Инструкция на Модели: MDVO-VCM224V2R1A…MDVO-VCM850V2R1A. Сервисное руководство: общая информация, компоновка и холодильный контур, управление, настройки, электрические компоненты и схемы, диагностика и коды ошибок,
Модели: MDVO-VCM224V2R1A…MDVO-VCM850V2R1A. Сервисное руководство: общая информация, компоновка и холодильный контур, управление, настройки, электрические компоненты и схемы, диагностика и коды ошибок, поиск неисправностей. Документ на английском языке.
Смотрите также: Руководство по установке и эксплуатации →
Загружаем документ…
Текст инструкции
-
R410A
-
CONTENTS
Part 1 General Information 3 Part 2 Component Layout and Refrigerant Circuits 19 Part 3 Control 33 Part 4 Field Settings 50 Part 5 Electrical Components and Wiring Diagrams 62 Part 6 Diagnosis and Troubleshooting 77 1
-
Мм
-
Part 1
General Information 1 Indoor and Outdoor Unit Capacities 2 External Appearance 3 Outdoor Unit Combinations 4 Nomenclature 5 Combination Ratio 12 6 Selection Procedure Part 1 - General Information 14 3
-
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units 1.1.1 Standard indoor units Table 1-1.1: Standard indoor unit abbreviation codes Abbreviation Type code C1 One-way Cassette Type High Static Pressure Duct C2 Two-way Cassette WM Wall-mounted C4C Compact Four-way Cassette CF Ceiling & Floor C4 Four-way Cassette FS Floor Standing…
-
1.2 Heat recovery ventilator
-
2 External Appearance
2.1 Indoor Units 2.1.1 Standard indoor units MDV VC MAX Series Service Manual Table 1-2.1: Standard indoor unit appearance One-way Cassette Two-way Cassette C1 C2 Compact Four-way Cassette Four-way Cassette C4C C4 Arc Duct Medium Static Pressure Duct D1 D2 High Static Pressure Duct Floor Standing D3…
-
2.3 Outdoor Units
2.3.1 Single units Table 1-2.4: Single outdoor unit appearance 8/10/12/14/16/18/20HP (with single fan) 22/24/26/28/30HP (with dual fans) 2.3.2 Combinations of units Table 1-2.5: Combination outdoor unit appearance 40/42/44/46/48/50HP 52/54/56/58/60HP 62/64/66/68HP 70/72/74/76/78/80HP…
-
3 Outdoor Unit Combinations
Table 1-3.1: Outdoor unit combinations Modules1 MDV VC MAX Series Service Manual System capacity kW HP 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 73.0 78.5 85.0 90.0 96.0 101.0 106.0 112.0 117.0 123.0 130.0 135.0 141.0 146.5 152.0 158.0 163.5 170.0 175.0 181.0 186.0 191.0 197.0 202.0 208.0 215.0…
-
4 Nomenclature
4.1 Indoor Units 4.1.1 Standard indoor units VC MAX indoor units MDV I 3 - 18 D1 V D 7 1 ○ 2 ○ ○ 6 ○ ○ ○ ○ Legend No. Code Remarks 1 MDV MDV 2 I VRF indoor unit 3 3 V8 genera�on with Hyperlink 4 H Capacity index (the capacity in kW multiplied by 10) Indoor unit type C1: One-way Casse�e Part 1…
-
DC Indoor Units
-
4.1.2 Fresh air processing unit
MDV I3 200 OA V R12 D 1 ○ ○ ○ ○ ○ ○ ○ Legend No. Code Remarks 1 MDV MDV 2 I3 V8 VRF indoor unit 3 22 Capacity index (the capacity in kW mul�plied by 10) 4 OA Indoor unit type OA: Fresh Air Processing Unit OAS: Small Air Flow Fresh Air Processing Unit 5 V DC fan motor 6 R12 Refrigerant type (R12…
-
4.2 Outdoor Units
MDV O - VCM 252 V2 R1 A ① 2 3 ○ ○ ○ ○ ○ ○ Legend No. Code Remarks 1 MDV MDV 7 O Outdoor unit 3 VCM VC MAX VRF 4 252 Capacity index (the capacity in kW multiplied by 10) 5 V2 Type (V2: All DC inverter) 6 R1 Refrigerant type (R1: R410A) 7 A Power supply D, E: 1 phase,220-240V, 50Hz MDV VC MAX Series…
-
Sum of capacity indexes of connected indoor
-
6 Selection Procedure
6.1 Procedure Step 1: Establish design conditions Design temperature and humidity (indoor and outdoor) Required heat load of each room System peak load Piping length, level differences Indoor unit specifications (type and quantity) Step 2: Select indoor units Decide indoor unit safety factor MDV VC…
-
6.2 Example
The following is a selection example based on total heat load for cooling. Figure 1-6.1: Room plan Room A Room B Room H Room G Room C Room D Room F Room E Step 1: Establish design conditions ▪ Indoor air temperature 25.8°C DB, 18°C WB; outdoor air temperature 33°C DB. ▪ Determine peak load of each…
-
Table 1-6.2: Extract from medium static pressure duct (T2) cooling capacity table
Indoor air temperature Model MDV VC MAX Series Service Manual T2 Capacity 14°C WB 16°C WB 18°C WB 19°C WB 20°C WB 22°C WB 24°C WB index 20°C DB 23°C DB 26°C DB 27°C DB 28°C DB 30°C DB 32°C DB TC SC TC SC TC SC TC SC TC SC TC SC TC SC 22 1.5 1.4 1.8 1.5 2.1 1.6 2.2 1.6 2.3 1.7 2.4 1.5 2.4 1.5 28 1.9…
-
Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
Outdoor unit capacity Maximum number of Sum of capacity indexes of connected indoor connected indoor units (standard Capacity kW HP units indoor units only) index 50.0 to 650 29 56.0 to 728 33 61.5 22 615 307.5 to 799.5 36 67.0 to 871 39 73.0 to 949 43 78.5 28 785 392.5 to 1020.5 46 85.0 to 1105 50…
-
c)
Find the correction factor for piping length and level difference (“K1”) MDV VC MAX Series Service Manual Figure 1-6.3: VC MAX rate of change in cooling capacity Notes: 1. The horizontal axis shows equivalent length of piping between farthest indoor unit and first outdoor branch joint; the vertical…
-
Part 2
Component Layout and Refrigerant Circuits 20 Part 2 - Component Layout and Refrigerant Circuits 1 Layout of Functional Components 2 Piping Diagrams 24 3 Refrigerant Flow Diagrams 29 19
-
1 Layout of Functional Components
1.1 8-12HP layout of functional components Figure 2-1.1: 8-12HP layout of functional components 15 Legend No. 2 1 Compressor 12 2 Oil separator 3 High pressure switch 4 Check value 5 High pressure sensor 6 Fan 7 Microchannel heat exchanger 8 Stop valve(gas side) 9 Electronic expansion valve (EEVA)…
-
1.2 14-20HP layout of functional components
Figure 2-1.2: 14-20HP layout of functional components 16 Legend No. Compressor 2 Oil separator 3 High pressure switch 4 Check value 5 High pressure sensor 6 Fan 7 Microchannel heat exchanger 8 Stop valve (liquid side) 9 Electronic expansion valve (EEVA) 10 Charge port 11 Electronic expansion valve…
-
1.3 22-24HP layout of functional component
Figure 2-1.3: 22-24HP layout of functional components 16 Legend No. MDV VC MAX Series Service Manual 11 1 Compressor 2 Oil separator 3 High pressure switch 4 Check value 5 High pressure sensor 6 Fan 7 Microchannel heat exchanger 8 Stop valve (liquid side) 9 Electronic expansion valve (EEVA) 10…
-
1.4 26-30HP layout of functional component
Figure 2-1.3: 26-30HP layout of functional components Legend No. Compressor 2 Oil separator 3 High pressure switch 4 Check value 5 High pressure sensor 6 Fan 7 Microchannel heat exchanger 8 Stop valve (gas side) 9 Electronic expansion valve (EEVA) 10 Charge port 11 Stop valve (liquid side) 12…
-
2 Piping Diagrams
2.1 8-12HP piping diagram MDV VC MAX Series Service Manual Figure 2-2.1: 8-12HP piping diagram Legend 24 No. Parts name No. Parts name 1 Compressor 14 Low pressure sensor 2 Oil separator 15 Gas-liquid separator 3 High pressure switch 16 Heat exchanger 4 Check value Sensor Code Description 5 High…
-
2.2 14-20HP piping diagram
Figure 2-2.2: 14-20HP piping diagram Part 2 - Component Layout and Refrigerant Circuits Legend No. Parts name No. Parts name 1 Compressor 15 Low pressure sensor 2 Oil separator 16 Gas-liquid separator 3 High pressure switch 17 Muffler 4 Check value 18 Heat exchanger 5 High pressure sensor Sensor…
