Service
Manual Quantum Series MDVOS-68HVR1A MDVOS-76HVR1A MDVOS-96HVR1A MDVOS-120HVR1A R410A
-
MDV Quantum Series Service Manual
Quantum 50/60Hz 2
-
Part 1
General Information 1 Indoor and Outdoor Unit Capacities 4 2 External Appearance 6 3 Nomenclature 7 Part 1 - General Information 3
-
1 Indoor and Outdoor Unit Capacities
Table 1-1.1 Outdoor Unit Model MDV Quantum Series Service Manual MDVOS-68HVR1A Indoor Unit Type Indoor Unit Capacity(kW) Number of Indoor Unit Model connectable indoor units High Static Pressure Duct 20 MDVID3-68HVR1D Medium Static Pressure Duct 10 MDVID2-36HVR1D Four-way cassette 10 MDVIC4Y-36HVR1D…
-
Outdoor Unit Model
MDVOS-120HVR1A Indoor Unit Type Indoor Unit Capacity(kW) Number of Indoor Unit Model connectable indoor units High Static Pressure Duct 33.5 MDVID3-120HVR1D Floor Standing 33.5 MFSL-120HVR1D Floor Standing 33.5 MFTL-120HVR1D High Static Pressure Duct 18 MDVID3-60HVR1D Four-way cassette 18…
-
2 External Appearance
2.1 Indoor Units MDV Quantum Series Service Manual Table 1-2.1: Indoor unit appearance Four-way Cassette Wall-mounted Medium Static Pressure Duct High Static Pressure Duct Ceiling & Floor Floor Standing 2.2 Outdoor Units Table 1-2.2: Outdoor unit appearance MDVOS-68HVR1A MDVOS-76HVR1A MDVOS-96HVR1A…
-
3 Nomenclature
3.1 Indoor Units MDVI D3 - 68 H V R1 D ○ ○ ○ ○ ○ ○ ○ Legend No. Code Remarks 1 MDVI MDV Indoor unit D3: High Static Pressure Duct WMY: Wall-mounted C: Ceiling & Floor 2 D3 C4Y: Four-way cassette D2: Medium Static Pressure Duct FST: Floor Standing – Top Discharge 3 192 L Capacity index kBtu/h 4 H…
-
3.2 Outdoor Units
-
Part 2
Component Layout and Refrigerant Circuits 2 Refrigerant Flow Diagrams 13 9 Part 2 - Component Layout and Refrigerant Circuits 1 Piping Diagrams 10
-
1 Piping Diagrams
Figure 2-1.1: 7/8/10HP piping diagram 11 SV7 SV2 T5 1 10 Tf T4 5 4 TL 7 6 T3 8 MDV Quantum Series Service Manual Legend 10 No. Parts name No. Parts name 1 Compressor 11 Stop valve (gas side) 2 High pressure switch 12 Stop valve (liquid side) 3 High pressure sensor T3 Heat exchanger temperature…
-
Figure 2-1.2: 12HP piping diagram
11 SV7 SV2 T5 1 10 Tf T4 5 4 TL 7 6 SV4 T3 8 Part 2 - Component Layout and Refrigerant Circuits Legend No. Parts name No. Parts name 1 Compressor 11 Stop valve (gas side) 2 High pressure switch 12 Stop valve (liquid side) 3 High pressure sensor T3 Heat exchanger temperature sensor 4 Oil separator T4…
-
MDV Quantum Series Service Manual
Quantum 50/60Hz Key components: 1. Oil separator: Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation efficiency is up to 99%. 2. Accumulator: Stores liquid refrigerant and oil to protect compressor from liquid hammering. 3. Electronic…
-
2 Refrigerant Flow Diagrams
Cooling operation Figure 2-2.1: Refrigerant flow during cooling operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure 11 Filter SV2 Tf Filter 5 Fan on Filter Unit on Thermostat on Normal control 4 1 Unit on Thermostat on Normal control T5…
-
Heating operation
Figure 2-2.3: Refrigerant flow during heating operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure 11 Filter SV2 Tf Filter 5 Fan on Filter Unit on Thermostat on Normal control 4 1 Unit on Thermostat on Normal control T5 3 T4 10 Fan on…
-
Defrosting operation
Figure 2-2.5: Refrigerant flow during defrosting operation High temperature, high pressure gas High temperature, high pressure liquid Low temperature, low pressure 11 SV7 Filter SV2 12 9 T5 Tf Filter 5 1 480steps 3 T4 10 Unit on Thermostat on Fan on Filter Unit on Thermostat on 480steps 4 TL 7 6 SV4…
-
Мм
Quantum 50/60Hz enue] ad1Asas $эмэ$ шпзиепо AGW 16
-
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated. Stop operation ▪ Abnormal shutdown ▪ System stop 2 Standby control ▪ Crankcase heater control 3 MDV Quantum Series Service Manual Thermo on Startup control ▪ Compressor startup delay…
-
2 Stop Operation
