/HP Midea V8S Series Service Manual Static Pressure mode 0Pa 20Pa 40Pa 60Pa 80Pa Note: 1. Standard models can provide 35Pa maximum external static pressure. High static pressure models can provide 80Pa maximum…
-
6 Protection Control
6.1 High Pressure Protection Control This control protects the system from abnormally high pressure and protects the compressors from transient spikes in pressure. Figure 3-6.1: High pressure protection control Normal operation Pc ≥ 4.15MPa Pc < 3.5MPa High pressure protection, error code P12 is…
-
6.4 Over-current Protection Control
Over current protection control is performed to prevent tripping due to transient inverter over-current. It protects the compressors from abnormally high currents. It is performed for each compressor. Figure 3-6.6: Over-current protection control Normal operation Current ≥ CurrentA Current <…
-
6.6 Inverter Module Temperature Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally high temperatures. It is performed for each compressor and inverter module. 6.6.1 Error code F62 Figure 3-6.9: Inverter module temperature protection control Normal operation Ntc…
-
6.8 High Pressure Ratio Protection Control
This high pressure ratio protection control is used to prevent the activation of protection devices due to abnormal increase of high pressure ratio, and to protect compressors against the transient increase of high pressure ratio. It is performed for entire system. Figure 3-6.11: High pressure ratio…
-
7 Special Control
7.1 Oil Return Operation In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that are in standby. When the outdoor…
-
Cooling indoor unit
FAN Electronic expansion valve (EEV) 500P EEV Thermo ON unit Thermo OFF unit Stop or Fan Thermo ON unit Thermo OFF unit Stop or Fan Keep the previous fan speed Superheat control 80pls 80pls Midea V8S Series Service Manual 7.1.2 Heating Oil Return Control It’s basically identical with defrosting…
-
7.2 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor heat exchanger temperature, indoor heat exchanger temperature and…
-
8 Other Control
8.1 Overload control Overload control is used to maintain comfort requirement (i.e. outlet air temperature) and keep proper system pressure. Figure 3-8.1: Overload control Normal operation Indoor unit operation ratio <105% Indoor unit operation ratio ≥ 130% Overload control, indoor units operates in…
-
Table 3-8.4: Low noise mode-1
ODU Silent mode 1 Silent mode 2 Silent mode 3 Max. Max. Fan step frequen cy step Max. Max. Fan step frequen cy step Max. Max. Fan step frequen cy step Silent mode 4 Silent mode 5 Silent mode 6 Max. Fan step Max. frequen cy step Max. Fan step Max. frequen cy step Max. Fan step Max. frequen cy step…
-
8.5 Power Limitation Mode
The energy saving mode is used to limit the system power. It can be used to limit the line selection current or to reduce the peak current. Table 3-8.5: Power limitation mode Power limitation mode setting Power limitation mode level n23 40 n23 41 n23 42 Midea V8S Series Service Manual n23 40 ~n23…
-
Part 4
Field Settings 1. Overview 50 2. Digital display and button settings 50 3. System Parameter Check 60 Part 4 - Field Settings 49
-
1. Overview
This chapter describes how the system configuration can be implemented once the installation is completed , and other relevant information. It contains the following information: Implement field settings Using the Check function Midea V8S Series Service Manual 2. Digital display and button…
-
2.3 Menu mode
Only master unit has the full menu functions, slave units only have error codes check and cleaning functions. 1. Long press SW5 "MENU" button for 5 seconds to enter menu mode, and the digital display displays "n0". 2. Press SW3 / SW4 "UP / DOWN" button to select the first level menu "n0" to "n9"or…
-
Menu mode function
Table 4-2.3 Menu mode function: First level menu n0 (Information query) Second level menu Specified menu mode 0 (History error) 0 Query History error (last ten error codes) 1 Cleaning history error 1 (address) 0 Query Indoor unit's address 2 Query the address of Indoor unit in power-off condition 2…
-
First level menu
Second level menu 1 (Silent mode) 2 (static pressure) Specified menu mode Description 8 Silent mode 8 9 Silent mode 9 A Silent mode 10 b Silent mode 11 C Silent mode 12 d Silent mode 13 E Silent mode 14 0 0Pa static pressure 1 20Pa static pressure 2 40Pa static pressure(Customized) 3 60Pa static…
-
First level menu
n3 (Installation parameters) Specified menu mode 7 (Ambient temperature) 0 Enable Internal ambient temperature sensor(T4) √ 1 Enable External ambient temperature sensor(T10-Optional) - 0 Reserved - 1 Reserved √ 0 Reserved - 1 Reserved √ 0 - Set address of Outdoor unit - 1 - Set Network address of…
-
First level menu
n6 (evaporation and condensation temperature) n8 Second level menu 2 (target condensation temperature of the indoor unit) 7 (Low noise defrosting) 1 (Rotation) n9 5 0 nc[1] (Dry contact function) 1 2 Description Default 0 41°C 1 42°C 2 43°C 3 44°C 4 45°C 5 46°C 6 48°C √ 7 51°C - 0 Low noise…
-
2.4 Special mode introduction
2.4.1 Priority mode setting Priority mode can only be set on the master unit. When an indoor unit is in mode conflict with the outdoor units the unit displays the mode conflict error. The digital display on indoor main PCB will display error code E0. Midea V8S Series Service Manual There are ten…
-
5. Changeover mode: Before using this mode, you need to set the VIP indoor unit address. The default VIP address is 63, the VIP address also can be changed through menu mode“n1-6”. In changeover mode, if the VIP indoor unit is operating, the outdoor units will operate in the mode of the VIP indoor…
-
Step1:preparation
Step2:Calculate static pressure of Outdoor unit Step3:Indoor and outdoor temperatures are within the allowable range of test run No Display error code U32/U33/U34 Midea V8S Series Service Manual Yes Turn on all indoor units Yes Step4:The stop valve has been opened No Display error code U35 Yes…
