MDV 2 nd Generation ALL IN ONE Type
Heat Pump Water Heater Technical Manual Applicable Models: RSJ-35/300RDN3-B 1
-
MDV reserves the right to discontinue, or change at any time, specifications or designs without notices and without incurring obligations. 2
-
1. Measurements
-
3. Nomenclature
Household Water Heating Unit - 12 Design code Refrigerant code Water supply pump lift code Other functions code Power supply specification code Heating mode code Water tank volume, unit: L Rated hot water output, unit: 100 W Installation type code Water heating unit code Export model code 1 - 2 3…
-
4. Features
4.1 Safety a. Complete isolation between water and electricity. No electric shock problem, more safety. b. No fuel tubes and storage, no potential danger from oil leakage, fire, explosion etc. c. No cross contamination potential, the condenser coil wrapped around the stainless steel inner tank 4.2…
-
4.5 Automatic Control
Automatic start-up and shutdown, automatic defrosting by revising refrigerant cycle. Save you much extra operation. 4.6 High Efficiency and Energy Saving. The unit adopts heat pump principle, which absorbs heat from outdoor air and produce heat water, thermal efficiency can be approximately 3.6…
-
1. Specifications
Model RSJ-35/300RDN3-B Economy Running Models Running Ambient temp. Power supply Storage size Capacity Input Cop Rated current Water Heating Nonimal ℃ ph-V-Hz Ltr KW KW W/W A Testing Condition Max. Input Max. Current KW A Testing Condition Max. Input Max. current Starting current Model Type Brand…
-
mm
mm kg Kg Auto/Manual start up, Energy-saving, standard, Enhanced heating type heating water High-pressure protection, Over-load protection, Temp protection, Electric leakage protection Φ650×1920 745*2030*775 113/129 R134a/1.2 MPa 3.0/1.2 Mpa 0.15/0.7 polyurethane/55mm -30~43 DN20 DN20 DN20 DN20…
-
2. Operation range
Mode explanation: there are 3 operation MODE: ECONOMY, HYBRID and E-HEATER ECONOMY MODE: Water firstly is heated by compressor, if can’t get target temp when ambient temp. too low or too high (limitation figure is shown above), element will start as a secondary heat resource. Hybrid mode: In case of…
-
ECONOMY MODE
Hybrid mode: 14
-
E-HEATER MODE
-
3. Capacity & COP table
5000 5.5 4500 5 4000 4.5 Capa. (W) COP (W/W) 4 3500 3.5 3000 3 2500 2.5 2000 2 1500 1.5 1000 1 0.5 500 -7 -2 Ambient temp(℃) Remark: Water inlet temp. 15℃, Water outlet temp. 45℃ 16
-
4. Dimensions
-
5. Service Space
6. Wiring Diagrams manometer (High Pressure Switch) Discharge temp sensor ass'y (Tp) room temp sensor ass'y (T4) 1 202301800820 1 202301300130 1 202301300196 18
-
202301300437 1 202301300303 1 202301300485 1 202301300486 2 202300800003 TCO(turn off temp. 85±3°C,manually recovery) 1 202301610028 TOD Auto Recovery, turn off temp.78±3°C,Recovery temp 68±3°C 1 202301600046 Temp.sensor ass'y (T3) Temperature sensor (Th) senor ass'y, for the pipe (T5L) senor ass'y…
-
7. Piping Diagrams
-
8. Duct connection
A: Air inlet & outlet without canvas B: Only air outlet with canvas, A≤10m When there is stable heat source in room in winter C: Air inlet & outlet with canvas, A+B≤10m D: Only air inlet with canvas A≤10m Charge fresh air from ambient in summer 21
-
9. Exploded View
-
No
Part Name Quantity 14.1 14.2 airout ring air filter filter plastic hourse top magnesium stick plug cover, wire-connceting box asynchronism motor Display board Display board ass'y centrifugal fan cover, display electric control box forming forming plug Froth plug TCO(turn off temp. 85±3°C, manually…
-
16.1 16.2 16.3 16.4 16.5 16.6 16.7 17 electric control board ass'y electric control board jointing Compressor capacitor main control board ass'y transformer for power supply Motor capacitor Wire joint Relay of Elment & Compressor holder for electric control board ass'y 1 34.2 Wire joint, 3p front…
