1. Introduction
Fan coil unit is a kind of compound device which assemble fan and heat exchanger (coil) together. Fan coil with fresh air supply system is a main type of central air-conditioner system, so it is an important component of AC devices. A cooling (heating) supply system usually consists of fan coil…
-
4. External Appearance
Product Schedule 3
-
5. Features
1. 2. 3. 4. 5. 6. 7. Wide external static pressure supplying. Two external static pressure (12Pa/30Pa) settings for added flexibility. Left or right hand piping connections, field convertible. Quiet operation A patent design is able to prevent abnormal noise caused by blowing fins. Superior air…
-
Third-generation 2-row Ducted FCU Washable filter Iron frame filter is standard, and aluminum frame filter can be customized. Air outlet flange and multi-direction pull-out filter can be customized. 10. Optional wired controller Optional wired controller offers simple and flexibility in controlling…
-
6. Specifications
Model MDKT2 200G12 300G12 400G12 200G30 300G30 400G30 200EG30 300EG30 400EG30 H/M/L m /h 3 340/255/170 510/385/255 680/510/340 H/M/L CFM 200/150/100 300/225/150 400/300/200 Air flow External Static pressure Pa Capacity Cooling G12 models: 12; G30 models: 30 H/M/L kW 2/1.74/1.52 2.7/2.31/2.03…
-
Specifications
Model MDKT2 500G12 600G12 800G12 500G30 600G30 800G30 500EG30 600EG30 800EG30 H/M/L m /h 3 850/640/425 1020/765/510 1360/1020/680 H/M/L CFM 500/375/250 600/450/300 800/600/400 Air flow External Static pressure Pa Capacity Cooling G12 models: 12; G30 models: 30 H/M/L kW 4.4/3.74/3.25 5.5/4.58/4.09…
-
таблицы и схемы — в просмотре
-
7. Dimensions
F A B (Air return port) Electriccontrol box Intlet Outlet Air exhaust valve Condensation water drainingport 4-10X16Hoisting hole Unit: mm Model 200-Model 300-Model A 545 645 B 484 C 400-Model 600-Model 800-Model 1000-Model 1200-Model 1400-Model 745 965 1265 1370 1660 1826 1205 1310 1600 1766 1233…
-
8. Wiring Diagrams
G30 Motor Red Orange Yellow Orange Red Yellow Blue Yellow/green Low speed Blue 2 Medium speed 1 High speed Black Black Motor Earth wire Zero line Power Three-speed switch Live line Note: Black: supper high fan speed; Orange: high fan speed; Blue: medium fan speed; Yellow: low fan speed. Terminal…
-
Wiring diagrams
G30 Motor Black 3 Red Yellow Blue Black Red Yellow Blue Yellow/green Low speed High speed 1 Medium speed Orange Orange Motor Earth wire Zero line Power Three-speed switch Live line Note: Black: supper high fan speed; Orange: high fan speed; Blue: medium fan speed; Yellow: low fan speed. Terminal…
-
9. Capacity Tables
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Heating Capacities (with fan at high speed and 12Pa/30Pa static pressure for relative models)
Remark: Δt:WaterTemperature Difference (℃) ; 3 TH: Total Heating Capacity (kW);WF: Water Flow (m /h);WPD: Water Pressure Drop (kPa) Air inlet temp. (20℃ DB) Model Water inlet temp. (℃) Δt 1000 1200 1400 TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD 10 0.50 0.04 0.1 1.76 0.15 1.0 3.08…
-
10.Static Pressure Graphs
200G12 200G30 Static pressure,Pa Static pressure,Pa How to read the diagram: The vertical axis is the External Static Pressure (Pa) while the horizontal axis represents the Air Flow (m3/h). The fan performance curves are for the“1-Super High”, “2-High”, “3-Medium” and “4-Low” fan speed. The dotted…
-
Static pressure graphs
-
1000G12
-
11. Exploded Views
200G12 200G30 No. Part Name Quantity 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 1 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporator ass'y 1 11 Right panel 1 12 Middle clapboard assy 1 13 Rear below cover…
-
300G12
600G12 Third-generation 2-row Ducted FCU 300G30 600G30 No. 400G12 Part 400G30 500G12 Name Quantity 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 2 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporator ass'y 1 11…
-
800G12
1400G12 Third-generation 2-row Ducted FCU 800G30 1400G30 No. 1000G12 Part 1000G30 1200G12 1200G30 Name Quantity 1 Top panel assy 1 2 Motor ass'y 2 3 Fan ass'y 4 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9 Drain tray assy 1 10…
-
12. Installation
12.1 Installing site Install the unit where installation and maintenance space is enough. Install the unit where the ceiling is horizontal and enough to bear the weight of the indoor unit. Install the unit where the air inlet and outlet are not baffled and are the least affected by external…
-
Old concrete roughcast
Use embedded bolts and embedded pulling plugs. Steel beam and girder structure: Set and use supportive angle steel. New concrete roughcast: Set it with embedded bushes or embedded bolts. 2) Suspending the indoor unit Use tools such as pulleys to hoist the indoor unit to the pendant bolt. Use…