-
3. System refrigerant quantity detection
After entering this mode, the system will automatically run and finally output the diagnostic results of the system refrigerant quantity. Diagnostic results: a) b) c) d) e) Normal: Digital display “d34” f) No result- The system operation conditions do not meet the functional requirements: Digital…
-
3. System Parameter Check
3.1 UP / DOWN system check button Before pressing UP or DOWN button, allow the system to operate steadily for more than an hour. On pressing UP or DOWN button, the parameters listed in below table will be displayed in sequence. Table 4-3.1 system check list: DSP1 content Midea V8S Series Service…
-
DSP1 content
Parameters displayed on DSP2 Remarks 28.-- Primary current(A) Actual value = value displayed /10 29.-- Inverter compressor A current (A) Actual value = value displayed /10 30.-- Reserved - 31.-- EEVA position Actual value = value displayed × 24 32.-- Reserved - 33.-- EEVC position Actual value =…
-
DSP1 content
Parameters displayed on DSP2 Remarks 0 :No result 1 :Significantly insufficient 51.-- Refrigerant volume judgment (1) 2 :insufficient 3 :Normal 4 :excessive 5 :Significantly excessive Midea V8S Series Service Manual 52.-- Dirty blockage rate (outdoor heat exchanger) 53.-- Fan historical error 54.…
-
1. Outdoor Unit Electric Control Box Layout
Figure 5-1.1: 8-24HP top layer of electric control box Main control board Midea V8S Series Service Manual Communication terminals block Power supply terminals Figure 5-1.2: 8-24HP bottom layer of electric control box Filter board Inductor Reactor Compressor drive board DC fan drive board 64 PED…
-
Outdoor Unit Main Control Board 2.1 Outdoor unit main Control Board ports Figure 5-2.1: Outdoor unit main Control Board ports1 Part 5 - Electrical Components and Wiring Diagrams Notes: Label descriptions are given in Table 5-2.1: Main Control Board port . 65
-
Table 5-2.1: Main Control Board port
Label in Figure 5-2.1 Port code Content Port voltage 1 CN82 Reserved 5Vdc 2 CN36 Reserved 3.3Vdc 3 CN70 EEVA drive port 12Vdc 4 CN71 EEVB drive port(Reserved) 12Vdc 5 CN72 EEVC drive port 12Vdc 6 CN73 EXVE drive port 12Vdc Microchannel heat exchanger inlet temperature sensor(T6A) /Liquid pipe inlet…
-
2.2 Outdoor unit main Control Board components
2.2.1 Layout Figure 5-2.2: Outdoor unit main Control Board components Part 5 - Electrical Components and Wiring Diagrams 2.2.2 Function of buttons SW3 to SW6 Table 5-2.2: Function of buttons SW3 to SW6 Button SW3 (UP) SW4 (DOWN) SW5 (MENU) SW6 (OK) Function In menu mode: previous and next buttons…
-
Digital display output Table 5-2.4: Digital display output in different operating states Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2 The number of indoor units in Standby The address of outdoor unit communication with the outdoor DSP1 units Normal operation For…
-
Compressor & Fan drive board 3.1 Corresponding table of Compressor & Fan drive board and outdoor units Table 5-2.5: Corresponding table of Compressor & Fan drive board and outdoor units Model 35A 8-14HP 50A 16-18HP 75A 20-24HP Part 5 - Electrical Components and Wiring Diagrams Compressor & Fan drive…
-
3.3 Compressor & Fan drive board of 50A
Midea V8S Series Service Manual Figure 5-2.4: Compressor & Fan drive board of 50A 3.4 Compressor & Fan drive board of 75A Figure 5-2.5: Compressor & Fan drive board of 75A 70
-
3.5 Compressor & Fan drive board ports
Figure 5-2.6: Compressor & Fan drive board ports of 50A Part 5 - Electrical Components and Wiring Diagrams Table 5-2.6: Compressor & Fan drive board port Label in Port Feature Figure 5-2.5 code identifier 1 CN1 P-in 2 CN5 P-out 3 CN16 L1 Three phase power input of L1 phase 4 CN7 L2 Three phase power…
-
Table 5-2.6: Compressor & Fan drive board port
Label in Port Feature Figure 5-2.5 code identifier 6 CN38 - 7 CN26 - 8 CN3 DCFAN CN8/C Midea V8S Series Service Manual 9 N9 O-Motor Content Port voltage Power supply terminal for DC fan drive board (P,N) 438Vdc~650Vdc(Rated 540Vdc; (Reserved) P is positive, N is negative) Fan module controls power…
-
3.6 The installation guide of Compressor & Fan drive board
Figure 5-2.7: The installation guide of Compressor & Fan drive board Part 5 - Electrical Components and Wiring Diagrams 73
-
1. Before maintaining or repairing the outdoor unit, cut off the power supply of the outdoor unit for 5 minutes and use a mustimeter to ensure that the voltage is zero to avoid electric shock. Notice The unit has the low-power standby function. After entering this mode, only the power indicator of…
-
4. Wiring Diagrams
Figure 5-3.1: V8S outdoor unit wiring diagram Part 5 - Electrical Components and Wiring Diagrams 75
-
1 Error Code Table
1.1 Outdoor Error code table Table 6-1.1 Outdoor Error code table Error code Error description Manual re-start Remarks required2 Emergency shutdown Outdoor unit’s fault NO AAx No.x Inverter driver board does not match the main control board Outdoor unit’s fault NO xA61 No.x slave unit error Salve…
-
Table 6-1.1 Outdoor Error code table (continued)
Midea V8S Series Service Manual Error code Error description Remarks Manual re-start required2 P11 High pressure sensor error Sensor error NO P12 High pressure protection Pressure protection NO P13 High pressure switch protection Pressure protection NO P14 P12 protection occurs 3 times in 60 minutes…
-
1.2 Installation and debugging error code table
Table 6-1.2 Installation and debugging error code table Error code Error description Manual re- Remarks start required2 U11 Outdoor unit model is not set System configuration YES U12 Outdoor unit Capacity setting error System configuration YES U21 System contains the old Indoor Unit with old…
-
Error code
Error description Remarks Manual re-start required2 xL51 Out-of-step error Control error NO xL52 Locked-rotor protection Motor error NO xL6E Compressor motor lack of phase protection Diagnosis error NO xLBE High pressure switch operation Pressure protection NO xLB7 Other check exceptions Diagnosis…
