Инструкция на Промышленные сплит-системы MDV серии Quantum: Наружные блоки Quantum MDVOS-xxxCVR1B для моделей MDVOS-68CVR1B, MDVOS-76CVR1B, MDVOS-96CVR1B. Руководство по ремонту и обслуживанию.
Смотрите также: Руководство по установке и эксплуатации →
Загружаем документ…
Текст инструкции
-
R410A
Service Manual Cooling Only Quantum Series Quantum MDVOS-68CVR1B MDVOS-76CVR1B MDVOS-96CVR1B
-
таблицы и схемы — в просмотре
-
Part 1
General Information 1 Indoor and Outdoor Unit Capacities 4 2 External Appearance 5 3 Nomenclature 6 Part 1 – General Information 3
-
1 Indoor and Outdoor Unit Capacities
Outdoor Unit Model MDV Quantum Series Service Manual MDVOS-68HVR1A Indoor Unit Type Indoor Unit Capacity(kW) Number of Indoor Unit Model connectable indoor units High Static Pressure Duct 20 MDVID3-68HVR1D Medium Static Pressure Duct 10 MDVID2-36HVR1D Four-way cassette 10 MDVIC4Y-36HVR1D Ceiling &…
-
2 External Appearance
2.1 Indoor Units Table 1-2.1: Indoor unit appearance Four-way Cassette Wall-mounted Medium Static Pressure Duct High Static Pressure Duct Ceiling & Floor Floor Standing Part 1 – General Information 2.2 Outdoor Units Table 1-2.2: Outdoor unit appearance MDVOS-68CVR1B MDVOS-76CVR1B MDVOS-96CVR1B 5
-
3 Nomenclature
-
Part 2
Component Layout and Refrigerant Circuits 2 Piping Diagrams 9 3 Refrigerant Flow Diagrams 11 7 Part 2 - Component Layout and Refrigerant Circuits 1 Layout of Functional Components 8
-
1 Layout of Functional Components
8 Number Description 1 Compressor 2 High Pressure Switch 3 Oil Separator 4 Heat Exchanger 5 Electronic Expansion Valve 6 Fan 7 Low Pressure Switch 8 Accumulator 9 Stop Valve (Gas Side) 10 Stop Valve (Liquid Side) 11 Heat Exchanger Outlet Temperature Sensor 12 Outdoor Ambient Temperature Sensor 13…
-
2 Piping Diagrams
Figure 2-4.1: 7/8/10HP piping diagram T5 T3 T4 Part 2 - Component Layout and Refrigerant Circuits 7 12 Legend No. Parts name No. Parts name 1 Compressor 13 Solenoid valve SV7 2 High pressure switch T3 Heat exchanger temperature sensor 3 Oil separator T4 Outdoor ambient temperature sensor 4 Heat…
-
Key components
1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Accumulator: Stores liquid refrigerant and oil to protect compressor from liquid hammering. 3. Electronic expansion valve (EXV): Controls…
-
3 Refrigerant Flow Diagrams
Cooling operation Figure 2-3.1: 7-10HP refrigerant flow during cooling operation High temperature,high pressure gas High temperature,high pressure liquid Low temperature,low pressure Fan on 2 T5 6 Unit on Thermostat on Normal control 5 4 T3 T4 Fan off Part 2 - Component Layout and Refrigerant…
-
Oil return operation in cooling mode
Figure 2-3.2: 7-10HP refrigerant flow during oil return operation in cooling mode High temperature,high pressure gas High temperature,high pressure liquid Low temperature,low pressure Fan on 2 T5 6 Unit on Thermostat on Normal control T3 MDV Quantum Series Service Manual T4 Fan off Unit off 300…
-
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated. 2 Stop operation ▪ Abnormal shutdown ▪ System stops MDV Quantum Series Service Manual Thermo on Startup control ▪ Compressor startup delay control ▪ Startup control for cooling operation…
-
2 Stop Operation
The stop operation occurs for one of the three following reasons: 1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with thermo off' operation and an error code is displayed on the outdoor unit digital displays. 2. The system stops when…
-
4 Normal Operation Control
4.1 Component Control during Normal Operation Table 3-4.1: Component control during normal cooling operation Inverter compressor Wiring diagram label COMP Upper DC fan motor Lower DC fan motor Component 7~10HP Control functions and states ● Controlled according to load requirement FAN_UP ● FAN_DOWN…
-
5 Protection Control
5.1 High Pressure Protection Control This control protects the system from abnormally high pressure and protects the compressors from transient spikes in pressure. Figure 3-5.1: High pressure protection control Normal operation Pc > 4.4MPa Pc < 3.2MPa High pressure protection, error code P1 is…
-