-
2.3 22-24HP piping diagram
MDV VC MAX Series Service Manual Figure 2-2.3: 22-24HP piping diagram Legend 26 No. Parts name No. Parts name 1 Compressor 15 Low pressure sensor 2 Oil separator 16 Gas-liquid separator 3 High pressure switch 17 Muffler 4 Check value 18 Heat exchanger 5 High pressure sensor Sensor Code Description 6…
-
2.4 26-30HP piping diagram
Figure 2-4.4: 26-30HP piping diagram Part 2 - Component Layout and Refrigerant Circuits Legend No. Parts name No. Parts name 1 Compressor 16 Low pressure sensor 2 Oil separator 17 Gas-liquid separator 3 High pressure switch 18 Muffler 4 Check value 19 Heat exchanger 5 High pressure sensor 20 Liquid…
-
2.5 Key components
1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Gas-liquid separator: Separates liquid refrigerant from gas refrigerant, stores liquid refrigerant and oil to protect compressor from…
-
Refrigerant Flow Diagrams 3.1 8-12HP 3.1.1 Cooling operation Figure 2-3.1: 8-12HP refrigerant flow during cooling operation Part 2 - Component Layout and Refrigerant Circuits 3.1.2 Oil return operation in cooling mode Figure 2-3.3: 8-12HP refrigerant flow during oil return operation in cooling mode…
-
3.2 14-20HP
3.2.1 Cooling operation MDV VC MAX Series Service Manual Figure 2-3.6: 14-20HP refrigerant flow during cooling operation 3.2.2 Oil return operation in cooling mode Figure 2-3.8: 14-20HP refrigerant flow during oil return operation in cooling mode 30
-
3.3 22-24HP
3.3.1 Cooling operation Figure 2-3.11: 22-24HP refrigerant flow during cooling operation Part 2 - Component Layout and Refrigerant Circuits 3.3.2 Oil return operation in cooling mode Figure 2-3.13: 22-24HP refrigerant flow during oil return operation in cooling mode 31
-
3.4 26-30HP
3.4.1 Cooling operation MDV VC MAX Series Service Manual Figure 2-3.11: 26-30HP refrigerant flow during cooling operation 3.4.2 Oil return operation in cooling mode Figure 2-3.13: 26-30HP refrigerant flow during oil return operation in cooling mode 32
-
Part 3
Control 1 General Control Scheme Flowchart 34 2 Stop Operation 35 3 Startup Control 36 4 Normal Operation Control 5 Protection Control 47 7 Other Control 48 44 Part 3 - Control 6 Special Control 38 33
-
1 General Control Scheme Flowchart
Sections 2 to 7 on the following pages detail when each of the controls in the flowchart below is activated. 2 Stop operation ▪ Abnormal shutdown ▪ System stops ▪ A unit stops when the load demanded decreases Special control 6 Thermo on MDV VC MAX Series Service Manual Startup control ▪ Compressor…
-
2 Stop Operation
The stop operation occurs for one of the three following reasons: 1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs, the system will makes a 'stop with thermos-off' operation and an error code will be displayed on the outdoor unit digital displays. 2. The system…
-
3 Startup Control
3.1 Startup Sequence and Frequency Control in Combination Modules During the start-up process, the control of the compressor and the heat exchange mode is uniformly judged by the master outdoor unit, and the electronic expansion valve and solenoid valve are self-judged by the salve unit according to…
-
3.3 Startup Control for Cooling Operation
Table 3-3.1: Component control during startup in cooling mode Component Inverter compressor INV1 A Inverter compressor INV2 B[1] Inverter fan 1 FANA Inverter fan 2[1] FANB Solenoid valve Ending conditions STEP2 STEP3 STEP4 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0 Step If T4 temperature exceeds the operating…
-
4 Normal Operation Control
4.1 Component Control during Normal Operation Table 3-4.1: Outdoor unit component control during normal operation Component Cooling PI control, High pressure protection, Low pressure protection, Discharge temperature protection, Inverter Over-current protection control, Inverter module temperature…
-
4.2 Compressor Control
Cooling operation Compressor frequency is PI controlled to keep low pressure at target temperature. Te: Low pressure equivalent saturation temperature (°C) Tes: Target Te value. Tes will be decided by Te setting, if you choose Auto that means except Te setting, the Tes would be adjusted according to…
-
4.3 Rotation of Compressors
In order to make operating time equal for each compressor of combination outdoor units, outdoor units are used in rotation. Figures 3-5.1 to 3-5.2 show the compressor rotation in systems with two and three units. The master unit and slave units 1 and 2 are shown from left to right in that order, and…
-
4.5 Electronic Expansion Valve Control
4.5.1EEVA control The positions of electronic expansion valves EEVA are controlled in steps from 0/0 (fully closed) to 480/2880 (fully open). 4.5.1.1 Outdoor unit heat exchanger is performed via the condenser This function is used to exert PI control on the electronic expansion valve EEVA so that…
-
4.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-4.4 Table 3-4.4 Outdoor unit fan step Fan speed index MDV VC MAX Series Service Manual Fan speed (rpm) 22-30HP 8-20HP FANA / FANB 0 150/150 120 150/150 130 150/150 140 150/150 150 150/150 170 150/150 190 180/180 250 250/250…
-
Table 3-4.5 Upper limit fan step in static pressure mode
-
5 Protection Control
5.1 High Pressure Protection Control This control protects the system from abnormally high pressure and protects the compressors from transient spikes in pressure. Figure 3-5.1: High pressure protection control Normal operation Pc ≥ 4.15MPa Pc < 3.5MPa High pressure protection, error code P12 is…
-
5.4 Over-current Protection Control
Over current protection control is performed to prevent tripping due to transient inverter over-current. It protects the compressors from abnormally high currents. It is performed for each compressor. Figure 3-5.4: Over-current protection control Normal operation Current ≥ CurrentA Current <…
-
5.6.2 Error code F63
Figure 3-5.7: Non-inductance resistors temperature protection control Normal operation Tr <70°C Tr ≥95°C Non-inductance resistors temperature protection, error code F63 is displayed Notes: 1. Tr: Non-inductance resistors temperature 5.7 Wet Compression Protection Control This protection is used to…
-
6 Special Control
6.1 Oil Return Operation In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that are in standby. When the outdoor…
-
7 Other Control
7.1 Overload control Overload control is used to maintain comfort requirement (i.e. outlet air temperature) and keep proper system pressure. Figure 3-7.1: Overload control Normal operation Indoor unit operation ratio <105% Indoor unit operation ratio ≥ 130% Overload control, indoor units operates in…
-
Table 3-7.1: Low noise mode (continued)
Silent mode 8 ODU Silent mode 9 Silent mode 10 Silent mode 11 Silent mode 12 Silent mode 13 Silent mode 14 Max. Fan step Max. frequency step Max. Fan step Max. frequency step Max. Fan step Max. frequency step Max. Fan step Max. frequency step Max. Fan step Max. frequency step Max. Fan step Max.…
-
Part 4
Field Settings 50 1. Overview 51 2. Digital display and button settings 3. System Parameter Check 59 51
-
1. Overview