The stop operation occurs for one of the three following reasons: 1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with thermo off' operation and an error code is displayed on the outdoor unit digital displays. 2. The system stops when…
-
4 Startup Control
4.1 Compressor Startup Delay Control In initial startup control and in restart control (except in oil return operation and defrosting operation), compressor startup is delayed such that a minimum of 7 minutes has elapsed since the compressor stopped, in order to prevent frequent compressor on/off…
-
4.3 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode Wiring diagram label 7-12HP Control functions and states Inverter compressor COMP ● Controlled according to load requirement, operating frequency increased by 1 step / sec Upper DC fan motor FAN_UP ● Lower DC fan motor FAN_DOWN ●…
-
5 Normal Operation Control
5.1 Component Control during Normal Operation Table 3-5.1: Component control during normal cooling operation Inverter compressor Wiring diagram label COMP Upper DC fan motor FAN_UP ● Lower DC fan motor FAN_DOWN ● Electronic expansion valve EEV ● Position (steps) from 0 (fully closed) to 480 (fully…
-
5.2 Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor unit first estimates the indoor unit load requirement according to the nominal capacity of indoor units currently running, and then correct for ambient temperature. The compressors…
-
6 Protection Control
6.1 High Pressure Protection Control This control protects the system from abnormally high pressure and protects the compressors from transient spikes in pressure. Figure 3-6.1: High pressure protection control Normal operation Pc > 4.4MPa Pc < 3.2MPa High pressure protection, error code P1 is…
-
6.4 Compressor and Inverter Module Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally high temperatures. Figure 3-6.4: Compressor current protection control Normal operation Current ≥ Currentmax Current < Currentmax Compressor current protection, error code P3 is…
-
7 Special Control
7.1 Oil Return Operation In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that are in standby. When the outdoor…
-
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode Inverter compressor Wiring diagram label COMP Upper DC fan motor FAN_UP ● Lower DC fan motor FAN_DOWN ● Electronic expansion valve EEV1 ● Position 350 (steps) Four-way valve ST1 ● Off SV2 ● Normal control…
-
7.2 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor heat exchanger temperature, indoor heat exchanger temperature and…
-
Part 4
Field Settings 1 Outdoor Unit Field Settings 30 Part 4 - Field Settings 29
-
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings Figure 4-1.2: Outdoor unit main PCB switches PCB switches ENC1 MDV Quantum Series Service Manual SW3 S1 30 ENC3 SW4 SW1 S2 S9 SW2
-
Table 4-1.2: Outdoor unit main PCB switch settings
Switch ENC1 S9-3 ENC3 Setting Number of indoor units Network address Switch positions1 Description The number of indoor units is in the range 0-15 0-9 on ENC1 indicate 0-9 indoor units; A-F on ENC1 indicate 10-15 indoor units The number of indoor units is in the range 16-31 0-9 on ENC1 indicate…
-
1.2 Priority Mode Setting on Main PCB
Priority mode can only be set on the outdoor unit. When an indoor unit is in mode conflict with the outdoor units the unit displays the mode conflict error. The digital display on indoor main PCB will display error code E0. Figure 4-1.2: Indoor unit digital displays Digital display MDV Quantum…
-
Cooling priority mode
Refer to above “1.2. Cooling priority mode” descriptions. First on priority mode: The outdoor unit operates in the mode of the first on indoor unit is being requested. Indoor units that are in a mode different to the first on unit display the mode conflict error. Heating only mode The outdoor unit…
-
Мм
Quantum 50/60Hz enue] ad1Asas $эмэ$ шпзиепо AGW 34
-
1 Outdoor Unit Electric Control Box Layout