5.4 Compressor and Inverter Module Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally high temperatures. Figure 3-5.4: Compressor current protection control Normal operation Current ≥ Currentmax Current < Currentmax Compressor current protection, error code P3 is…
-
6 Special Control
6.1 Oil Return Operation In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that are in standby. Timing of oil…
-
Part 4
Field Settings MDV Quantum Series Service Manual 1 Outdoor Unit Field Settings 21 20
-
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings Figure 4-1.1: Outdoor unit main PCB switches 21
-
Table 4-1.1: Outdoor unit main PCB switch settings
Switch ENC1 Setting Switch positions1 S9-3 Indoor unit address ENC3 S1-1 Description The number of indoor units is in the range 0-15 0-9 on ENC1 indicate 0-9 indoor units; A-F on ENC1 indicate 10-15 indoor units The number of indoor units is in the range 16-31 0-9 on ENC1 indicate 16-25 indoor…
-
1 Outdoor Unit Electric Control Box Layout
MDV Quantum Series Service Manual Figure 5-1.1: Front view of electric control box Figure 5-1.2: Side view of electric control box Figure 5-1.3: Front view of power supply box 24
-
2 Outdoor Unit Main PCB
Part 5 - Electrical Components and Wiring Diagrams 2.1 Ports Figure 5-2.1: Outdoor unit main PCB ports1 ① ② ③ ④ 12 11 ⑤ ⑥
-
Notes
-
2.2 Components
2.2.1 Layout Figure 5-2.2: Outdoor unit main PCB components Display chip Dial switches Dial switches Buttons 2.2.2 Function of buttons SW1 to SW2 Table 5-2.2: Function of buttons SW1 to SW4 Button SW1 (MENU) SW2 (OK) Function Press SW1 for 5s to enter forced cooling, then press for 5s to exit Sport…
-
2.2.4 OK system check button
Before pressing OK button, make sure that the system has been operating steadily for more than one hour. On pressing OK button, the parameters listed in Table 5-2.3 will be displayed in sequence. Table 5-2.3: System check DSP content Normal MDV Quantum Series Service Manual display Parameters…
-
2.2.5 Digital display output
Table 5-2.6: Digital display output in different operating states Outdoor unit state Standby Parameters displayed on DSP The number of indoor units in communication with the outdoor unit Normal operation Frequency limitation code1 and running speed of the compressor in rotations per second Error or…
-
3 Compressor Inverter Module
3.1 Ports Figure 5-3.1: Outdoor unit inverter module ports1 ⑨ ① 3-phase bridge rectifier power input 3-phase bridge MDV Quantum Series Service Manual rectifier power output ⑧ ⑩ ② ③ ④ ⑤ ⑥ Notes: 1. 30 Label descriptions are given in Table 5-3.1. LED ⑦
-
Table 5-3.1: Inverter module ports
Label in Figure 5-2.1 Port code Content Port voltage 1 CN6 Power input L1 of inverter module 380V AC 2 CN7 Power input L2 of inverter module 380V AC 3 CN11 Power input L3 of inverter module 380V AC 4 CN12 Power output U of inverter module to compressor 5 CN13 Power output V of inverter module to…
-
4 Filter Board
4.1 Ports Figure 5-4.1: Outdoor unit filter board ports1 ⑩ ⑨ ⑧ ① ⑦ MDV Quantum Series Service Manual ② ③ Notes: 1. 32 Label descriptions are given in Table 5-4.1. ④ ⑤ ⑥
-
Table 5-4.1: Filter board ports
-
5 Wiring Diagrams
Figure 5-5.1: Wiring diagram INVERTER COMPRESSOR DRIVER BOARD о Фо ® ® lel { reo влкФвше Jon12 [смз |CN14 [98 АСЕАМ DOWN. чих До W(BLUE) BLACK| BLACK) BLACK] is} Bis des du 05 CN6 CNT. | cri) FILTER BOARD [onto (CN9)} смт см см см ea The ground cm N Ls 12 AE Те ом Pou Yar смз wire connects @u the…
-
Part 6
Diagnosis and Troubleshooting Error Code Table 36 2 Troubleshooting 37 3 Appendix to Part Part 6 - Diagnosis and Troubleshooting 1
-
1 Error Code Table
Table 6-1.1: Error code table Error code1 Displayed on the outdoor unit PCB Yes E2 Communication error between indoor and outdoor units Displayed on the outdoor unit PCB No Displayed on the outdoor unit PCB No Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor…
-
2 Troubleshooting
2.1 Warning Warning ▪ All electrical work must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations and other legislation that apply in a…
-
2.2 E1: Phase sequence error
2.2.1 Digital display output 2.2.2 Description ▪ Phase sequence error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.2.3 Trigger / recover condition ▪ Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s. ▪…