This chapter describes how the system configuration can be implemented once the installation is completed, and other relevant information. It contains the following information: ● Implement field settings ● Using the Check function Note: The installation personnel should read this chapter. 2.…
-
2.3 Menu mode
Only master unit has the full menu functions, slave units only have error codes check and cleaning functions. 1. Long press SW5 "MENU" button for 5 seconds to enter menu mode, and the digital display displays "n1". 2. Press SW3 / SW4 "UP / DOWN" button to select the first level menu "n1", "n2"…
-
Menu mode function
Table 4-2.3 Menu mode function: First level menu n0 (Information query) Second level menu Specified menu mode 0 (History error) 0 Query History error (last ten error codes) 1 Cleaning history error 1 (address) 0 Query Indoor unit's address 2 Query the address of Indoor unit in power-off condition 2…
-
First level menu
Second level menu 1 (Silent mode) MDV VC MAX Series Service Manual 2 (static pressure) Specified menu mode Description 8 Silent mode 8 9 Silent mode 9 A Silent mode 10 b Silent mode 11 C Silent mode 12 d Silent mode 13 E Silent mode 14 0 0Pa static pressure 1 20Pa static pressure 2 40Pa static…
-
First level menu
Second level menu Default Description 0 0m level difference between indoor unit and outdoor unit 1 20m level difference between indoor unit and outdoor unit 2 40m level difference between indoor unit and outdoor unit 3 60m level difference between indoor unit and outdoor unit 4 80m level difference…
-
First level menu
Second level menu 0 (target evaporation temperature of the indoor unit) n6 (evaporation and condensation temperature) MDV VC MAX Series Service Manual 2 (target condensation temperature of the indoor unit) n8 7 1 (Rotation) n9 nc[1] (Dry contact function) 1 2(customized) Notes: 1. 56 Using with…
-
2.4 Special mode introduction
Step1:preparation Step2:Calculate static pressure of Outdoor unit Step3:Indoor and outdoor temperatures are within the allowable range of test run No Display error code U32/U33/U34 Yes The number of Indoor units is greater than 4 No Turn on all indoor units Yes Start the Indoor unit with Yes…
-
2.4.2.3. System refrigerant quantity detection
After entering this mode, the system will automatically run and finally output the diagnostic results of the system refrigerant quantity. Diagnostic results: a) b) c) d) e) Normal: Digital display “d34” f) No result- The system operation conditions do not meet the functional requirements: Digital…
-
3. System Parameter Check
3.1 UP / DOWN system check button Before pressing UP or DOWN button, allow the system to operate steadily for more than an hour. On pressing UP or DOWN button, the parameters listed in below table will be displayed in sequence. Table 4-3.1 system check list: DSP1 content Parameters displayed on DSP2…
-
Table 4-3.1 system check list(continue)
DSP1 content Parameters displayed on DSP2 Remarks 27.-- Discharge superheat degree (°C) Actual value = value displayed 28.-- Primary current(A) Actual value = value displayed /10 29.-- Inverter compressor A current (A) Actual value = value displayed /10 30.-- Inverter compressor A current (A) Actual…
-
Table 4-3.1 system check list(continue)
DSP1 content 50.-- Parameters displayed on DSP2 Reserved Remarks Actual value = value displayed(1) 0 :No result 1 :Significantly insufficient 51.-- Refrigerant volume judgment(1) 2 :insufficient 3 :Normal 4 :excessive 5 :Significantly excessive 52.-- Dirty blockage rate (outdoor heat exchanger)…
-
Part 5
Electrical Components and Wiring Diagrams 62 1. Outdoor Unit Electric Control Box Layout 2. Outdoor Unit Main Control Board 3. Compressor & Fan drive board 69 4. Wiring Diagrams
-
1. Outdoor Unit Electric Control Box Layout
1.1 8-18HP electric control box Figure 5-1.1: 8-18HP electric control box Part 5 - Electrical Components and Wiring Diagrams 1.2 20HP electric control box Figure 5-1.2: 20HP electric control box Notes: The differences between electric control box of 20HP and 8-18HP are shown in the Figure 5-1.2.…
-
1.3 22-24HP electric control box
MDV VC MAX Series Service Manual Figure 5-1.3: 22-24HP electric control box Notes: The differences between electric control box of 22-24HP and 8-18HP are shown in the Figure 5-1.3. Others are the same as 8-18HP electric control box. 1.4 26-36HP electric control box Figure 5-1.4: 26-30HP electric…
-
Outdoor Unit Main Control Board 2.1 Outdoor unit main Control Board ports Figure 5-2.1: Outdoor unit main Control Board ports1 Part 5 - Electrical Components and Wiring Diagrams Notes: Label descriptions are given in Table 5-2.1: Main Control Board port . 65
-
Table 5-2.1: Main Control Board port
Label in Figure 5-2.1 Port code Content Port voltage 1 CN82 Reserved 5Vdc 2 CN36 Recirculation fan control port 3.3Vdc 3 CN70 EEVA drive port 12Vdc 4 CN71 EEVB drive port(Reserved) 12Vdc 5 CN72 EEVC drive port 12Vdc 6 CN73 EEVE drive port 12Vdc Microchannel heat exchanger inlet temperature…
-
2.2 Outdoor unit main Control Board components
2.2.1 Layout Figure 5-2.2: Outdoor unit main Control Board components Part 5 - Electrical Components and Wiring Diagrams 2.2.2 Function of buttons SW3 to SW6 Table 5-2.2: Function of buttons SW3 to SW6 Button SW3 (UP) SW4 (DOWN) SW5 (MENU) SW6 (OK) Function In menu mode: previous and next buttons…
-
Digital display output Table 5-2.4: Digital display output in different operating states Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2 The number of indoor units in Standby The address of outdoor unit communication with the outdoor DSP1 units Normal MDV VC MAX Series…
-
Compressor & Fan drive board 3.1 Corresponding table of Compressor & Fan drive board and outdoor units Table 5-3.1: Corresponding table of Compressor & Fan drive board and outdoor units Compressor & Fan drive board model Outdoor unit series Model 35A VC MAX 8-16HP;26-30HP 50A VC MAX 18HP 75A VC MAX…
-
3.3 Compressor & Fan drive board of 50A
MDV VC MAX Series Service Manual Figure 5-3.2: Compressor & Fan drive board of 50A 70
-
3.4 Compressor & Fan drive board of 35A
Figure 5-3.3: Compressor & Fan drive board of 35A Part 5 - Electrical Components and Wiring Diagrams 71
-
3.5 Compressor & Fan drive board ports
MDV VC MAX Series Service Manual Figure 5-3.4: Compressor & Fan drive board ports Table 5-3.2: Compressor & Fan drive board port Label in Port Feature Figure 5-2.5 code identifier 1 CN1 P-in 2 CN5 P-out 3 CN16 L1 Three phase power input of L1 phase 4 CN7 L2 Three phase power input of L2 phase 5 CN15…
-
Table 5-3.2: Compressor & Fan drive board port (continued)
Label in Port Feature Figure 5-2.5 code identifier 8 CN3 DCFAN CN8/C 9 N9 O-Motor Content Port voltage Three phase output of the inverter ,connected to the DC fan Communication port between main control board and Inverter drive board 0~100%*input voltage(varying) Ports from top to bottom are defined…
-
3.6 The installation guide of Compressor & Fan drive board
MDV VC MAX Series Service Manual Figure 5-3.5: The installation guide of Compressor & Fan drive board 1. Before maintaining or repairing the outdoor unit, cut off the power supply of the outdoor unit for 5 minutes and use a mustimeter to ensure that the voltage is zero to avoid electric shock.…
-
4. Wiring Diagrams
Figure 5-3.1: Outdoor unit wiring diagram Part 5 - Electrical Components and Wiring Diagrams 75