Figure 5-1.1: Front view of electric control box Main PCB MDV Quantum Series Service Manual Communication terminals block Power supply terminals Figure 5-1.2: Rear view of electric control box Reactor Inverter module Filter board 36 Inductor
-
2 Outdoor Unit Main PCB
2.1 Ports Figure 5-2.1: Outdoor unit main PCB ports1 ① ② ③ ④ ⑤ ⑥ ⑦ Part 5 - Electrical Components and Wiring Diagrams ⑧ ⑨ 20 ⑩ Notes: 1. Label descriptions are given in Table 5-2.1. 13 37
-
Table 5-2.1: Main PCB ports
-
2.2 Components
2.2.1 Layout Figure 5-2.2: Outdoor unit main PCB components Display Part 5 - Electrical Components and Wiring Diagrams Main control chip Dial switches Dial switches Buttons 2.2.2 Function of buttons Table 5-2.2: Function of buttons SW1 to SW4 Button Function SW3 (UP) In menu mode: previous and next…
-
2.2.3 Menu mode
1. Long press SW1 “MENU” button for 5 seconds to enter menu mode, and the digital display displays “n1”; 2. Press SW3 / SW4 “UP / DOWN” button to select the first level menu “n1”, “n2”, “n3”, “n4”, “nb” or “nF”; 3. Press SW2 “OK” button to enter specified first level menu, for example, enter “n3”…
-
Menu mode function
Table 5-2.3: Menu mode function Digital display Menu mode content Remarks n14 Force cooling mode All indoor units running in cooling mode n16 Maintenance mode The system does not check the indoor units’ number. n27 Vacuum mode n31 History error codes n32 Cleaning history error codes n34 Factory…
-
2.2.4 System check button
Before pressing UP or DOWN button, make sure that the system has been operating steadily for more than one hour. On pressing UP or DOWN button, the parameters listed in Table 5-2.5 will be displayed in sequence. Table 5-2.5: System check MDV Quantum Series Service Manual DSP content Parameters…
-
2.2.5 Digital display output
Table 5-2.6: Digital display output in different operating states Outdoor unit state Standby Parameters displayed on DSP The number of indoor units in communication with the outdoor unit Normal operation Frequency limitation code1 and running speed of the compressor in rotations per second Error or…
-
3 Compressor Inverter Module and Filter Board
3.1 Inverter module ports Figure 5-3.1: Outdoor unit inverter module ports1 ⑨ ① 3-phase bridge MDV Quantum Series Service Manual rectifier power input 3-phase bridge rectifier power output ⑧ ⑩ ② ③ ④ ⑤ ⑥ Notes: 1. 44 Label descriptions are given in Table 5-3.1. LED ⑦
-
Table 5-3.1: Inverter module ports
Label in Figure 5-2.1 Port code Content Port voltage 1 CN6 Power input L1 of inverter module 380V AC 2 CN7 Power input L2 of inverter module 380V AC 3 CN11 Power input L3 of inverter module 380V AC 4 CN12 Power output U of inverter module to compressor 5 CN13 Power output V of inverter module to…
-
3.2 Filter board ports
Figure 5-3.2: Outdoor unit filter board ports1 ⑨ ⑩ ⑧ ① ⑦ MDV Quantum Series Service Manual 11 ② ③ Notes: 1. 46 Label descriptions are given in Table 5-3.3. ④ ⑤ ⑥
-
Table 5-3.3: Filter board ports
-
4 Wiring Diagrams
MDV Quantum Series Service Manual Figure 5-4.1: Wiring diagram 48
-
Part 6
Diagnosis and Troubleshooting 1 Error Code Table 50 3 Appendix to Part Part 6 - Diagnosis and Troubleshooting 2 Troubleshooting 51
-
1 Error Code Table
Table 6-1.1: Error code table Error Content code1 Displayed on the outdoor unit PCB Yes E2 Communication error between indoor and outdoor units Displayed on the outdoor unit PCB No Displayed on the outdoor unit PCB No Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient…
-
2 Troubleshooting
2.1 Warning Warning ▪ All electrical work must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations and other legislation that apply in a…
-
2.2 E1: Phase sequence error
2.2.1 Digital display output 2.2.2 Description ▪ Phase sequence error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.2.3 Trigger / recover condition ▪ Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s. ▪…