-
d36
Refrigerant quantity judgment:Significantly insufficient Status hint NO d37 IDU connected to system is not common Status hint NO d38 Too low proportion of running IDUs Status hint NO d39 Failed to detect refrigerant amount during backup Status hint NO d42 Communication error between the outdoor unit…
-
2 Error in Main Control
2.1 A01: Emergency shutdown of Outdoor Units Digital display output Midea V8S Series Service Manual Description Compressor protection shut down All Outdoor Units stop running Error codes are displayed only on master uint. Trigger / recover condition Scenario 1: ODU menu item n28 is set to 0: …
-
A01
One or both of the following are true: nC0 = 3 or nC1 = 3 If nC0 3, ignore port Input1 in the following troubleshooting If nC1 3, ignore port Input2 in the following troubleshooting Yes Menu set item n28 = 0 Yes Are Input1 and Input2 of port CN28 of the main board connected to the external? (See…
-
Digital display output Description xA61 shows a slave unit error with the ODU address of x (x = 1,2). All Outdoor Units stop running Error code are displayed only on master unit. Midea V8S Series Service Manual Trigger / recover condition Trigger condition: Slave unit is in error.…
-
2.3 AAx: Inverter driver board X does not match the main control board
Digital display output Description No.x Inverter driver board does not match the main control board All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: Parameters of the built-in drive in the module board do not match…
-
Digital display output Midea V8S Series Service Manual Description No.x Recirculation Fan[1] is in error Unit with the error stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: the difference between the actual fan speed…
-
2.5 bA1: HyperLink cannot open or close IDU’s Electronic expansion valve
Digital display output Description When some IDUs are powered off, HyperLink fail to close their EEV. All units stop running. Error code is only displayed on the master unit Error is generated only under the M1M2 communication protocol. Trigger / recover condition Trigger condition:when…
-
Digital display output Midea V8S Series Service Manual Description All units stop running Error code is displayed on the outdoor unit with the error. Trigger / recover condition Trigger condition: The main control board has not detected signals from the EEV for 2 minutes. Recover…
-
Digital display output 1b01 Part 6 - Diagnosis and Troubleshooting Description All units stop running Error code is displayed on the outdoor unit with the error. Trigger / recover condition Trigger condition: The main control board has not detected signals from the EEV for 2 minutes.…
-
2.8 C13: The address of Outdoor Unit is repeated
Digital display output Description The address of Outdoor Unit is repeated. Error code is displayed on the master outdoor unit. Midea V8S Series Service Manual Trigger /recover condition Trigger:Two or more outdoor units in the combined system have the same address Recover condition: The…
-
2.9 C21: Communication error between IDU and ODU
Digital display output Table 6.2.1 Communication troubleshooting list: ODU interface PQE M1M2 PQE IDU interface PQE M1M2 PQE IDU type V8 V8 V6 Communication protocol n45-0, V8 protocol P Q communication n45-1, V6 protocol PQE communication n45-2, V8 HyperLink protocol IDU uniform power supplied…
-
Midea V8S Series Service Manual
2. Faults caused by other factors (1) All indoor units are not set address; (2) All indoor units are not powered on; (3) The communication wiring between the master unit and the first IDU is not reliably connected: The communication wiring between the ODU and the first IDU is not tightened, or the…
-
C21
Is the communication protocol correct? No Select the correct communication protocol for the specific ODU interface, IDU interface, and IDU type according to Table 6.2.1. In the table, "/" in the [Digital display output] indicates normal communication state; otherwise, correction is required…
-
2.10 C26 Abnormal reduction in the number of indoor units
Digital display output Midea V8S Series Service Manual Description The number of online indoor units is smaller than the configured number All units stop running. Error code is only displayed on the master unit Trigger / recover condition Trigger condition: N0: The number of IDU set by ODU…
-
C26
Is the IDU address code not set or duplicated. Yes Select one of the following solutions Solution 1: Reset the address. In menu n44, set to [0] (automatic addressing)[1]. Solution 2: Manually set the address of IDUs. After setting, ensure that the IDU addresses are not duplicated. No Power on all…
-
2.11 C28: Abnormal increase in the number of indoor units
Digital display output Midea V8S Series Service Manual Description The number of online indoor units is greater than the configured number All units stop running. Error code is only displayed on the master unit Trigger / recover condition Trigger condition: N0: The number of IDU…
-
2.12 xC31: Communication error between No.x slave outdoor unit and master outduoor unit
Digital display output Description The No.x outdoor slave unit cannot communicate with the outdoor master unit. Outdoor units that display the error code stop running. Error code is only displayed on the slave unit with the error. Possible causes The address of slave outdoor unit is…
-
2.13 C32: Abnormal reduction in the number of outdoor units
Digital display output Midea V8S Series Service Manual Description The number of online slave outdoor units detected by the master outdoor unit decreases All units stop running. Error code is only displayed on the master unit Trigger / recover condition Trigger condition:The…
-
2.14 C33: Abnormal increase in the number of outdoor units