-
Legend
76 Code Name Code Name COMP A/ COMP B Compressor XT1 Terminal block EEVA / EEVC / EEVE Electronic expansion valve T4 Outdoor ambient temperature sensor FAN A/ FAN B DC Fan T5 Liquid pipe temperature sensor DC FAN A/DC FAN B Recirculation Fan T6A Microchannel heat exchanger inlet pipe temperature…
-
Part 6
Diagnosis and Troubleshooting 1 Error Code Table 78 3 Error in Compressor Driver 4 Error in Fan Drive Part 6 - Diagnosis and Troubleshooting 2 Error in Main Control Appendix 174 77
-
1 Error Code Table
1.1 Outdoor Error code table Table 6-1.1 Outdoor Error code table Error code Remarks Manual re-start required2 A01 Emergency shutdown Outdoor unit’s fault NO AAx No.x Inverter driver board does not match the main control board Outdoor unit’s fault NO xA61 No.x slave unit error Salve unit’s fault NO…
-
Table 6-1.1 Outdoor Error code table (continued)
Error code Manual re-start Error description Remarks F81 Gas pipe temperature sensor (Tg) error (open/short) sensor error NO F91 Liquid pipe temperature sensor (T5) error (open/short) sensor error NO FA1 Outdoor Heat exchanger gas temperature sensor (T8) error (open/short) sensor error NO FC1…
-
1.2 Installation and debugging error code table
Table 6-1.2 Installation and debugging error code table Error code Remarks Manual restart required2 U11 Outdoor unit model is not set System configuration YES U12 Outdoor unit Capacity setting error System configuration YES U21 System contains the old Indoor Unit with old platforms System…
-
Table 6-1.3 Compressor drive error code table (continued)
Manual re-start Error code Error description Remarks xL47 Module type mismatch Module error NO xL4E EEPROM error E party error NO xL5E Startup failed Control error NO xL51 Out-of-step error Control error NO xL52 Locked-rotor protection Motor error NO xL6E Compressor motor lack of phase protection…
-
Table 6-1.5 Status prompt code table (continued)
Status code d14 Code description The outdoor ambient temperature exceeds the lower limit (Cooling mode) required2 Status hint NO Refrigerant judgment: no result Status hint NO d32 Refrigerant quantity judgment:Significantly excessive Status hint NO d33 Refrigerant quantity judgment:Slightly…
-
2 Error in Main Control
2.1 A01: Emergency shutdown of Outdoor Units Digital display output ▪ ▪ ▪ Description Compressor protection shut down All Outdoor Units stop running Error codes are displayed only on master uint. Figure A The dry contact is open (taking Input1 as an example) ▪ ▪ ▪ Figure B The dry contact is closed…
-
A01
One or both of the following are true: nC0 = 3 or nC1 = 3 If nC0 3, ignore port Input1 in the following troubleshooting If nC1 3, ignore port Input2 in the following troubleshooting Yes Menu set item n28 = 0 Are Input1 and Input2 of port CN28 of the main board connected to the external? (See Figure…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Trigger / recover condition Trigger condition: Slave unit is in error. Recover condition: Error of slave unit recover Reset method: Resume automatically Possible causes Slave unit is in error Part 6 - Diagnosis and Troubleshooting ▪ Description xA61 shows a slave…
-
2.3 AAx: Inverter driver board X does not match the main control board
MDV VC MAX Series Service Manual Digital display output ▪ ▪ ▪ Description No.x Inverter driver board does not match the main control board All units stop running. Error code is displayed on the unit with the error ▪ ▪ ▪ Trigger / recover condition Trigger condition: Parameters of the built-in drive…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Part 6 - Diagnosis and Troubleshooting ▪ ▪ ▪ ▪ Description No.x Recirculation Fan[1] is in error Unit with the error stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: the difference between the actual…
-
2.5 bA1: HyperLink cannot open or close IDU’s Electronic expansion valve
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ Description When some IDUs are powered off, HyperLink fail to close their EEV. All units stop running. Error code is only displayed on the master unit Error is generated only under the M1M2 communication protocol.…
-
Digital display output
Part 6 - Diagnosis and Troubleshooting Description ▪ All units stop running ▪ Error code is displayed on the unit with the error. Trigger / recover condition Trigger condition: The main control board has not detected signals from the EEV for 2 minutes. Recover condition: The main control board…
-
Digital display output
▪ ▪ Description The address of Outdoor Unit is repeated. Error code is displayed on the master outdoor unit. ▪ ▪ ▪ Trigger /recover condition Trigger:Two or more outdoor units in the combined system have the same address Recover condition: The address of master and slave unit are set to be 0~3…
-
2.8 C21: Communication error between IDU and ODU
Digital display output Table 6.2.1 Communication troubleshooting list: ODU interface PQE M1M2 PQE IDU interface PQE M1M2 PQE IDU type V8 V8 V6 Communication protocol n45-0, V8 protocol P Q communication n45-1, V6 protocol PQE communication n45-2, V8 HyperLink protocol IDU uniform power supplied…
-
2. Faults caused by other factors
(1) All indoor units are not set address; (2) All indoor units are not powered on; (3) The communication wiring between the master unit and the first IDU is not reliably connected: ▪ The communication wiring between the ODU and the first IDU is not tightened, or the surface contact of the power…
-
2.9 C26 Abnormal reduction in the number of indoor units
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ Trigger / recover condition Trigger condition: N0: The number of IDU set by ODU; N1: The number of online IDUs. 1) When the unit is installed and commissioned, enter the number of IDUs (N0). The number of IDUs detected by the system is N1. If N1 <…
-
C26
Is the IDU address code not set or duplicated. Yes Select one of the following solutions Solution 1: Reset the address. In menu n44, set to [0] (automatic addressing)[1]. Solution 2: Manually set the address of IDUs. After setting, ensure that the IDU addresses are not duplicated. No Power on all…
-
2.10 C28: Abnormal increase in the number of indoor units
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ C28 Spot check item 3: Setting the number of IDUs Set the number of IDUs. Does it match the number of installed IDUs in the system? No Enter the master ODU menu n42 to change the number of indoor units based on the actual installation Yes Spot check item 37…
-
2.11 xC31: Communication error between No.x slave outdoor unit and master outduoor unit
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ Description The No.x outdoor slave unit cannot communicate with the outdoor master unit. Outdoor units that display the error code stop running. Error code is only displayed on the slave unit with the error. Trigger /…
-
2.12 C32: Abnormal reduction in the number of outdoor units
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ C32 Spot check item 0: Address code of the slave ODU Yes Ent er menu n40 to set ODU addresses again, 1-3 for slav e O DUs without duplicati on Are slave ODU address codes repeated? No Check the slave ODU power supply Is there tripping, unst able voltage, or…