-
2.2.5 Procedure
E1 The phase sequence of the 3-phase power supply is incrorrect1 Yes Exchange any two of the 3 phase wires Yes Ensure all supply terminals are securely fastened Yes Check the power supply equipment No Some power supply terminals are loose2 No No Replace outdoor main PCB Notes: 1. The L1, L2, L3…
-
2.3 E2: Communication error between indoor and outdoor unit
2.3.1 Digital display output MDV Quantum Series Service Manual 2.3.2 Description ▪ Communication error between indoor and outdoor unit. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.3.3 Trigger / recover condition ▪ Trigger condition: Indoor units and the outdoor…
-
2.3.5 Procedure
E2 Communication wires P Q E have short circuited or disconnected1 Yes Reconnect the communication wires Yes Connect the communication wires in a daisy chain Yes Ensure normal power supply Yes Ensure the wires are connected properly Yes Ensure the communication wires and high voltage wires are…
-
2.4.1 Digital display output 2.4.2 Description ▪ Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.4.3 Trigger / recover condition ▪…
-
2.4.5 Procedure
E4 Temperature sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor No Temperature sensor has short-circuited or failed2 No Replace outdoor main PCB 57 Part 6 - Diagnosis and Troubleshooting Notes: 1. Outdoor ambient temperature sensor (T4) and…
-
2.5 E5: Abnormal power supply voltage
2.5.1 Digital display output 2.5.2 Description ▪ Abnormal power supply voltage. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.5.3 Trigger / recover condition ▪ Trigger condition: Outdoor unit power supply phase voltage < 172V. ▪…
-
2.5.5 Procedure
E5 ODU power supply is abnormal or a phase is missing1 Yes Provide normal power supply Yes Ensure the wires are connected properly Yes Replace outdoor filter board No Wires between outdoor main PCB, filter boards and electric control box power supply terminals are loose No Part 6 - Diagnosis and…
-
2.6.1 Digital display output MDV Quantum Series Service Manual 2.6.2 Description ▪ DC fan motor error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.6.3 Trigger / recover condition ▪ Trigger condition: For E6 protection: Actual fan speed is < 120 rps more than 20S…
-
2.6.5 Procedure
E6, Eb DC fan motor connection on main PCB or filter board is loose1 Yes Ensure the wires are connected properly Yes Replace the filter board No The voltage of CN53 terminals is 310V No Replace the DC fan motor, the problem is solved? Replace outdoor main PCB Notes: 1. DC fan motor connections on…
-
2.7 E7: Temperature sensor (T5) error
2.7.1 Digital display output 2.7.2 Description ▪ A compressor discharge pipe temperature sensor (T5) error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.7.3 Trigger / recover condition ▪ Trigger condition: Discharge temperature <…
-
2.7.5 Procedure
E7 Temperature sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor No Temperature sensor has short-circuited or failed2 No Replace outdoor main PCB 63 Part 6 - Diagnosis and Troubleshooting Notes: 1. Compressor discharge pipe temperature sensor…
-
2.8 EH: Outdoor refrigerant cooling pipe temperature sensor (TL) error
2.8.1 Digital display output 2.8.2 Description ▪ An outdoor refrigerant cooling pipe temperature sensor (TL) error. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.8.3 Trigger / recover condition ▪ Trigger condition: The main control…
-
2.8.5 Procedure
EH Refrigerant cooling pipe temperature sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor No Refrigerant cooling pipe temperature sensor has short-circuited or failed2 No Replace outdoor main PCB 65 Part 6 - Diagnosis and Troubleshooting…
-
2.9 F1: DC bus voltage error
2.9.1 Digital display output 2.9.2 Description ▪ F1 indicates compressor DC bus voltage error. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. MDV Quantum Series Service Manual 2.9.3 Trigger / recover condition ▪ Trigger condition: DC bus voltage < 200V continuously…