-
2.3 E2: Communication error between indoor and outdoor unit
2.3.1 Digital display output 2.3.2 Description ▪ Communication error between indoor and outdoor unit. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.3.4 Possible causes ▪ Communication wires between indoor and outdoor units not connected properly. ▪ Indoor unit…
-
2.3.5 Procedure
E2 Communication wires P Q E have short circuited or disconnected1 Yes Reconnect the communication wires Yes Connect the communication wires in a daisy chain Yes Ensure normal power supply Yes Ensure the wires are connected properly Yes Ensure the communication wires and high voltage wires are…
-
2.4.1 Digital display output 2.4.2 Description ▪ Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.4.3 Trigger / recover condition ▪ Trigger condition: The main…
-
2.4.5 Procedure
E4 Temperature sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor No Temperature sensor has short-circuited or failed2 No MDV Quantum Series Service Manual Replace outdoor main PCB Notes: 1. Outdoor ambient temperature sensor (T4) and heat…
-
2.5 E5: Abnormal power supply voltage
2.5.1 Digital display output 2.5.2 Description ▪ Abnormal power supply voltage. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.5.3 Trigger / recover condition ▪ Trigger condition: Outdoor unit power supply phase voltage < 172V. ▪ Recover condition: Outdoor unit…
-
2.5.5 Procedure
E5 ODU power supply is abnormal or a phase is missing1 Yes Provide normal power supply Yes Ensure the wires are connected properly Yes Replace outdoor filter board No Wires between outdoor main PCB, filter boards and electric control box power supply terminals are loose MDV Quantum Series Service…
-
2.6 E7: Temperature sensor (T5) error
2.6.1 Digital display output 2.6.2 Description ▪ A compressor discharge pipe temperature sensor (T5) error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.6.3 Trigger / recover condition ▪ Trigger condition: Discharge temperature < 10oC for 5 minutes after…
-
2.6.5 Procedure
E7 Temperature sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor No Temperature sensor has short-circuited or failed2 No MDV Quantum Series Service Manual Replace outdoor main PCB Notes: 1. Compressor discharge pipe temperature sensor…
-
2.7 EP: Low ambient temperature protection during cooling
2.7.1 Digital display output 2.7.2 Description ▪ The outdoor ambient temperature sensor (T4) ≤10 oC, ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. Part 6 - Diagnosis and Troubleshooting 2.7.3 Trigger / recover condition ▪ Trigger condition: The outdoor ambient…
-
2.8 H0: Communication error
2.8.1 Digital display output MDV Quantum Series Service Manual 2.8.2 Description ▪ H0 indicates a communication error between the main control chip and the compressor inverter driver chip. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.8.3 Trigger / recover…
-
2.8.5 Procedure
H0 Communication wire from main PCB CN36 to invert module CN8 is loose1 Yes Reconnect the communication wire Yes Check the power supply circuit3 Yes Normal No Both LED1 and LED2 on the inverter module are off when power on2 No Replace outdoor main PCB, is the malfunction solved? NO Part 6…
-
2.9 H4: Inverter module protection
2.9.1 Digital display output 2.9.2 Description ▪ H4 indicates compressor inverter module protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.9.3 Trigger / recover condition ▪ Trigger condition: Compressor appears three…
-
The specific error codes L0, L1, L2 and L4 can also be obtained from the inverter module LED indicators. If an inverter module error has occurred, LED2 is continuously on and LED1 flashes. Figure 6-2.2: LED indicators LED1 and LED2 on inverter module Part 6 - Diagnosis and Troubleshooting Table…
-
2.9.6 L0: Inverter module protection
L0 protection The compressor wiring is connected incorrectly Yes Reconnect the cables based on wiring diagram No Disconnect the power supply The resistance between 3 phases of compressor is over 5Ω Yes Replace the compressor No The insulation resistance of compressor is less than 100kΩ Yes MDV…
-
2.9.7 L1: DC bus low voltage protection