-
2.13 C33: Abnormal increase in the number of outdoor units
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ Description The number of online outdoor slave units detected by the outdoor master unit increases All units stop running. Error code is only displayed on the master unit Trigger / recover condition Trigger condition:One or…
-
2.14 xC41: Communication Error between main control board and No.x inverter driver board
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ board are duplicate (the correct addresses are: "00" ▪ ▪ ▪ ▪ for No. 1 drive board and "01" for No. 2 drive board). The main power has L1/L2/L3 misphase or abnormal voltage. The filter board is damaged. No. x inverter drive board is damaged. The ODU main…
-
C41
Measure the ODU main power L1/L2/L3. Is there phase loss or voltage failure? Yes Eliminate the problems with the power supply accordingly No Measure the input voltage L1/L2/L3 after module rectification. Is there phase loss or voltage failure? Is there circuit break, misphase, or poor contact with…
-
Digital display output Error code E41 F81 Error description Outdoor ambient temperature sensor (T4) error(open/short) Gas pipe temperature sensor (Tg) error (open/short) Remarks Digital display output sensor error sensor error Outdoor heat exchanger liquid FC1 temperature sensor (TL) error sensor…
-
The temperature sensor is not properly connected to the main control board
The sensor is short-circuited or fails. The main control board is damaged Procedure 1. E41/F81/FC1/FP1 ▪ ▪ ▪ E41/F81/FC1/FP1 Correctly connect temperature sensor Yes Temperature sensor connection on main board is loose[1] No Temperature sensor is short-circuited or has failed[2] No PCB is damaged[3]…
-
3. xF71
1F71, 2F71 T7C sensors are not connected to the compressor top or T7C1 and T7C2 are connected reversely to the compressor Yes Connect T7C sensors correctly to the compressor top and fix them with spring clips. No Correctly connect T7C sensor Yes T7C sensor is not connected or is in poor contact[1]…
-
2.16 F63: Non-inductive resistance Tr overtemperature protection
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ Description The temperature of the Tr non-inductive resistance NTC is too high. All units stop running Error code is displayed on the outdoor unit with the Error Trigger/ Recover condition Trigger condition: The non-inductive…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ 105 Part 6 - Diagnosis and Troubleshooting ▪ ▪ Description Discharge Temperature is over the limit. All outdoor Unit stop running Error code is displayed on the unit with the error Trigger / Recover condition Trigger condition: F72: Discharge Temperature…
-
Procdure
F72/F7A Yes Open the ODU check valve and power on. Does the error display again? Is the ODU check valve closed? No Is the piping and wiring connected correctly? Yes Correctly connect the piping and wiring, then power on. Does the error display again? No Is the temperature of the discharge…
-
2.18 F75: Compressor discharge insufficient superheat protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ Trigger / recover condition Trigger condition: During the system operation, the discharge superheat of the compressor is lower than 6 ° C and lasts for more than 90 minutes Recover condition: Resume automatically after 30 seconds of downtime Reset…
-
F75
Correctly connect the piping and wiring, then power on. Does the error display again? No Is the piping and wiring connected correctly? Yes Yes Figure I Do any of the following conditions occur? 1. T7C sensors are not connected to the compressor top 2. T7C1 and T7C2 are connected reversely to the…
-
2.19 P11: High pressure sensor error
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Part 6 - Diagnosis and Troubleshooting ▪ ▪ Description Open/short circuit error of high pressure sensor All units stop running. The error code is displayed on the Outdoor Unit with error. Trigger / recover condition Trigger condition: The high pressure sensor is…
-
2.20 P12/P14: High pressure protection
Digital display output ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ 110 Description P12: The high pressure is over the limit. P14: 3 times P12 in 100 minutes All units stop running Error code is displayed on the unit with the Error Trigger / recover condition Trigger condition: • P12: Phigh…
-
P12
Enter the MENU vacuum mode (n15) after power off. Wait for 1min. Are the HP and LP pressures close, and troubleshooting? No Yes If the HP pressure is too high, preferably check the following items. 1. Is the ODU check valve fully opened? 2. Is the piping and wiring connected correctly? 3. Are coils…
-
2.21 P13: High pressure switch protection
Digital display output Description All units stop running Error code is displayed on the unit with the Error Trigger / recover condition Trigger condition: discharge pressure≥ 4.1MPa or the switch is open-circuited. Recover condition: pressure switch is closed. Reset method: Resume automatically.…
-
2.22 P21: Low pressure sensor error
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Part 6 - Diagnosis and Troubleshooting ▪ ▪ ▪ ▪ ▪ ▪ Description Open/short circuit Error in suction pressure sensor All units stop running. Error code is only displayed on the unit with the error. Trigger / recover condition Trigger condition: PLow Pressure<0.02MPa…
-
2.23 P22/P25: Low pressure protection
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ 114 Description P22: Low pressure protection; P25: Low pressure protection occurs 3 times in 60 min. All units stop running. Error code is displayed on the unit with the error. Trigger/ Recover condition Trigger…
-
P22/P25
Enter the MENU vacuum mode (n15) after power off. Wait for 1min. Are the HP and LP pressures close, and troubleshooting? No Yes If the LP pressure is too low, preferably check the following items. 1. Is the ODU check valve fully opened? 2. Is the piping and wiring connected correctly? 3. Are coils…
-
2.24 P24: Low Pressure too High Protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ 116 Description All units stop running. ODU fault is determined based on the sensor. Error code is displayed on the unit with the error Trigger/ Recover condition Trigger condition: Suction pressure >1.6MPa and lasts 60…
-
P24
Is the pressure of the detection valve during s teady operation 1.6 MPa? [1] No No Is the main board pressure normal? [3] The main board is damaged. Rep lace it Yes Yes There may be 3 co nditio ns for the sys tem: 1. The ODU operates out of the operating temperature range in cooling mode [2] 2. The…
-
2.25 P31: Primary Side Overcurrent Protection
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ Description The AC current at the device primary side is too high, which triggers protective shutdown. The current is transmitted by the module to the main control board. All units stop running Error code is displayed on the…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ Trigger / recover condition Trigger condition: P32: During operation, the DC bus current of any compressor exceeds the upper limit P33: Within 100min, No.x compressor appears P32 for 3 times Recover condition: P32: The DC bus current of all compressors is…