Digital display output Part 6 - Diagnosis and Troubleshooting Description The number of online outdoor slave units detected by the outdoor master unit increases All units stop running. Error code is only displayed on the master unit Trigger / recover condition Trigger…
-
2.15 xC41: Communication Error between main control board and No.x inverter driver board
Digital display output Midea V8S Series Service Manual Description The communication between the main control board and No.x inverter driver board is error All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition…
-
C41
Measure the ODU main power L1/L2/L3. Is there phase loss or voltage failure? Yes Eliminate the problems with the power supply accordingly No Measure the input voltage L1/L2/L3 after module rectification. Is there phase loss or voltage failure? Is there circuit break, misphase, or poor contact with…
-
Digital display output Error code E41 F81 Error description Outdoor ambient temperature sensor (T4) error(open/short) Gas pipe temperature sensor (Tg) error (open/short) Remarks sensor error sensor error Outdoor heat exchanger liquid FC1 temperature sensor (TL) error sensor error (open/short)…
-
Description
Temperature sensor error All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition:The main control board cannot obtain the normal AD value of the temperature sensor Recover condition:The main control board obtain the normal AD…
-
2. F41/FA1
F41/FA1 Correctly connect T3/T8 sensor The sensor connection on main board is loose[1] Yes No The sensor is sho rt-circu ited or fails[2] No PCB is damaged[3] Yes Replace the sensor Automatic res toration in 5s? No Replace the main board For T8/T3 sensor, a set of wires are connected to the same…
-
4. xF71
1F71, 2F71 T7C sensors are not connected to the compressor top or T7C1 and T7C2 are connected reversely to the compressor Yes Connect T7C sensors correctly to the compressor top and fix them with spring clips. No Correctly connect T7C sensor Yes T7C sensor is not connected or is in poor contact[1]…
-
Digital display output Midea V8S Series Service Manual 106 Description The temperature of the Tf/Ntc radiator is too high. All units stop running Error code is displayed on the outdoor unit with the Error Trigger/ Recover condition Trigger condition: F62: The temperature of the…
-
F62, F6A
Yes Is the ODU check valve closed? No Open the ODU check valve and power on. Does the error display again? No Yes No Is the piping and wiring connected correctly? Correctly connect the piping and wiring, then power on. Does the error display again? No Yes Yes Yes Are the module board screws loose?…
-
2.18 F63: Non-inductive resistance Tr overtemperature protection
Digital display output Midea V8S Series Service Manual Description The temperature of the Tr non-inductive resistance NTC is too high. All units stop running Error code is displayed on the outdoor unit with the Error Trigger/ Recover condition Trigger condition: The non-inductive…
-
Digital display output 109 Part 6 - Diagnosis and Troubleshooting Description Discharge Temperature is over the limit. All outdoor Unit stop running Error code is displayed on the unit with the error Trigger / Recover condition Trigger condition: F72: Discharge Temperature…
-
Procdure
F72/F7A Yes Open the ODU check valve and power on. Does the error display again? Is the ODU check valve closed? No Is the piping and wiring connected correctly? Yes Correctly connect the piping and wiring, then power on. Does the error display again? No Is the temperature of the discharge…
-
2.20 F75: Compressor discharge insufficient superheat protection
Digital display output Description Superheat degree of compressor discharge temperature is too low, triggering protection shutdown Determination during operation of outdoor unit. All units stop running. The error code is displayed on the outdoor unit with error. Possible causes Piping and…
-
F75
Correctly connect the piping and wiring, then power on. Does the error display again? No Is the piping and wiring connected correctly? Yes Yes Figure I Do any of the following conditions occur? 1. T7C sensors are not connected to the compressor top 2. T7C1 and T7C2 are connected reversely to the…
-
2.21 P11: High pressure sensor error
Digital display output Part 6 - Diagnosis and Troubleshooting Description Open/short circuit error of high pressure sensor All units stop running. The error code is displayed on the Outdoor Unit with error. Trigger / recover condition Trigger condition: The high pressure sensor is…
-
2.22 P12/P14: High pressure protection
Digital display output Midea V8S Series Service Manual 114 Description P12: The high pressure is over the limit. P14: 3 times P12 in 100 minutes All units stop running Error code is displayed on the unit with the Error Trigger / recover condition Trigger condition: P12: Phigh…
-
P12
Enter the MENU vacuum mode (n15) after power off. Wait for 1min. Are the HP and LP pressures close, and troubleshooting? No Yes If the HP pressure is too high, preferably check the following items. 1. Is the ODU check valve fully opened? 2. Is the piping and wiring connected correctly? 3. Are coils…
-
2.23 P13: High pressure switch protection
Digital display output Description All units stop running Error code is displayed on the unit with the Error Trigger / recover condition Trigger condition: discharge pressure≥ 4.1MPa or the switch is open-circuited. Recover condition: pressure switch is closed. Reset method: Resume automatically.…
-
2.24 P21: Low pressure sensor error
Digital display output Description Open/short circuit Error in suction pressure sensor All units stop running. Error code is only displayed on the unit with the error. Trigger / recover condition Part 6 - Diagnosis and Troubleshooting Trigger condition: PLow Pressure<0.02MPa or PLow…
-
2.25 P22/P25: Low pressure protection
Digital display output Midea V8S Series Service Manual Description P22: Low pressure protection; P25: Low pressure protection occurs 3 times in 60 min. All units stop running. Error code is displayed on the unit with the error. Trigger/ Recover condition Trigger condition: P22: suction…
