Промышленные сплит-системы MDV серии Quantum - Колонные блоки Quantum MDVIFS-xxxHVR1D/ MDVIFST-xxxHVR1D для моделей MDVIFS-76HVR1D / MDVIFS-96HVR1D / MDVIFS-120HVR1D /, MDVIFS-150HVR1D / MDVIFS-192HVR1D, MDVIFST-76HVR1D / MDVIFST-96HVR1D / MDVIFST-120HVR1D /, MDVIFST-150HVR1D / MDVIFST-192HVR1D. Руководство по ремонту и обслуживанию.
Смотрите также: Руководство по установке и эксплуатации →
Загружаем документ…
Текст инструкции
-
R410A
J Commercial Air Conditioners Service Manual Floor Standing Units
-
Main PCB Ports Floor Standing MDV Indoor Units Figure 3.10: 3.1 Floor Standing main PCB ports Table 3.11: Floor Standing main PCB ports Label in Figure 3.10 Code CN1(L.N) CN22 (ALARM,N,AC2) CN12(H-L) CN29(H-N) Content Port voltage Note AC power input 220V AC Standard 220V AC Standard Reserved 220V…
-
Table 3.11: High Static Pressure Duct main PCB ports (continued)
Label in Code Content Port voltage Note 11 CN-A Sterilization module port 12V DC Reserved 12 CN190 Drainage pump port 12V DC[5] Standard 13 CN26 Communication with wire controller 18V DC[5] Standard 14 CN18 Switch module 5V/12V DC[5] Standard 15 CN14/CN11 Fan module connection 5V DC Standard 16 CN25…
-
2 Indoor unit settings
MDV Indoor Units 2.1 Parameter settings Taking KJR-86S/BK as an example, the parameters can be set in the power-on or power-off state. ①Hold " " and " " for 3 seconds to enter the parameter setting interface, and the main interface will display "CC" ② Spot check a) Wired controller Parameter…
-
Parameter
-
таблицы и схемы — в просмотре
-
Parameter
-
Parameter
Code Parameter Name Parameter Range Default Value 00: Disable Whether energy C17 efficiency attenuation is displayed when Remarks 01: Enable 00/01 00 The setting is valid only when the wired controller is connected to a V8 power off IDU. 00: Disable Whether IDU filter C18 blockage is displayed 01…
-
Table 4.2: Indoor unit Parameter Settings
Paramete r Code Parameter Name Parameter Range Default Value Remarks IDU static pressure level: N00 Static pressure of IDU 00/01/02/03/ The IDU sets the selected corresponding static pressure FF 04/05/06/07/08/ (FF-there may be different default values for different series of indoor units)…
-
Paramete
r Code Parameter Name Parameter Range Default Value Remarks 0-7 3 0-7 indicates 0 - 7°C (The value is accurate to 1°C or 1°F.) 0-10 5 0-10 indicates -4 - 6°C(The value is accurate to 1°C or 1°F.) 00/01 00 T1 temperature N13 difference for auxiliary heat source/alternative heat source to turn on T1…
-
таблицы и схемы — в просмотре
-
Parameter
Code N35 N37 Parameter Name Q4/Q4C air outlet 4 setting One-to-more of wired controller enabled Parameter Range Default Value 00/01 00 00/01 00 Remarks 00 - Free control 01 - Off 00: No 01: Yes 00: Remote off (closed); N38 Remote On/Off port logic of the IDU 01: Remote off (open) 00/01 00 Note: When…
-
Parameter
Code N49 Parameter Name Condensation proof Parameter Range Default Value 00/01 00 Remarks 00: Invalid 01: Valid 00: Invalid N50 Human Detect Sensor 00/01/02 01 01: Used to adjust the set temperature when unattended 02: Used to turn off the unit when unattended 00: 15 min Setting temperature N51…
-
Parameter
Code Parameter Name Parameter Range Default Value 00/01/02 00 Ambient temperature N60 when preheating is Remarks 00: 5°C turned on 01: 0°C 02: (-5)°C 00: Disconnected N61 Fresh air dry contact 1 00/01 00 01: Connected Note: Applicable to FAPU only 00: Disconnected N62 Fresh air dry contact 2 00/01…
-
Parameter
Code Parameter Name Parameter Range Default Value 00/01/02/03/04 00 Remarks Anti-cold wind N74 temperature setting of 00/01/02/03: corresponds to different values; 04: Anti-cold wind disabled special IDUs 00: After the remote shutdown signal is canceled, the IDU runs in the preset mode or based on…
-
Check No
Parameters Remarks 11 Actual RH indoor humidity Actual value = value displayed 12 [―――] is displayed 13 Air discharge pipe temperature Actual value = value displayed 14 Compressor discharge temperature Actual value = value displayed 15 Target superheat Actual value = value displayed 16 EEV opening…
-
2.3 Function Descriptions
2.3.1 Power failure memory function The power failure memory function can be used to ensure that, in the event of a power outage, the indoor units, which was in operation before, automatically restart once the power returns. When the power returns following a power outage, units with Power failure…