-
2.9.5 Procedure
F1 error Compressor inverter module wiring is loosened Yes Reconnect cables based on wiring diagram Yes Reconnect the reactor and DC bus wire based on wiring diagram Yes Check the power supply equipment No Disconnect the power supply Reactor and DC bus wiring is incorrectly 1 No The power supply is…
-
2.10 H0: Communication error
2.10.1 Digital display output 2.10.2 Description ▪ H0 indicates a communication error between the main control chip and the compressor inverter driver chip. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.10.3 Trigger / recover…
-
2.10.5 Procedure
H0 Communication wire from main PCB CN36 to invert module CN8 is loose1 Yes Reconnect the communication wire Yes Check the power supply circuit3 Yes Normal No Both LED1 and LED2 on the inverter module are off when power on2 No Replace outdoor main PCB, is the malfunction solved? NO Part 6…
-
2.11 H4: Inverter module protection
2.11.1 Digital display output 2.11.2 Description ▪ H4 indicates compressor inverter module protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. MDV Quantum Series Service Manual 2.11.3 Trigger / recover condition ▪ Trigger condition: Compressor appears three…
-
The specific error codes L0, L1, L2 and L4 can also be obtained from the inverter module LED indicators. If an inverter module error has occurred, LED2 is continuously on and LED1 flashes. Figure 6-2.2: LED indicators LED1 and LED2 on inverter module Part 6 - Diagnosis and Troubleshooting Table…
-
2.11.6 L0: Inverter module protection
L0 protection The compressor wiring is connected incorrectly Yes Reconnect the cables based on wiring diagram No Disconnect the power supply The resistance between 3 phases of compressor is over 5Ω Yes Replace the compressor No The insulation resistance of compressor is less than 100kΩ Yes MDV…
-
2.11.7 L1: DC bus low voltage protection
L1 protection Yes The power supply is abnormal Check the power supply equipment No Yes No output from bridge rectifier No The DC bus voltage (P, N) is abnormal 1 Yes The reactor performs well No Replace the reactor Replace the inverter module Yes Note: 1. The normal DC voltage between terminals P…
-
2.11.8 L2: DC bus high voltage protection
L2 protection Yes The power supply is abnormal Check the power supply equipment No The DC bus voltage (P, N) is abnormal 1 Yes Replace the 3-phase bridge rectifier No Replace the inverter module MDV Quantum Series Service Manual Note: 1. The normal DC voltage between terminals P and N on inverter…
-
2.11.9 L4: MCE error
L4 protection ODU ventilation is not good Yes Remove barriers from heat exchanger and air outlet of ODU No ODU stop valves are closed Yes Open the ODU stop valves No Compressor wiring is not properly Yes Reconnect the cables based on wiring diagram Yes Reset the inverter module address and reconnect…
-
2.11.10 L5: Zero speed protection
L5 protection There is abnormal noise of compressor when startup or running No MDV Quantum Series Service Manual Replace the inverter module 76 Yes Replace the compressor
-
2.11.11 L7: Phase sequence error
L7 protection Compressor wiring is loose Yes Reconnect cables based on wiring diagram No Disconnect the power supply An open circuit in the 3-phase U/V/W of compressor terminals Yes Replace the compressor No Replace the inverter module Part 6 - Diagnosis and Troubleshooting 77
-
2.11.12 L8: Compressor frequency variation greater than 15Hz within one second protection
L9: Actual compressor frequency differs from target frequency by more than 15Hz protection L8 protection L9 protection ODU stop valves are closed Yes Open the ODU stop valves No Compressor wiring is not properly Yes Reconnect the cables based on wiring diagram MDV Quantum Series Service Manual No…
-
2.11.13 Compressor replacement procedure