-
P22/P25
Enter the MENU vacuum mode (n15) after power off. Wait for 1min. Are the HP and LP pressures close, and troubleshooting? No Yes If the LP pressure is too low, preferably check the following items. 1. Is the ODU check valve fully opened? 2. Is the piping and wiring connected correctly? 3. Are coils…
-
2.26 P24: Low Pressure too High Protection
Digital display output Midea V8S Series Service Manual 120 Description All units stop running. ODU fault is determined based on the sensor. Error code is displayed on the unit with the error Trigger/ Recover condition Trigger condition: Suction pressure >1.6MPa and lasts 60 minutes…
-
P24
Is the pressure of the detection valve during s teady operation 1.6 MPa? [1] No No The main board is damaged. Rep lace it Is the main board pressure normal? [3] Yes Yes There may be 3 co nditio ns for the sys tem: 1. The ODU operates out of the operating temperature range in cooling mode [2] 2. The…
-
2.27 P31: Primary Side Overcurrent Protection
Digital display output Midea V8S Series Service Manual Description The AC current at the device primary side is too high, which triggers protective shutdown. The current is transmitted by the module to the main control board. All units stop running Error code is displayed on the…
-
Digital display output Description The DC bus current of No.x compressor is too high, triggering protection shutdown All units stop running. Error code is displayed on the unit with the error. Part 6 - Diagnosis and Troubleshooting Trigger / recover condition Trigger condition: P32…
-
XP32,XP33
Yes Open ODU stop valve ODU stop valve is closed? No Yes compressor cable is damaged Replacing the compressor Cable No Yes The resistance of the compressor wiring terminals to the ground is less than 1 MΩ The compressor is damaged. Replace the compressor No Midea V8S Series Service Manual Measure…
-
2.29 P51: High AC voltage protection
Digital display output Description The AC voltage of the system is too high, triggering the protection shutdown All units stop running Error code is displayed on the unit with the error. Trigger / recover condition Trigger condition:The AC voltage of Outdoor Unit over 265 V Recover…
-
2.30 P52: Low voltage protection
Digital display output Midea V8S Series Service Manual Description The AC voltage of the system is too low, triggering the protection shutdown All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition:The Vac of…
-
2.31 P53: Phase B and N of the power cable are connected to the opposite protection
Digital display output Description System phase and neutral wires are connected reversely and fail the inspection All units stop running Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: The drive board uploads L35 fault Recover condition…
-
2.32 P54: DC bus low voltage protection
Midea V8S Series Service Manual Digital display output Description The DC bus voltage of the compressor is too low All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: The drive board uploads XL3E fault Recover condition…
-
2.33 P55: DC bus ripple over protection
Digital display output P55 Measure the AC voltage between module input power supplies L 1 and L2, L1 and L3, and L2 and L3. Is it within ±10% of the rat ed volt age[1]? Is there phase-lack or misphase? Yes Correct the power suppl y No Replace the drive board Note: [1] When the system is…
-
Midea V8S Series Service Manual Digital display output Description No.x inverter driver board DC bus voltage is too low All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: The inverter driver board upload L3E/J3E fails …
-
Digital display output Part 6 - Diagnosis and Troubleshooting Description No.x inverter driver board DC bus voltage is too high All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: The inverter driver board upload L31/J31…
-
2.36 xP58: No.x inverter driver board DC bus voltage is seriously too high
Midea V8S Series Service Manual Digital display output Description No.x inverter driver board DC bus voltage is seriously too high All units stop running Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: The inverter driver board upload L32/J32…
-
Digital display output Part 6 - Diagnosis and Troubleshooting Description The phase and neutral wires are connected reversely and fail the inspection. All units stop running Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: phase and neutral…
-
Digital display output Description The EEPROM parameter of the ODU main control board is incorrect All units stop running. Error code is displayed on the unit with the error Midea V8S Series Service Manual Trigger / recover condition Trigger condition:EEPROM parameter verification is…
-
2.39 Pb1: HyperLink overcurrent error
Digital display output Pb1 Check the communication wiring of the system. Is there short circuiting of M1/M2 wiring? Yes Correct the wiring and eliminate the short circuit No Connect the communication wiring of ODU to the M1/M2 port and the communication wiring of IDUs to the P/Q port…
-
2.40 Pd1, Pd2: Anti-condensation protection
Digital display output Midea V8S Series Service Manual 136 Description Anti-condensation protection All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: Pd1: Liquid pipe inlet temperature (T5) remains…
-
Pd1/Pd2
Check the following aspects first: 1. EEVC terminal is correctly connected to the main board and the EEVC is correctly connected to the coil [1] 2. The temperature of T6A/T6B/T5 is consistent when spot check in ODU power-off condition. Is all of the above correct? No Connect the EEVC or sensor…
-
2.41 U11: Outdoor unit model is not set
Digital display output Description The outdoor unit model is not set into the main board. All units stop running Error code is displayed on the unit with the error Midea V8S Series Service Manual Trigger / recover condition Trigger condition: The model information is not set. Recover…