-
1. Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause harm or damage. The safety precautions listed here are divided into two categories. In either case, important safety…
-
It’s normal if some water drips from the hole of PT valve in operation. But, if the water is in a great amount, call your supplier for instructions. ■ After a long use, check the unit stand and fittings. If damaged, the unit may fall and result in injury. ■ Arrange the drain hose to ensure smooth…
-
The unit must be securely fixed, or else, noise and shaking will be resulted. ■ Make sure that there’s no remora around the unit. ■ In the place where there is strong wind like seashore, fix the unit in the location protected from the wind. ■ Carry the unit onto the site 1) In order to avoid scratch…
-
4. Accessories
Check whether the following assemblies are complete. Quantity Note Installation& Operation Manual Name 1 Installation and Operation instruction Y-sharp Filter 1 Inlet water filter Drain Pipe for Condensate water 2 For condensed water discharge use One Way Valve 1 To prevent water from flowing back…
-
6.3 Power Supply Wiring
A. Power Supply Schematic Diagram Manual Switch Water Heating Unit Power supply Earthing Creepage Breaker Warming: Although there is a leakage protector in the electric control box of the unit, for the security reason, it is required that a leakage protection equipped cable and Earthing should be…
-
1. Confirmation Before the Trial Operation
1.1 All the installation is complete. 1.2 Water heater is installed correctly. 1.3 The pipelines and wiring are correct. 1.4 The accessories are installed correctly. 1.5 The drainage is smooth. 1.6 The thermal insulation is sound. 1.7 The earthing wire is connected correctly. 1.8 The power voltage…
-
2.1.2 After powered on, the display lights up. Users can operate the unit through the buttons under the display for different modes. Emptying: If the unit needs cleaning, moving etc, the tank should be emptied. Method: See Figure 2.1.2 Close the cool water inlet, open the hot water outlet and open…
-
2.2.2 Display Explanation
TEMP-SET 16 HIGH TEMP 15 5 ECONOMY MODE FILL WATER ALARM LOCK HYBRID MODE OUTLET TEMP E-HEATER MODE 13 TIME ON TIME OFF TIMER CONFLICT 10 9 Number Explanation Number Explanation 1 HIGH TEMP indicator. When the setting temp. exceeds 50℃, it lights up to remind you that the outlet temp. is too high…
-
2.2.4 Operation Instruction
2.2.4.1 Preparation before running the unit. a) When you run the unit for the first time, all the indicators on the UI will light for 3 second, and the buzzer will “didi” ring twice at the same time, and then, display the fiducially web page. After no operation for 1 minute, all indicators will go…
-
Press the CLOCK key, the minute digit of
the clock on the display starts flashing slowly. Press the “UP” and “DOWN” key, you can adjust the minute. Press the “UP” and “DOWN” key, you can adjust the hour. Press the CLOCK key again, the minute digit stops flashing while the hour digit starts. Stop operation for about 10s, flashing will stop…
-
2.2.4.4 Mode Selection
a) The unit is enhanced with three operation modes, Economy Mode, Hybrid Mode and E-heater Mode. b) Economy Mode: The unit heats water only by compressor drive according to heat-pump principle. Used when the ambient temp. is high. c) Hybrid Mode: The unit heats water not only by compressor drive but…
-
2.2.4.6 TIMER
User can set up a running start time and a stop time on a specifically by the timer function. The least numbers of timer is ten minutes.Time on: User can set up a start time by this. The unit will auto run one time between the set time and 24:00 on the same day. Method for set. Press the TIMER ON…
-
Method for set