-
4 Control
3.1 Temperature Compensation Control Because of the installation position of Indoor Unit and different layout, indoor temperature detected by Indoor Unit may not consist with actual temperature. Indoor temperature could be compensated by controller (The parameter code is”N25” “N26”) 3.2 EEV Control…
-
3.3 Start and Stop Control
Cooling (Dry) Cooling(Dry) T1 − T𝑠 ≥ (0 + ΔTC)℃ T1 − T𝑠 <( − 1 + ΔTC)℃ Enter standby mode when the set temperature is reached Heating T1 − T𝑠 <(0 + ΔTC)℃ Heating T1 − T𝑠 ≥ (1 + ΔTC)℃ Enter standby mode when the set temperature is reached Note: The temperature compensation value (ΔTC) of cooling and…
-
3.4 Fan Control
3.4.1 Fan speeds control The IDU can work in seven-speeds or three-speeds. Seven-speeds When the Indoor Unit detects seven wind speeds the wind speed is set as follows. Sleep Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Auto Three-speeds When the Indoor Unit detects only three wind speeds…
-
Determine the initial fan speed of auto fan control
The initial fan speed is determined according to the difference between ambient indoor temperature (T1) and set temperature (TS), and it updates in the following situations: 1) The first time enter this mode 2) TS is changed 3) When switching between normal operation and silent operation 3.4.3…
-
3.5 Swing control
3.5.1 Horizontal swing control Angle range of horizontal swing Table 6.1: Angle range of horizontal swing heating cooling adjustable range A1+A2 A1+A2 shutdown angle A1+B/A2+C A1+B/A2+C MDV Indoor Units Figure 6.1 Horizontal swing angle 3.5.2 Vertical swing control Figure 6.2 Vertical swing control…
-
3.6 Operation mode control
Outdoor Unit is Heat Pump ①When the mode is set by ODU to VIP priority, Voting priority, Capability requirements priority, Cooling priority, heating priority, the Indoor Unit can be set to cooling, heating, dehumidification, ventilation modes. When the IDU set mode different from the mode of ODU…
-
3.7 Controlling the Condensate Water Pump and Water Level Switch
1) 2) 3) When the IDU is powered on the first time, the water pump is forced to operate for 5 minutes. When the IDU and ODU are in cooling, dehumidification and self-cleaning mode, the water pump starts immediately and operates continuously. After this mode is stopped (stop or mode switch), the…
-
3.10 Remote on/off control
Both IDU’S main control board and 1# Expansion board (Optional) have remote on/off control port Remote on/off control port selection ①Port on IDU’S main control board Port CN55 connects the passive switch signal Note: The port on the main board will be disabled when the port on the expansion board…
-
3.11 Dry mode control
There is a difference between the control with humidity sensor and the control without humidity sensor, when the humidity sensor is damaged, the indoor unit automatically switches to the state without humidity sensor. Without humidity sensor Related settings: ①The temperature of dry mode;②Maximum…
-
Errors and operation code 4.1 Error Code Table Table 7.1: Error code Error Content code Emergency stop E81 A51 Outdoor unit fault F01 b36 Water level switch alarm F11 C21 Abnormal communication between the IDU and ODU F21 E21 E24 Abnormal communication between the IDU and wired controller T0 (fresh…
-
5.1.1 A01 – Emergency shutdown
Digital display Display position Error display Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: stop running, displaying code "A01" (V6 platform indoor Error impact unit displays "A0" code) ODU of the same system: stop running, displaying code "A01" (V6…
-
5.1.2 A51 - ODU fault
Digital display Display position Error display Panel, display box, and wired controller The faulty IDU and other IDUs of the same system: The fan continues running, the EEV is closed, and code "A51" is displayed (V6 platform IDU displays the code "Ed") Error impact ODU of the same system: stops. The…
-
5.1.3 b36 - Water level switch alarm error
Digital display Display position Error display Error impact Error trigger Error recovery Panel, display box, and wired controller The faulty IDU stops. Other IDUs of the same system: operate normally. ODU of the same system: operate normally. The water level switch alarm is triggered when the…