-
2.42 U12: Outdoor unit Capacity setting error
Digital display output Description The capability information of outdoor unit is not set All units stop running Error code is displayed on the unit with the Error Trigger / recover condition Trigger condition: The capability information of outdoor unit is not set Recover condition: Reset…
-
2.43 U21: The indoor unit connection is incorrect
Digital display output Midea V8S Series Service Manual Description Connected to the 1st generation indoor unit or indoor unit address repeated in system All Outdoor units stop running Error code is displayed on the master unit Trigger / recover condition Trigger condition: • 1st…
-
2.44 U31: The test run was never successful
Digital display output Description The system is not in the test run or the test run is unsuccessful All units stop running Error code is only displayed on the master unit. Part 6 - Diagnosis and Troubleshooting Trigger / Recover condition Trigger condition: • The system is not in the test…
-
2.45 U32, U33, U34: The temperature is not suitable for test run
Digital display output Description During the test run, the indoor or outdoor temperature exceeds the operating range All units stop running Error code is only displayed on outdoor unit Trigger /Recover condition Trigger condition: After entering into test run, the master unit estimates…
-
Digital display output Description The outdoor unit stop valve is not opened during the test run. All units stop running Error code is only displayed on the master unit. Trigger/ Recover condition Trigger condition: Error code Description U35 The liquid side stop valve of the Discharge…
-
2. U37
U37 Are all ODU check valves opened? Yes Are piping and wiring signals of the system consistent? Yes Yes Is the Indoor unit faulty? No Open all stop valves No No Unify the piping and wiring signals Clear indoor unit faults according to the indoor unit error guidelines. Midea V8S Series Service…
-
2.47 U38: Outdoor Unit has no address
Digital display output U38 Set the address of each ODU in menu "n40", 0 for the master unit and 1/2/3 for slave unit respectively. ODU addresses of the same refrigerant system shall not be repeated Troubleshooting Notes: [1]After setting the outdoor unit address, waiting for 30 seconds…
-
2.48 U3A: The communication wiring is connected incorrectly
Digital display output Description Indoor unit piping and communication wiring are not connected in the same system. All units stop running Error code only displayed on the master unit. Midea V8S Series Service Manual Trigger / Recover condition Trigger condition: Indoor unit piping and…
-
Digital display output U3b The ODU temperature detected by T4 during the test run is higher than 10°C Check whether the air inlet and outlet of the ODU heat exchanger is blocked Yes Take corrective measures according to the <Installation and Operation Manual>[1]. No Check whether T4…
-
2.50 U3C: Changeover mode error
Digital display output Midea V8S Series Service Manual Description ODU in changeover mode doesn’t set the VIP IDU address. ODUs stop running Error code only displayed on the master unit. Trigger / Recover condition Trigger condition: Outdoor unit in changeover mode, but the VIP…
-
Digital display output Description Combination ratio of indoor unit and outdoor unit is out of range All units stop running Error code only displayed on the master unit Trigger / Recover condition Trigger condition: 1) 2) Part 6 - Diagnosis and Troubleshooting Error code Description U41 The…
-
Reset method: Resume manually
Possible causes Indoor units and outdoor units combination ratio is out of range. Outdoor unit address is repeated or the slave outdoor unit does not have an address. Individual series indoor unit is installed in combination with a combinable series. Procedure 1. U41 Midea V8S Series Service…
-
3. U43
U43 Yes Are all IDU s of the sys tem AHU KIT (air discharge co ntrol) IDUs? Calculate the combination ratio (A) of AHU KIT (air discharge control) IDUs: A = Total HP of FAPU s/Total HP of ODUs * 100% N o Calcu late th e comb in ation ratio (B) of FAPUs + AHU KIT (air discharge control) IDUs: B =…
-
5. U48
U48 Cal cul ate the combinat ion rat io (A) of all IDUs in the sy stem: A = Tot al HP of all IDUs in the sy stem/Tot al HP of ODUs * 100% Does the combination ratio (A) falls between 50% A 130%? No Midea V8S Series Service Manual Adjust the capacity of IDUs to ensure the combination rat io A falls…
-
2.52 U51: More than One Outdoor Unit Models in the Individual Series System
Digital display output Description Outdoor unit of Individual Series is installed in combine system, and the number of ODUs detected is greater than 1. All units stop running Error code is only displayed on master unit. Trigger / Recover condition Trigger condition: The number of ODUs…
-
2.53 U53: Two or More Outdoor Unit Models in the Combined System
Digital display output Description Detected different series outdoor units in the combined system All units stop running Error code is only displayed master unit Midea V8S Series Service Manual Trigger / Recover condition Trigger condition: Detected different series outdoor units in the…
-
3 Error in Compressor Driver
3.1 xL1E: Hardware overcurrent Digital display output XL1E Shut the unit down to check whether the compressor wiring is reversely or loosely connected Yes Adjust compressor wiring No Shut the unit downt and use a multimeter to measure the resistance to ground of the compressor winding. Is it less…
-
Digital display output Midea V8S Series Service Manual Description The compressor current exceeds the protection value set by the software. The compressor will shutdowm when the error occurs. If the error disappears one minute later, the compressor will start again. Trigger / recover…
-
3.3 xL2E: Module overtemperature protection