Step 1: Remove faulty compressor and remove oil ▪ Remove the faulty compressor from the outdoor unit. ▪ Before removing the oil, shake the compressor so as to not allow impurities to remain settled at the bottom. ▪ Drain the oil out of the compressor and retain it for inspection. Normally the oil…
-
Figure 6-2.7: Inspecting compressor oil
This oil is black This oil is a little - it has been yellow, but is clear carbonized and transparent and the condition is acceptable This oil is still transparent but there are impurities which Cloudy or gray may clog the filter oil indicates abnormal system MDV Quantum Series Service Manual…
-
2.12 H7: Unmatched total number of indoor units
2.12.1 Digital display output 2.12.2 Description ▪ Number of indoor units detected by the outdoor unit not same as number set on main PCB. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.12.4 Possible causes ▪ Number of indoor units set on main PCB not same as actual…
-
2.12.5 Procedure
H7 Number of indoor units set on main PCB not same as actual number of indoor units1 Yes Change the setting on the PCB to be the same as the actual number of indoor units Yes Power on all indoor units Yes Refer to indoor unit troubleshooting guide. Resolving the indoor unit error resolves the…
-
2.13 H8: High pressure sensor error
2.13.1 Digital display output 2.13.2 Description ▪ High pressure sensor error. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. 2.13.3 Trigger / recover condition ▪ Trigger condition: Discharge pressure ≤ 0.3MPa. ▪ Recover condition: Discharge pressure > 0.3MPa. ▪…
-
2.13.5 Procedure
H8 High pressure sensor connection on main PCB is loose1 Yes Ensure the sensor is connected properly Yes Replace the sensor Yes Add refrigerant and inspect system for leaks Yes Inspect the system and fix the error. If the filter is blocked by ice, the piping should be cleaned Yes Inspect the system…
-
2.14 P1: Discharge pipe high pressure protection
2.14.1 Digital display output 2.14.2 Description ▪ Discharge pipe high pressure protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.14.3 Trigger / recover condition ▪ Trigger condition: Discharge pressure ≥ 4.4MPa. ▪ Recover condition: Discharge pressure ≤…
-
Excess refrigerant3
Yes Discharge part of the refrigerant. Add oil if it leaks during discharge Yes Flush all refrigerant then vacuum the system and recharge the refrigerant. Add oil to the system if it leaks Yes Inspect the system and fix the error Yes Inspect the system and fix the error No System contains air or…
-
2.15 P2, H5: Suction pipe low pressure protection
2.15.1 Digital display output 2.15.2 Description ▪ Suction pipe low pressure protection. ▪ The system stops running. ▪ Error code is displayed on outdoor unit PCB. Part 6 - Diagnosis and Troubleshooting 2.15.3 Trigger / recover condition ▪ Trigger condition: For P2 protection: Suction pressure ≤…
-
2.15.5 Procedure
P2 / H5 ODU stop valves are closed Yes Open the stop valves Yes Add refrigerant or inspect the system for leaks Yes Inspect the system and fix the error. If the filter is blocked by ice, the piping should be cleaned Yes Inspect the system and fix the error No Insufficient refrigerant caused by…
-
2.16 P3: Compressor current protection
2.16.1 Digital display output 2.16.2 Description ▪ P3 indicates current protection on compressor. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. 2.16.3 Trigger / recover condition ▪ Trigger condition: Current of compressor LNB65FAGMC ≥ 29A. ▪ Recover condition…
-
Excess refrigerant2
Yes Discharge part of the refrigerant. Add oil if it leaks during discharge Yes Flush all refrigerant then vacuum the system and recharge refrigerant. Add oil to the system if it leaks Yes Inspect the system and fix the error Yes Inspect the system and fix the error Yes Replace the inverter module…
-
2.17 P4: Discharge temperature protection