-
Two grooves
The extended drain pan Rope Push it this way Water pipes Please hang up the extended drain pan to the pipes or ceiling by a rope. 12.4Installing water pipe With air release valve, the other side is water inlet pipe. When connect water collector, set the tightening torque to 6180~7540N.cm…
-
2. Drain test
Before the test, ensure that the drain pipes are smooth and the adapters are sealed. Newly built rooms should undergo the drain test before the ceiling is laid. 12.6 Wiring installation CAUTIONS: The air conditioner should use separate power supply with rated voltage. The external power…
-
13. Accessories
13.1 Standard accessories Accessory name Qty. Shape Usage Owner’s & installation manual 1 / Installation guide Extended drain pan 1 Connect drain water from valve kit 13.2 Optional accessories Accessory name PCB control kit CE-FCUKZ-01 Remote controller R05/BGE Remote controller R51/E Wired…
-
1. Specifications
Model CE-FCUKZ-01 CE-FCUKZ-02 Available appliance 2-pipe ducted FCU 4-pipe ducted FCU Power supply 220-240V-1Ph-50Hz Operation range Room temperature 17℃-30℃ Inlet water temperature 3℃-75℃ Temperature controlling precision ±1℃ Dimension (W×H×D) 310×76×290 Packing Size (W×H×D) 384×174×359 2. Internal…
-
5. Address setting
Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner in LAN is set by code switch on Network Interface Module (NIM), and the set range is 0-63. Functions of cold-air proof and heat-air proof can be selected. 6. Trouble-shooting…
-
E2: T2 evaporator sensor malfunction
T2 Connecting wire between sensor Exist Reconnect and ensure that the and mainboard gets loose connection is reliable. OK Exist Temperature sensor Replace sensor is short-circuited or punctured OK Error Chip fault, or chip foot sheds off, or chip is Reinstall chip, or install other chip with same…
-
13.2.2 Optional remote controller : R05/BGE
1. Part names Operation section Display section Accessories 41
-
2. How to operate
1. MODE: Once pressing, running mode will be selected in the following sequence: AUT TO → COOL → DRY Y → HEAT → FA AN NOTE: No heating mode for cool only type unit. 2. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO →LOW →M ED →HIGH 3. Adjust: Decrease the…
-
13.2.3 Optional remote controller : R51/E
1. Part names 2. How to operate 1. TEMP DOWN Button: Push the TEMP DOWN button to decrease the indoor temperature setting or to adjust the timer in a counter-clockwise direction. 2. MODLE SELECT Button: Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY…
-
13.2.4 Optional wired controller for ducted units without electric heater :KJR-18B/E
1. Models KJR-18B/E is a thermostat that has developed into 4 types. Each type has its own features to suit different environment. Models Features KJR-18B/E-A Only control 3-speed fan, when the temperature reaches the set-point, it will close the Fan. KJR-18B/E-B KJR-18B/E-C KJR-18B/E-D Control…
-
Third-generation 2-row Ducted FCU Install the back base 4) 4. Wiring diagrams : KJR-18B/E-A KJR-18B/E-B KJR-18B/E-C Wire Connection KJR-18B/E-D N(220VAC) N(220VAC) L (220VAC) L (220VAC) Valve Val 2 Val 1 Fan L N Val Hi Med Fan Low Val2 Val1 L 2-wireNCvalve system Val1: For heating Val2: For cooling…
-
KJR-21B/D is available for ducted FCU with electric heater. It has large LCD
display which can dispaly: working mode (cooling, heating and ventilation), fan speed, room temperature, setting temperature, etc. The buttons on the panel are : on/off ( ) , mode exchange ( M ), timer (), fan speed ( ) and temperature adjustment () Function : Specifications : Available for…
-
Wiring diagram
220V AC 50Hz N L L RH Thermostat Touching machine Val Aux heating Valve Low Med Hi Fan N How to operate On/off Press“ ”to turn on, press“ ”again to turn off. Temperature Press“”to reduce temperature,press“” to raise temperature;each time, temperature will change 1℃. setting Cooling Press “M” until…
-
13.2.6 Optional central controller: CCM03
-
Accessories
Third-generation 2-row Ducted FCU 49
-
Liquid crystal matrix display description
1. 2. 3. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure). The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+ and 48+ on the left Side, which indicate…
-
Query page description
1) 2) 3) The LCD displays the query page, and the air conditioner with the address of 08 is being queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature 22°C, set temperature 20°C, cooling mode “lock”. In the matrix, only the big and small…