Digital display output XL2E Shut the unit down to check if the check valve is opened No Open the check valve Yes Shut the device down to ch eck whether th e s crews of IPM are tigh tened and the thermally conductive silicone grease is properly applied No Fix th e IP M screw again or apply…
-
Digital display output Midea V8S Series Service Manual Description xL1*/xL2* fault occurs 10 times in 1 h. Possible Cause Spot check to inquire about the code. Find out the cause by the error code. Procedure Spot check to inquire about the error code. Refer to the process for the error code.…
-
3.5 xL3E: The bus voltage is too low
Digital display output XL3E fault Power off and measure the power module, including the fan module. Is it damaged?[1] Yes Replace the compressor drive board or fan drive board No Power on and measure bus voltage, which should be within the range of 350-800VDC[1], but is lower than 350VDC…
-
3.6 xL31: The bus voltage is too high
Digital display output Midea V8S Series Service Manual Description Bus voltage is higher than the high bus voltage protection threshold set by the software (800VDC). The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts…
-
3.7 xL32: The bus voltage is excessively high
Digital display output XL32 Measure the AC voltage between module input power supplies L1 and L2, L1 and L3, and L2 and L3 No Is the voltage range of power supply within ±10% of the rated voltage? Adjust the power supply (incorrect power load) Yes Is the unbalanced phase-to-phase voltage…
-
3.8 xL43: The current sampling bias is abnormal
Digital display output Description The drive board is faulty upon the power-on self test. Once this fault occurs, the compressor cannot be started up, and the drive board must be checked. Trigger / recover condition Trigger condition: The drive board fails the power-on self test. Midea V8S…
-
3.9 XL45: Motor Code Mismatch
Digital display output XL45 Yes Spot-check the outdoor unit capacity, which should match the barcode on the outdoor unit No Reset the capacity code Yes Yes Is there any fault in the setting of the drive plate DIP switch S7? Adjust the DIP switch on the drive board No Replace the drive…
-
Digital display output Midea V8S Series Service Manual Description IPM has overcurrent or IPM has drive undervoltage. The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts again. Trigger / recover condition Trigger…
-
3.11 XL47: Module type mismatch
Digital display output XL47 Yes No Spot-check the unit capacity, which should match the barcode on the outdoor unit Reset the capacity code Yes Is there any fault in the setting of the drive board DIP switch S7? Yes Adjust the DIP switch of the drive module board Yes Replace it with a drive…
-
Digital display output Midea V8S Series Service Manual Description The compressor fails to start The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts again. Trigger / recover condition Trigger condition:The compressor…
-
3.13 xL52: Locked-rotor protection
Digital display output XL5E No Is the check valve opened? Open the check valve No Is the high-low pressure difference greater than 0.2 MPaf upon startup? Yes System is unbalanced. Check the refrigerant system No Shut the unit down and check the drive board[1] Yes The power board is…
-
3.14 xL6E: Compressor motor lack of phase protection
Digital display output Midea V8S Series Service Manual 168 Description The high pressure switch (CN21) connected to the drive board acts. When the fault occurs, the compressor stops operation. If the fault disappears in 1 min, the compressor is started up again. Trigger / recover…
-
4 Error in Fan Drive
4.1 xJ1E: Hardware overcurrent Digital display output XJ1E Check fan install ation. Is the fan blocked or locked? Yes Adjust installat ion or replace the fan No Check the fan connection plug (CN3). Is it l oose? Yes Adjust connection wiring No Shut the unit down and use a multimeter to measure the…
-
Digital display output Midea V8S Series Service Manual Description The fan current exceeds the protection value set for the software. The fan will stop when the error occurs. If the error disappears five seconds later, the fan will start again. Trigger / recover condition Trigger…
-
4.3 xJ2E: Module overtemperature protection
Digital display output XJ2E No Shut the unit down to check if the check val ve i s opened Open the check v alve Yes No Are t he screws tightened, and i s thermally conducti ve sili cone grease properly applied? Reapply t he silicone grease and tighten the module screws Yes Yes Power on again…
-
Digital display output Midea V8S Series Service Manual Description xJ1*/xJ2* fault occurs 10 times in 1 h. Possible Cause Spot check to inquire about the code. Find out the cause by the error code. Procedure Spot check to inquire about the error code. Refer to the process for the error code.…
-
4.5 xJ3E: The bus voltage is too low
Digital display output Part 6 - Diagnosis and Troubleshooting Description Bus voltage is lower than the low bus voltage protection threshold set by the software (350VDC). The fan stops running after the error occurs. If the error disappears five seconds later, the fan starts again. Trigger /…
-
4.6 xJ31: The bus voltage is too high
Digital display output Description Bus voltage is higher than the high bus voltage protection threshold set by the software (750VDC). The fan stops running after the error occurs. If the error disappears five seconds later, the fan starts again. Midea V8S Series Service Manual Trigger / recover…
-
4.7 xJ32: The bus voltage is excessively high
Digital display output Description Bus voltage is higher than the high bus voltage protection threshold set by the software (770VDC). The fan stops running after the error occurs. If the error disappears five seconds later, the fan starts again. Trigger / recover condition Trigger condition…
-
4.8 xJ43: The current sampling bias is abnormal