L1 protection Yes The power supply is abnormal Check the power supply equipment No Yes No output from bridge rectifier No The DC bus voltage (P, N) is abnormal 1 Yes The reactor performs well No Replace the reactor Yes Replace the inverter module Note: 1. The normal DC voltage between terminals P…
-
2.9.8 L2: DC bus high voltage protection
L2 protection Yes The power supply is abnormal Check the power supply equipment No The DC bus voltage (P, N) is abnormal 1 Yes Replace the 3-phase bridge rectifier No Replace the inverter module MDV Quantum Series Service Manual Note: 1. The normal DC voltage between terminals P and N on inverter…
-
2.9.9 L4: MCE error
L4 protection ODU ventilation is not good Yes Remove barriers from heat exchanger and air outlet of ODU No ODU stop valves are closed Yes Open the ODU stop valves No Compressor wiring is not properly Yes Reconnect the cables based on wiring diagram Yes Reset the inverter module address and reconnect…
-
2.9.10 L5: Zero speed protection
L5 protection There is abnormal noise of compressor when startup or running Yes Replace the compressor No Replace the inverter module 2.9.11 L7: Phase sequence error MDV Quantum Series Service Manual L7 protection Compressor wiring is loose Yes Reconnect cables based on wiring diagram No Disconnect…
-
2.9.12 L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection L8 protection L9 protection ODU stop valves are closed Yes Open the ODU stop valves No Compressor wiring is not properly Yes Reconnect the cables based on wiring diagram Disconnect the power supply The…
-
2.9.13 Compressor replacement procedure
Step 1: Remove faulty compressor and remove oil ▪ Remove the faulty compressor from the outdoor unit. ▪ Before removing the oil, shake the compressor so as to not allow impurities to remain settled at the bottom. ▪ Drain the oil out of the compressor and retain it for inspection. Normally the oil…
-
Step 8: Vacuum drying and refrigerant charging
▪ Once all the compressors and other components have been fully connected, vacuum dry the system and recharge refrigerant. Figure 6-2.7: Inspecting compressor oil This oil is black This oil is a little - it has been yellow, but is clear carbonized and transparent and the condition is acceptable This…
-
2.10 H7: Unmatched total number of indoor units
2.10.1 Digital display output MDV Quantum Series Service Manual 2.10.2 Description ▪ Number of indoor units detected by the outdoor unit not same as number set on main PCB. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.10.3 Trigger / recover condition ▪ Trigger…
-
2.10.5 Procedure
H7 Number of indoor units set on main PCB not same as actual number of indoor units1 Yes Change the setting on the PCB to be the same as the actual number of indoor units Yes Power on all indoor units Yes Refer to indoor unit troubleshooting guide. Resolving the indoor unit error resolves the…
-
2.11 HF: The indoor and outdoor units does not match
2.11.1 Digital display output 2.11.2 Description ▪ The indoor and outdoor units does not match. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.11.3 Trigger / recover condition ▪ Trigger condition: The indoor and outdoor units does…
-
2.12 P1: Discharge pipe high pressure protection
2.12.1 Digital display output 2.12.2 Description ▪ Discharge pipe high pressure protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.12.3 Trigger / recover condition ▪ Trigger condition: Discharge pressure ≥ 4.4MPa. ▪ Recover condition: Discharge pressure ≤…
-
Excess refrigerant3
Yes Discharge part of the refrigerant. Add oil if it leaks during discharge Yes Flush all refrigerant then vacuum the system and recharge the refrigerant. Add oil to the system if it leaks Yes Inspect the system and fix the error Yes Inspect the system and fix the error No System contains air or…
-
2.13 P2: Suction pipe low pressure protection
2.13.1 Digital display output 2.13.2 Description ▪ Suction pipe low pressure protection. ▪ The system stops running. ▪ Error code is displayed on outdoor unit PCB. Part 6 - Diagnosis and Troubleshooting 2.13.3 Trigger / recover condition ▪ Trigger condition: For P2 protection: Suction pressure ≤…
-
2.13.5 Procedure