-
Note
1. The plug attached to the WATER port of the main control board corresponds to the following two cases: a. The factory default of IDUs without a water level switch uses a short-circuit plug to seal the WATER port. b. IDUs with a water level switch use a water level switch plug to seal the WATER…
-
5.1.4 C21 - Abnormal communication between IDU and ODU
Digital display Error display Display position Panel, display box, and wired controller Faulty IDU: The fan continues running, and the EEV is closed. Other IDUs of the same system: The fan continues running, the EEV is closed, and error code "A51" is displayed (V6 platform IDU displays the code…
-
If the indoor and outdoor units communicate via HyperLink (M1M2)
Properly connect the cable Cause 2: The repeater UP and DOWN ports are not connected to the corresponding indoor unit (2) Properly connect the cable Cause 3: The power supply of repeater is cut off Check the power supply of the repeater and restore the power supply Cause 4: Communication cables of…
-
Figure 1 Schematic diagram of HyperLink communication cable connection
Upstream IDU and ODU of repeater 1# (including master ODU) Master ODU IDU 10# IDU 1# Repeater 1# Repeater 2# IDU 11# IDU 20# IDU 21# Downstream IDUs of repeater 1# Upstream IDUs of repeater 2# IDU 30# Downstream IDUs of repeater 2# 1) The UP communication port of 1# repeater is connected to the…
-
5.1.5 C51: communication exception between the IDU and wired controller
Note: The error code C51 can be triggered either at the IDU side or the wired controller side. LED display Display position If a powered-on IDU does not receive any message from the wired controller: 1) Wired controller: "C51" is displayed; 2) Panel or display box: The LED display and the error code…
-
MDV Indoor Units
Troubleshooting 36 Cause 1: The communi cation wire does not meet antiinterference requirements Repl ace the communi cation wire that meets anti interference requirements Cause 2: The communi cation wire is bonded and connected or the w ire end metal oxidation exists, leading to the connection fai…
-
5.1.6 E21, E24, E81 - T0 (fresh inlet air temperature sensor) short-circuits or cuts off, T1 (IDU return air temperature sensor) short-circuits or cuts off, and TA (outlet air temperature sensor) short-circuits or cuts off Digital display Display position Error display Error impact Panel, display…
-
sensors are short-circuited or open-circuited, but it is not able to determine if the T1 sensor is short-circuited or open-circuited. 4) Only the master unit needs to be connected to the T1/T0/TA sensors when the AHU kit is MDV Indoor Units installed in parallel. 38
-
5.1.7 F01, F11, F21 - T2A (heat exchanger liquid pipe temperature sensor) short-circuits or cuts off, T2 (heat exchanger middle temperature sensor) short-circuits or cuts off, and T2B (heat exchanger gas pipe temperature sensor) short-circuits or cuts off Digital display Display position Error…
-
5.1.8 U12 - Capacity(HP) code not set
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system: If the address for the faulty IDU has been set, other IDUs will operate normally. Error impact If the address of the faulty IDU was not set…
-
5.1.9 U38 - Address code not detected
Digital display Display position Error display Panel, display box, and wired controller 1) The faulty IDU stops running. 2) Other IDUs of the same system: The fan continues running, the EEV is closed, and ODU error code "A51" Error impact is displayed (V6 platform IDU displays the code "Ed"). ODU of…
-
Appendix 6.1 Temperature Sensor Resistance Characteristics Table 9.1: Indoor temperature sensors resistance characteristics MDV Indoor Units R25=10KΩ±3% 42 B25/50=4100K±3% Temperature Resistance Resistance Resistance Temperature Resistance Resistance Resistance (°C) min(kΩ) Normal(kΩ) max(kΩ) (°C)…
-
Table 9.1: Indoor temperature sensors resistance characteristics(continues)
Resistance Resistance Resistance Temperature Resistance Resistance Resistance (°C) min(kΩ) Normal(kΩ) max(kΩ) (°C) min(kΩ) Normal(kΩ) max(kΩ) 40 4.951 5.175 5.404 80 1.07 1.151 1.235 41 4.745 4.964 5.188 81 1.034 1.113 1.195 42 4.549 4.763 4.982 82 0.999 1.076 1.156 43 4.362 4.571 4.785 83 0.966…
-
S-V8FS