-
XP32,XP33
ODU stop valve is closed? Yes Open ODU stop valve No Yes compressor cable is damaged Replacing the compressor Cable No Yes The resistance of the compressor wiring terminals to the ground is less than 1 MΩ The compressor is damaged. Replace the compressor No MDV VC MAX Series Service Manual Measure…
-
2.27 P51: High AC voltage protection
Digital display output ▪ ▪ ▪ Trigger / recover condition Trigger condition:The AC voltage of Outdoor Unit over 265 V Recover condition: Wait 7/15/30min for each occurrence, and the AC voltage of Outdoor Unit drops below 250 V Reset method: Resume automatically. ▪ ▪ Possible causes The power supply…
-
2.28 P52: Low voltage protection
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ Description The AC voltage of the system is too low, triggering the protection shutdown All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition:The Vac of…
-
2.29 P53: Phase B and N of the power cable are connected to the opposite protection
Digital display output ▪ ▪ ▪ Trigger / recover condition Trigger condition: The drive board uploads L35 fault Recover condition: The drive board does not upload L35 fault Reset method: Resume automatically ▪ ▪ ▪ Possible causes Outdoor Uint power supply B N is inversely connected Cables in the…
-
2.30 P54: DC bus low voltage protection
MDV VC MAX Series Service Manual Digital display output Description ▪ The DC bus voltage of the compressor is too low ▪ All units stop running. ▪ Error code is displayed on the unit with the error Trigger / recover condition ▪ Trigger condition: The drive board uploads XL3E fault ▪ Recover…
-
2.31 P55: DC bus ripple over protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ P55 Measure the AC voltage between module input power supplies L 1 and L2, L1 and L3, and L2 and L3. Is it within ±10% of the rat ed volt age[1]? Is there phase-lack or misphase? Yes Correct the power suppl y No Replace the drive board Note: [1] When the system is…
-
MDV VC MAX Series Service Manual Digital display output Description ▪ No.x inverter driver board DC bus voltage is too low ▪ All units stop running. ▪ Error code is displayed on the unit with the error Trigger / recover condition ▪ Trigger condition: The inverter driver board upload L3E/J3E fails ▪…
-
Digital display output Part 6 - Diagnosis and Troubleshooting Description ▪ No.x inverter driver board DC bus voltage is too high ▪ All units stop running. ▪ Error code is displayed on the unit with the error Trigger / recover condition ▪ Trigger condition: The inverter driver board upload L31/J31…
-
2.34 xP58: No.x inverter driver board DC bus voltage is seriously too high
MDV VC MAX Series Service Manual Digital display output Description ▪ No.x inverter driver board DC bus voltage is seriously too high ▪ All units stop running ▪ Error code is displayed on the unit with the error Trigger / recover condition ▪ Trigger condition: The inverter driver board upload…
-
Digital display output Part 6 - Diagnosis and Troubleshooting Description ▪ The phase and neutral wires are connected reversely and fail the inspection. ▪ All units stop running ▪ Error code is displayed on the unit with the error Trigger / recover condition ▪ Trigger condition: phase and neutral…
-
MDV VC MAX Series Service Manual Digital display output ▪ ▪ ▪ Description The EEPROM parameter of the ODU main control board is incorrect All units stop running. Error code is displayed on the unit with the error ▪ ▪ ▪ Trigger / recover condition Trigger condition:EEPROM parameter verification is…
-
2.37 Pb1: HyperLink overcurrent error
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ Pb1 Check the communication wiring of the system. Is there short circuiting of M1/M2 wiring? Yes Correct the wiring and eliminate the short circuit No Connect the communication wiring of ODU to the M1/M2 port and the communication wiring of IDUs to the P/Q port…
-
2.38 Pd1, Pd2: Anti-condensation protection
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ ▪ 132 Description Anti-condensation protection All units stop running. Error code is displayed on the unit with the error Trigger / recover condition Trigger condition: Pd1: Liquid pipe inlet temperature (T5) remains…
-
Pd1/Pd2
Check the following aspects first: 1. EEVC terminal is correctly connected to the main board and the EEVC is correctly connected to the coil [1] 2. The temperature of T6A/T6B/T5 is consistent when spot check in ODU power-off condition. Is all of the above correct? No Connect the EEVC or sensor…
-
2.39 U11: Outdoor unit model is not set
MDV VC MAX Series Service Manual Digital display output ▪ ▪ ▪ Description The outdoor unit model is not set into the main board. All units stop running Error code is displayed on the unit with the error ▪ ▪ ▪ Trigger / recover condition Trigger condition: The model information is not set. Recover…
-
2.40 U12: Outdoor unit Capacity setting error
Digital display output ▪ ▪ ▪ Trigger / recover condition Trigger condition: The capability information of outdoor unit is not set Recover condition: Reset the capability information of outdoor unit Reset method: Resume manually ▪ Possible causes The capability information of outdoor unit is not set…
-
2.41 U21: The indoor unit connection is incorrect
Digital display output ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ Description Connected to the 1st generation indoor unit or indoor unit address repeated in system All Outdoor units stop running Error code is displayed on the master unit Trigger / recover condition Trigger condition: • 1st…
-
2.42 U31: The test run was never successful
Digital display output ▪ ▪ ▪ Description The system is not in the test run or the test run is unsuccessful All units stop running Error code is only displayed on the master unit. ▪ Possible causes The system is not in the test run or the test run is unsuccessful ▪ Part 6 - Diagnosis and…
-
2.43 U32, U33, U34: The temperature is not suitable for test run
Digital display output ▪ ▪ ▪ ▪ Description During the test run, the indoor or outdoor temperature exceeds the operating range All units stop running Error code is only displayed on outdoor unit Trigger /Recover condition Trigger condition: After entering into test run, the master unit estimates…
-
Digital display output ▪ ▪ ▪ ▪ Description The outdoor unit stop valve is not opened during the test run. All units stop running Error code is only displayed on the master unit. Trigger/ Recover condition Trigger condition: Error code Description The liquid side stop valve of the U35 system is not…
-
2.45 U38: Outdoor Unit has no address
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ Description Outdoor Unit has no address. Outdoor Unit with error can not run. Outdoor Unit with error cannot communicate with indoor units. Trigger / recover condition Trigger condition: Outdoor unit address is not set Recover…
-
2.46 U3A: The communication wiring is connected incorrectly