Digital display output Description The detection circuit of the drive board fails the power-on self test. After this error occurs, the fan cannot start. Check whether the inverter driver board is in error. Trigger / recover condition Trigger condition: The drive board fails the power-on self…
-
4.9 xJ45: Motor Code Mismatch
Digital display output 177 Part 6 - Diagnosis and Troubleshooting Description The compressor parameters set by the main control board do not match the compressor parameters of the drive board. Once this fault occurs, the fan cannot be started up, and the drive board must be checked. Trigger /…
-
4.10 XL47: Module Type Mismatch
Midea V8S Series Service Manual Digital display output Description The fan parameters set by the main control board do not match the fan parameters, the driver board specifications set by the main control board do not match the fan specifications of the drive board. Trigger / recover condition …
-
Digital display output XJ5E fault Yes Is the fan blocked or locked, or incorrectly assembled? Replace the fan and adjust assembly No Shut the unit down and use a multimeter to measure the fan winding. Is it open-circuited? Yes Replace the fan No Shut the unit down and check the drive…
-
4.12 xJ52: Locked-rotor protection
Digital display output Midea V8S Series Service Manual Description The fan is blocked. The fan stops running after the error. If the error disappears after five seconds, the fan starts again. Trigger / recover condition Trigger condition: The fan is blocked. Recover condition: The…
-
Digital display output Part 6 - Diagnosis and Troubleshooting Description The fan has phase loss protection. The fan stops running after the error. If the error disappears after five seconds, the fan starts again Trigger / recover condition Trigger condition: The fan has phase loss…
-
4.14 xJ65: Fan IPM Short Circuit Protection
Digital display output Midea V8S Series Service Manual Description The fan is in IPM short circuit protection. The fan stops running after the error. If the error disappears after five seconds, the fan starts again Trigger / recover condition Trigger condition: The fan is in IPM…
-
5 Appendix
5.1 Resistance characteristics of temperature sensor Table 6-5.1: Temperature probe symbol and position Temperature probe symbol and position The probe type Bottom of heat exchanger Type A T4 Outdoor ambient temperature Type A T5 Liquid pipe stop valve Type A T6A Microchannel heat exchanger inlet…
-
Midea V8S Series Service Manual
-
temperature
resistance (kΩ) Type A Type B Type C 44 4.387 24.85 24.85 45 4.213 23.89 23.9 46 4.046 22.89 22.98 47 3.887 22.1 22.1 48 3.735 21.26 21.26 49 3.59 20.46 20.47 50 3.451 19.69 19.7 51 3.318 18.96 18.97 52 3.192 18.26 18.26 53 3.071 17.58 17.59 54 2.959 16.94 16.94 55 2.844 16.32 16.32 56 2.738 15.73…
-
Midea V8S Series Service Manual
-
temperature
resistance (kΩ) (°C) Type A 130 0.2777 131 0.2708 132 0.2641 133 0.2576 134 0.2513 135 0.2451 Type B Type C 1.632 Part 6 - Diagnosis and Troubleshooting 187
-
5.2 Normal status parameter of refrigerant system
The parameters listed in Tables 6.5.3 and 6.5.4 need to be noted when the following conditions are met: The master can detect all indoor machines: The number of indoor units displayed for outdoor units is consistent with the actual installation. All stop valves have been opened and all indoor…
-
5.3 Analysis of the cause of system anomalies
Cause Analysis of Excessive discharge Temperature failure of SV7 coil Check whether coil is not properly installed failure of SV7 body Control failure of SV7 Control failure of mainboard failure of EEVC coil failure of EEVC Check whether coil is normal failure of SV7 body Control failure of EEVC…
-
Cause Analysis of too high Pressure
Stop valve is closed The resistance of the high-pressure side pipe is too large Piping is bent or severely deformed The pipe is blocked. *Cooling mode Control failure of EEV coil Control failure of ODU EEV Check whether coil is normal Failure of High pressure sensor whether sensor is not properly…
-
Cause Analysis of too Low Pressure
*cooling mode Control failure of suction pressure Whether there is a big difference between the actual low pressure and the spot low pressure Check whether the power supply of the mainboard is abnormal Whether there is a big difference between the actual low pressure and the spot low pressure…
-
5.4 Inverter drive board measurement guidelines
Midea V8S Series Service Manual Please give priority to the following things before testing Inverter drive board: 1) Cut off the power supply: 2) To avoid electric shock from capacitor discharge, power off for 10 minutes and wait for capacitor discharge before operation: 3) Remove all wiring on the…
-
Schematic diagram of measuring points of Inverter drive board
Part 6 - Diagnosis and Troubleshooting 193
-
5.5 Appendix of Pressure Sensor Detection
Pressure sensor characteristics 5.00 High Pressure sensor PH Low Pressure sensor PL 4.50 y = 2x + 0.5 y = 0.87x + 0.5 output voltage(V) 4.00 3.50 3.00 2.50 2.00 1.50 Midea V8S Series Service Manual 1.00 0.50 0.00 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 Pressure(MPa) PH :Vout(H)=0.87×PH+0.5…
-
5.6 Refrigerant volume diagnosis
When running the refrigerant quantity detection program, the machine calculates the system refrigerant quantity according to the ambient temperature, condensing temperature and evaporation temperature, heat exchanger inlet and outlet temperature and other parameters, and give hints according to the…
-
Start
Confirm whether the following two points meet the requirements: 1. Whether all IDUs in the system are V8 series? 2. Does the system choose V8 communication protocol or HyperLink? Whether the above two points are consistent No The detection results of the system have V6 IDUs may have a large…
-
5.7 Oil volume table
-
S-V8S
Ver. 2024-3 Midea Building Technologies Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 mbt.midea.com / global.midea.com/ ics.midea.com Note: Midea reserves the right to change the specifications of the product, and to…