Press the TIMER ON key, the minute digit of the clock on the display starts flashing slowly Press the UP and DOWN key,you can adjust the minute setting. Press the UP and DOWN key,you can adjust the hour setting. Press the TIMER ON key again, the minute digit stops flashing and hour digit starts to…
-
CANCEL
In the unlocked status, press the CANCEL key for 1s, the TIMER ON and TIMER OFF fuction will be canceled. NOTE: 1) TIMER ON and TIMER OFF can not be set to the same time. If they are the same, the stop time will delay 10 minutes automatically. For example,Time on and Time off set to 1:00 at the same…
-
The light will flash with Alarm
Press CANCEL key to stop the buzzer. ALARM The system will display the error code and the water tempera-ture alternatively on the display in error. The water temperature and error code will display alternatively OUTLET T 41
-
When error happens, though the system could be used in some circumstances, it could not reach the
expected efficiency. Please contact your supplier for help. Error Code Explanation (See table below table) Display Malfunction Description Display Malfunction Description E0 Error of sensor T5U P1 System high pressure protection ≥3.0MPa active; ≤2.4Mpa inactive E1 Error of sensor T5L P2 High…
-
2.3 Running and Operating
2.3.1 Trial Running 1) Before running, please check the following items first: 2) Correct installation of the system; 3) Correct connection of pipeline and wiring; 4) Leakage of the refrigerant pipeline tested; 5) Efficient drainpipe; 6) Complete insulation protection; 7) Correct earthing; 8)…
-
(If Comp. restart frequently, which can only run within 10 min. for each start cycle, system will count accumulated running time, when accumulated running time reaches 40min, defrosting cycle will activate 2 min. after Compressor’s next start Conditions to inactivate defrosting cycle (when achieve…
-
b)
The 6 indicators beside the water temperature on the display are the lower part water temperature. When the temperature is 15℃ lower than the set temperature, the blue one will light up; when 10℃ lower, the blue and yellow ones light up; when 5℃ lower, the blue, yellow and red ones light up and when…
-
nd Generation ALL IN ONE Type Heat Pump Water Heater Technical Manual 3. PCB explanation Remote On/Off 2.5 PCB I/O Ports description Response High electrical level means HPWH ON signal Low electrical means HP OFF signal level Remote On/OFF input from Solar pre-warming system low electrical level…
-
MCAC-R
2 nd Generation ALL IN ONE Type Heat Pump Water Heater Technical Manual Wiring explanation 49
-
3.2 SW2/SW3 SETTING
3.3 Self-checking function How to get in self-checking function? Press 2 buttons together: “Cancel” + “Clock” Hour Min. Min. Ts Ts Tank Tank No Low High Low High Low Temp. Temp. . Low High bit bit bit bit bit 50 Explanation
-
bit
bit 0 Temp. valve T5L 1 Temp. valve T5U 2 Temp. valve T4 3 Temp. valve T3 4 Temp. valve Tp 5 Temp. valve Th 6 X X Current valve Opening degree 7 XX: COPM; Lower Element Upper Element; EEV opening degree, 8 times to real value 8 X Running mode:: Economy, E-heater, Close 9 X Fan speed: Low 10 X Model:…
-
3.1.4 Check the sacrificial anode every half year and change it if it has been used out. For more details, please contact the supplier or the after-sale service. 3.1.5 It is recommended to set a lower temperature to decrease the heat release, prevent scale and save energy if the outlet water is…
-
5 Malfunctions and Resolutions
Malfunction Cause Resolutions Outlet water Bad connection of power supply Reconnect the plug; is cold. plug and socket; Set outlet water an a The display Outlet water is set an a low higher temperature; is dark. temperature; Contact the technician. Outlet water temperature controller is damaged…
-
Appendix 1 Temp.—Resistance Table of TP Sensor