2.17.1 Digital display output 2.17.2 Description ▪ Discharge temperature protection. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. 2.17.4 Possible causes ▪ Outdoor unit stop valves are closed. ▪ Temperature sensor/switch not properly or has malfunctioned. ▪…
-
Insufficient refrigerant caused by
refrigerant leakage3 Yes Add refrigerant and inspect the system for leaks Yes Inspect the system and fix the error. If the filter is blocked by ice, the piping should be cleaned Yes Make sure the combination ratio is less than 130% Yes Flush all refrigerant then vacuum the system and recharge…
-
2.18 P5: Outdoor heat exchanger temperature protection
2.18.1 Digital display output 2.18.2 Description ▪ Outdoor heat exchanger temperature protection. ▪ The system stops running. ▪ Error code is displayed on the unit with the error. 2.18.3 Trigger / recover condition ▪ Trigger condition: Outdoor heat exchanger temperature (T3) ≥ 65oC. ▪ Recover…
-
2.18.5 Procedure
P5 ODU stop valves are closed Yes Open the stop valves Yes Ensure the sensor is connected properly Yes Replace the sensor Yes Make sure the combination ratio is less than 130% Yes Flush all refrigerant then vacuum the system and recharge the refrigerant. Add oil to the system if it leaks Yes Inspect…
-
2.19 P8: Typhoon protection
2.19.1 Digital display output 2.19.2 Description ▪ P8 indicates strong wind protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. Part 6 - Diagnosis and Troubleshooting 2.19.3 Trigger / recover condition ▪ Trigger condition: Fan speed ≥400rps when the outdoor…
-
2.19.5 Procedure
P8 There is strong wind around the outdoor unit No Replace the DC fan motor, the problem is solved? No MDV Quantum Series Service Manual Replace outdoor main PCB Notes: 1. P8 protection recovers in 2 minutes when the strong wind stops. 96 Yes Wait unit the strong wind stops1
-
2.20 PL: Inverter module temperature protection
2.20.1 Digital display output 2.20.2 Description ▪ PL indicates inverter module temperature protection. ▪ The system stops running. ▪ Error code is displayed on the outdoor unit PCB. Part 6 - Diagnosis and Troubleshooting 2.20.3 Trigger / recover condition ▪ Trigger condition: Inverter module heat…
-
2.20.5 Procedure
PL The inverter module heat sink is blocked or dirty Yes Clean or replace the heat sink Yes Tighten the screws and make sure the heat sink is well-connected Yes Ensure the sensor is connected properly Yes Replace the sensor No The screws connecting the heat sink to the inverter module are loose No…
-
3 Appendix to Part 6
3.1 Temperature Sensor Resistance Characteristics Table 6-3.1: Outdoor ambient temperature sensor, outdoor heat exchanger temperature sensor and refrigerant cooling pipe temperature sensor resistance characteristics Resistance Temperature Resistance Temperature Resistance Temperature Resistance (°C)…
-
Table 6-3.2: Compressor discharge pipe temperature sensor resistance characteristics
MDV Quantum Series Service Manual Temperature 100 Temperature (°C) Resistance (kΩ) Temperature (°C) Resistance (kΩ) Temperature (°C) Resistance (kΩ) (°C) Resistance (kΩ) -30 913.239 16 83.541 62 12.809 108 2.918 -29 862.001 -28 813.806 17 79.801 63 12.357 109 2.835 18 76.248 64 11.923 110 2.755 -27…
-
Table 6-3.3: Heat sink temperature sensor resistance characteristics
Temperature Temperature (°C) Resistance (kΩ) Temperature (°C) Resistance (kΩ) (°C) Resistance (kΩ) -30 971.4 10 109.0 50 19.70 90 5.000 -29 912.8 11 103.9 51 18.97 91 4.855 -28 858.2 12 99.02 52 18.26 92 4.705 -27 807.3 13 94.44 53 17.59 93 4.566 -26 759.7 14 90.11 54 16.94 94 4.431 -25 715.3 15…
-
3.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 6-3.4 and 6-3.5 should be observed: ▪ The outdoor unit can detect all the indoor units. ▪ The number of indoor units displayed on DSP is steady and is equal to the actual number of indoor units installed. ▪ All stop valves are…
-
Ver. 2025-2