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Trigger / Recover condition Trigger condition: Indoor unit piping and communication wiring are not connected in the same system. The communication wiring of the indoor unit is connected to another system. Recover condition: Set "n11-2" in the MENU for test run, and…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ Description Ambient temperature of the test environment exceeds the allowed range during the test run All units stop running Error code only displayed on the master unit. Trigger / Recover condition Trigger condition: Return…
-
2.48 U3C: Changeover mode error
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Part 6 - Diagnosis and Troubleshooting ▪ ▪ Description ODU in changeover mode doesn’t set the VIP IDU address. ODUs stop running Error code only displayed on the master unit. Trigger / Recover condition Trigger condition: Outdoor unit in changeover mode, but the…
-
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ Description Combination ratio of indoor unit and outdoor unit is out of range All units stop running Error code only displayed on the master unit Trigger / Recover condition Trigger condition: Error code 1) 2) Description U41 The…
-
▪ ▪ ▪ Reset method: Resume manually Possible causes Indoor units and outdoor units combination ratio is out of range. Outdoor unit address is repeated or the slave outdoor unit does not have an address. Individual series indoor unit is installed in combination with a combinable series. Procedure U4x…
-
2.50 U51: More than One Outdoor Unit Models in the Individual Series System
MDV VC MAX Series Service Manual Digital display output ▪ ▪ ▪ Description Outdoor unit of Individual Series is installed in combine system, and the number of ODUs detected is greater than 1. All units stop running Error code is only displayed on master unit. ▪ ▪ ▪ Trigger / Recover condition Trigger…
-
2.51 U53: Two or More Outdoor Unit Models in the Combined System
Digital display output ▪ ▪ ▪ Trigger / Recover condition Trigger condition: Detected different series outdoor units in the combined system Recover condition: There is only one series of Outdoor Unit in the combined system Reset method: Resume manually (Power on again) ▪ ▪ Possible causes Detected…
-
3 Error in Compressor Driver
3.1 xL1E: Hardware overcurrent Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ Description The compressor current exceeds the protection value set for the hardware. The compressor stops running after the error occurs. If the error disappears one minute later, the…
-
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ XL11/XL12 Shut the unit down to check whether the compressor wiring is reversely or loosely connected Yes Adjustcompressor wiring No Shut the unit downt and use a multimeter to measure the resistance to ground of the compressor winding. Is it less than 10MΩ or is…
-
3.3 xL2E: Module overtemperature protection
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ Description The temperature of the compressor or fan drive board (IPM) exceeds the set value (100°C). The compressor will stop when the error occurs. If the error disappears one minute later, the compressor will start again…
-
3.4 xL3E: The bus voltage is too low
Digital display output ▪ ▪ ▪ ▪ ▪ XL3E fault Power off and measure the power module, including the fan module. Is it damaged?[1] Yes Replace the compressor drive board or fan drive board No Power on and measure bus voltage, which should be within the range of 350-800VDC[1], but is lower than 350VDC…
-
3.5 xL31: The bus voltage is too high
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ Description Bus voltage is higher than the high bus voltage protection threshold set by the software (800VDC). The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts…
-
3.6 xL32: The bus voltage is excessively high
Digital display output ▪ ▪ ▪ ▪ ▪ XL32 Measure the AC voltage between module input power supplies L1 and L2, L1 and L3, and L2 and L3 Is the voltage range of power supply within ±10% of the rated voltage? No Adjust the power supply (incorrect power load) Yes Is the unbalanced phase-to-phase voltage…
-
3.7 xL43: The current sampling bias is abnormal
MDV VC MAX Series Service Manual Digital display output ▪ ▪ Description The drive board is faulty upon the power-on self test. Once this fault occurs, the compressor cannot be started up, and the drive board must be checked. ▪ Trigger / recover condition Trigger condition: The drive board fails the…
-
3.8 XL45: Motor Code Mismatch
Digital display output ▪ ▪ ▪ ▪ ▪ XL45 Yes Spot-check the outdoor unit capacity, which should match the barcode on the outdoor unit No Reset the capacity code Yes Yes Is there any fault in the setting of the drive plate DIP switch S7? Adjust the DIP switch on the drive board No Replace the drive…
-
3.9 XL46: Motor Code Mismatch
Digital display output ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ Description IPM has overcurrent or IPM has drive undervoltage. The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts again. Trigger / recover condition Trigger…
-
3.10 XL47: Motor Code Mismatch
Digital display output ▪ ▪ ▪ ▪ XL47 Yes No Spot-check the unit capacity, which should match the barcode on the outdoor unit Reset the capacity code Yes Is there any fault in the setting of the drive board DIP switch S7? Yes Adjust the DIP switch of the drive module board Yes Replace it with a drive…
-
Digital display output ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ ▪ ▪ ▪ ▪ Description The compressor fails to start The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts again. Trigger / recover condition Trigger condition:The compressor…
-
3.12 xL52: Locked-rotor protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ XL5E Is the check valve opened? No Open the check valve No Is the high-low pressure difference greater than 0.2 MPaf upon startup? Yes System is unbalanced. Check the refrigerant system No Shut the unit down and check the drive board[1] Yes The power board is…
-
3.13 xL6E: Compressor motor lack of phase protection
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ Description Compressor motor lack of phase protection. The compressor stops running after the error occurs. If the error disappears one minute later, the compressor starts again. Trigger / recover condition Trigger condition: The…
-
4 Error in Fan Drive
4.1 xJ1E: Hardware overcurrent Digital display output ▪ ▪ ▪ ▪ ▪ XJ1E Check fan install ation. Is the fan blocked or locked? Yes Adjust installat ion or replace the fan No Check the fan connection plug (CN3). Is it l oose? Yes Adjust connection wiring No Shut the unit down and use a multimeter to…
-
Digital display output ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ Description The fan current exceeds the protection value set for the software. The fan will stop when the error occurs. If the error disappears five seconds later, the fan will start again. Trigger / recover condition Trigger…
-
4.3 xJ2E: Module overtemperature protection
Digital display output ▪ ▪ ▪ ▪ XJ2E No Shut the unit down to check if the check val ve i s opened Open the check v alve Yes No Are t he screws tightened, and i s thermally conducti ve sili cone grease properly applied? Reapply t he silicone grease and tighten the module screws Yes Yes Power on again…
-
4.4 xJ3E: The bus voltage is too low