P2 / H5 ODU stop valves are closed Yes Open the stop valves Yes Add refrigerant or inspect the system for leaks Yes Inspect the system and fix the error. If the filter is blocked by ice, the piping should be cleaned Yes Inspect the system and fix the error No Insufficient refrigerant caused by…
-
2.14 P3: Compressor current protection
2.14.1 Digital display output 2.14.2 Description ▪ P3 indicates current protection on compressor. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.14.3 Trigger / recover condition ▪ Trigger condition: Current of compressor ATQ580D66UNT ≥ 23A. ▪ Recover condition…
-
Excess refrigerant2
Yes Discharge part of the refrigerant. Add oil if it leaks during discharge Yes Flush all refrigerant then vacuum the system and recharge refrigerant. Add oil to the system if it leaks Yes Inspect the system and fix the error Yes Inspect the system and fix the error Yes Replace the inverter module…
-
2.15 P4: Discharge temperature protection
2.15.1 Digital display output 2.15.2 Description ▪ Discharge temperature protection. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. 2.15.4 Possible causes ▪ Outdoor unit stop valves are closed. ▪ Temperature sensor not connected properly or has malfunctioned. ▪…
-
Insufficient refrigerant caused by
refrigerant leakage3 Yes Add refrigerant and inspect the system for leaks Yes Inspect the system and fix the error. If the filter is blocked by ice, the piping should be cleaned Yes Make sure the combination ratio is less than 130% Yes Flush all refrigerant then vacuum the system and recharge…
-
2.16 P5: Outdoor heat exchanger temperature protection
2.16.1 Digital display output 2.16.2 Description ▪ Outdoor heat exchanger temperature protection. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. 2.16.3 Trigger / recover condition ▪ Trigger condition: Outdoor heat exchanger temperature (T3) ≥ 65oC. ▪ Recover…
-
2.16.5 Procedure
P5 ODU stop valves are closed Yes Open the stop valves Yes Ensure the sensor is connected properly Yes Replace the sensor Yes Make sure the combination ratio is less than 130% Yes Flush all refrigerant then vacuum the system and recharge the refrigerant. Add oil to the system if it leaks Yes Inspect…
-
2.17 PE: Indoor heat exchanger temperature protection
2.17.1 Digital display output 2.17.2 Description ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.17.3 Trigger / recover condition ▪ Trigger condition: Indoor heat exchanger mid-point temperature sensor (T2) ≤2oC for more than 40 minutes or ≤0oC for more than 10…
-
2.18 PL: Inverter module temperature protection
2.18.1 Digital display output MDV Quantum Series Service Manual 2.18.2 Description ▪ PL indicates inverter module temperature protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.18.3 Trigger / recover condition ▪ Trigger condition: Inverter module heat sink…
-
2.18.5 Procedure
PL The inverter module heat sink is blocked or dirty Yes Clean or replace the heat sink Yes Replace the Inverter board No Inverter module temperature sensor (NTC) has short circuited or failed1 No Replace outdoor main PCB 75 Part 6 - Diagnosis and Troubleshooting Notes: 1. Heat sink temperature…
-
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics Table 6-3.1: Outdoor ambient temperature sensor, outdoor heat exchanger temperature sensor, and indoor heat exchanger temperature sensor resistance characteristics Resistance Temperature Resistance Temperature Resistance Temperature Resistance (°C)…
-
Table 6-3.2: Compressor discharge pipe temperature sensor resistance characteristics
Temperature Temperature (°C) Resistance (kΩ) Temperature (°C) Resistance (kΩ) (°C) Resistance (kΩ) -20 542.7 20 68.66 60 13.59 100 3.702 -19 511.9 21 65.62 61 13.11 101 3.595 -18 483.0 22 62.73 62 12.65 102 3.492 -17 455.9 23 59.98 63 12.21 103 3.392 -16 430.5 24 57.37 64 11.79 104 3.296 -15 406.7…
-
Table 6-3.3: Heat sink temperature sensor(NTC)resistance characteristics
-
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 6-3.4 should be observed: ▪ The outdoor unit can detect all the indoor units. ▪ The number of indoor units displayed on DSP is steady and is equal to the actual number of indoor units installed. ▪ All stop valves are open and…
-
Ver. 2025-02