MDV VC MAX Series Service Manual Digital display output Description ▪ Bus voltage is lower than the low bus voltage protection threshold set by the software (350VDC). ▪ The fan stops running after the error occurs. If the error disappears five seconds later, the fan starts again. Trigger / recover…
-
4.5 xJ31: The bus voltage is too high
Digital display output ▪ ▪ ▪ Trigger / recover condition Trigger condition: The bus voltage is higher than the software overvoltage protection threshold. Recover condition: The bus voltage is lower than the overvoltage protection threshold set by the software. Reset method: Resume automatically…
-
4.6 xJ32: The bus voltage is excessively high
Digital display output ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ Description Bus voltage is higher than the high bus voltage protection threshold set by the software (770VDC). The fan stops running after the error occurs. If the error disappears five seconds later, the fan starts again. Trigger /…
-
4.7 xJ43: The current sampling bias is abnormal
Digital display output ▪ ▪ Trigger / recover condition Trigger condition: The drive board fails the power-on self test. Reset method: Restoration after passing the self test. ▪ Possible causes The fan drive board is abnormal ▪ Procedure Replace the inverter drive board Part 6 - Diagnosis and…
-
4.8 Motor Code Mismatch
MDV VC MAX Series Service Manual Digital display output Description ▪ The compressor parameters set by the main control board do not match the compressor parameters of the drive board. ▪ Once this fault occurs, the fan cannot be started up, and the drive board must be checked. Trigger / recover…
-
4.9 XL47: Motor Code Mismatch
Digital display output 169 Part 6 - Diagnosis and Troubleshooting Description ▪ The fan parameters set by the main control board do not match the fan parameters, the driver board specifications set by the main control board do not match the fan specifications of the drive board. Trigger / recover…
-
Digital display output ▪ ▪ ▪ ▪ ▪ MDV VC MAX Series Service Manual ▪ ▪ ▪ Description The fan fails to be started. The fan stops running after the error. If the error disappears after five seconds, the fan starts again. Trigger / recover condition Trigger condition: Fan startup failure. Recover…
-
4.11 xJ52: Locked-rotor protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ Description The fan is blocked. The fan stops running after the error. If the error disappears after five seconds, the fan starts again. Trigger / recover condition Trigger condition: The fan is blocked. Recover condition: The blocking error is removed. Reset…
-
Digital display output Description The fan has phase loss protection. The fan stops running after the error. If the error disappears after five seconds, the fan starts again Trigger / recover condition Trigger condition: The fan has phase loss protection. Recover condition: Check the fan wiring…
-
4.13 xJ65: Fan IPM Short Circuit Protection
Digital display output ▪ ▪ ▪ ▪ ▪ ▪ ▪ J65 The check valve is not opened Yes Open the check valve and power on for operation Yes Correctly connect the piping and wiring, power on No Piping and wiring are inconsistent No Replace the drive board Troubleshooting 173 Part 6 - Diagnosis and Troubleshooting…
-
5 Appendix
5.1 Resistance characteristics of temperature sensor Table 6-5.1: Temperature probe symbol and position MDV VC MAX Series Service Manual Temperature probe symbol and position The probe type T4 Outdoor ambient temperature Type A T5 Liquid pipe stop valve Type A T6A Microchannel heat exchanger inlet…
-
temperature
resistance (kΩ) Type A Type B Type C 3 29.91 155.2 153.6 4 28.35 147.6 146.1 5 26.88 140.4 139.1 6 25.5 133.5 132.3 7 24.19 127.1 126 8 22.57 21.81 115.2 114.3 10 20.72 109.8 109 11 19.69 104.6 103.9 12 18.72 99.69 99.02 13 17.8 95.05 94.44 14 16.93 90.66 90.11 15 16.12 86.49 86 16 15.34 82.54 82.09…
-
таблицы и схемы — в просмотре
-
temperature
resistance (kΩ) Type A Type B Type C 89 0.8795 5.157 5.159 90 0.8525 0.8264 4.849 4.855 92 0.8013 4.703 4.705 93 0.7771 4.562 4.566 94 0.7537 4.426 4.431 95 0.7312 4.294 4.301 96 0.7094 4.167 4.176 97 0.6884 4.045 4.055 98 0.6682 3.927 3.938 99 0.6486 3.812 3.825 100 0.6297 3.702 3.716 101 0.6115…
-
таблицы и схемы — в просмотре
-
5.2 Normal status parameter of refrigerant system
The parameters listed in Tables 6.5.3 need to be noted when the following conditions are met:: ▪ The master outdoor unit can detect all indoor machines: ▪ The number of indoor units displayed for outdoor units is consistent with the actual installation. ▪ All stop valves have been opened and all…
-
5.3 Analysis of the cause of system anomalies
Cause Analysis of Excessive discharge Temperature failure of SV7 coil failure of SV7 body Control failure of SV7 Control failure of mainboard failure of EEVC coil failure of EEVC Control failure of EEVC Control failure of Discharge temperature The internal disc of ST1 is stuck failure of IDUs EEV…
-
Cause Analysis of too high Pressure
Stop valve is closed The resistance of the high-pressure side pipe is too large Piping is bent or severely deformed The pipe is blocked. *Cooling mode Control failure of EEV coil Control failure of ODU EEV Check whether coil is normal Failure of High pressure sensor whether sensor is not properly…
-
Cause Analysis of too Low Pressure
*cooling mode Control failure of suction pressure Mainboard is damaged Failure of low pressure sensor Control failure of low pressure protection Control failure of IDU MDV VC MAX Series Service Manual *heating mode Check whether the solenoid valve coil is abnormal Mainboard is damaged Check whether…
-
5.4 Inverter drive board measurement guidelines
Please give priority to the following things before testing Inverter drive board: 1) Cut off the power supply: 2) To avoid electric shock from capacitor discharge, power off for 10 minutes and wait for capacitor discharge before operation: 3) Remove all wiring on the Inverter drive board. Tools…
-
Schematic diagram of measuring points of Inverter drive board
-
5.5 Appendix of Pressure Sensor Detection
Pressure sensor characteristics 5.00 High Pressure sensor PH Low Pressure sensor PL 4.50 y = 2x + 0.5 y = 0.87x + 0.5 output voltage(V) 4.00 3.50 3.00 2.50 2.00 1.50 Part 6 - Diagnosis and Troubleshooting 1.00 0.50 0.00 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Pressure(MPa) PH…
-
5.6 Refrigerant volume diagnosis
When running the refrigerant quantity detection program, the machine calculates the system refrigerant quantity according to the ambient temperature, condensing temperature and evaporation temperature, heat exchanger inlet and outlet temperature and other parameters, and give hints according to the…
-
Start
Confirm whether the following two points meet the requirements: 1. Whether all IDUs in the system are V8 series? 2. Does the system choose V8 communication protocol or HyperLink? Whether the above two points are consistent No The detection results of the system have V6 IDUs may have a large…
-
5.7 Oil volume table
-
S-VCMAX
Ver. 2023-11 MDV Professional Equipment Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 mbt.midea.com / global.midea.com/tsp.midea.com Note: Product specifications change from time to time as product improvements and developments…