Инструкция на Фанкойлы MDV (сервис мануалы)
Фанкойлы канального типа MDV серии MDKT3 G. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. Introduction
Fan coil unit is a kind of compound device which assemble fan and heat exchanger (coil) together. Fan coil with fresh air supply system is a main type of central air-conditioner system, so it is an important component of AC devices. A cooling (heating) supply system usually consists of fan coil…
-
3. Product Schedule
Model Air volume External static pressure (CFM) (Pa) MKT3-200G12 200 MKT3-300G12 300 MKT3-400G12 400 MKT3-500G12 500 MKT3-600G12 600 MKT3-800G12 800 MKT3-1000G12 1000 MKT3-1200G12 1200 MKT3-1400G12 1400 MKT3-200G30 200 MKT3-300G30 300 MKT3-400G30 400 MKT3-500G30 500 MKT3-600G30 600 MKT3-800G30 800…
-
5. Features
1. 2. 3. 4. 5. 6. 7. Wider external static pressure supplying. 12Pa and 30Pa ESP are standard, 50 Pa can be customized. Left or right hand piping connections, field convertible. Quiet operation A patent design is able to prevent abnormal noise caused by blowing fins. Superior air distribution As the…
-
Third-generation 3-row Ducted FCU Washable filter Iron frame filter is standard and aluminum frame filter can be customized. Air outlet flange and multi-direction pull-out filter can be customized. 10. Optional wired controller Optional wired controller offers simple and flexibility in controlling…
-
6. Specifications
Model MKT3- 200G12 300G12 400G12 200G30 300G30 400G30 200EG30 300EG30 400EG30 H/M/L m /h 3 340/255/170 510/385/255 680/510/340 H/M/L CFM 200/150/100 300/225/150 400/300/200 Air flow External Static pressure Pa Capacity Cooling G12 models: 12; G30 models: 30 H/M/L kW 2.2/1.9/1.68 3.1/2.7/2.3…
-
Specifications
Model MKT3- 500G12 600G12 800G12 500G30 600G30 800G30 500EG30 600EG30 800EG30 H/M/L m /h 3 850/640/425 1020/765/510 1360/1020/680 H/M/L CFM 500/375/250 600/450/300 800/600/400 Air flow External Static pressure Pa Capacity Cooling G12 models: 12; G30 models: 30 H/M/L kW 4.6/3.96/3.45 5.8/4.88/4.45…
-
Specifications
Model MKT3- 1000G12 1200G12 1400G12 1000G30 1200G30 1400G30 1000EG30 1200EG30 1400EG30 H/M/L m /h 3 1700/1275/850 2040/1530/1020 2380/1785/1190 H/M/L CFM 1000/750/500 1200/900/600 1400/1050/700 Air flow External Static pressure Pa Capacity Cooling G12 models: 12; G30 models: 30 H/M/L kW 9/7.8/6.57…
-
7. Dimensions
F A B (Air return port) Electriccontrol box Intlet Outlet Air exhaust valve Condensation water drainingport 4-10X16Hoisting hole Unit: mm Model 200-Model 300-Model A 545 645 B 484 C 400-Model 600-Model 800-Model 1000-Model 1200-Model 1400-Model 745 965 1265 1370 1660 1826 1205 1310 1600 1766 1233…
-
8. Wiring Diagrams
MKT3-200G12; MKT3-300G12; MKT3-400G12; MKT3-500G12; MKT3-600G12; MKT3-1000G12; MKT3-1300G12; MKT3-1400G30 (reserved high fan speed) Motor Orange 3 Red Yellow 4 5 Orange Red Yellow Blue Black Motor Yellow/green Low speed Blue Medium speed Black 2 High speed 1 MKT3-800G12; Earth wire Zero line Power…
-
Wiring diagrams
MKT3-200G30; MKT3-300G30; MKT3-400G30; MKT3-500G30; MKT3-600G30; MKT3-1000G30; MKT3-1200G30; MKT3-1400G12 (reserved super high fan speed) Motor Black 3 Red Yellow 4 5 Black Red Yellow Blue Orange Motor Yellow/green Low speed Blue 2 Medium speed Orange High speed 1 MKT3-800G30; Earth wire Zero line…
-
Wiring diagrams
MKT3-200EG30; MKT3-300EG30; MKT3-400EG30; MKT3-500EG30; MKT3-600EG30; MKT3-800EG30; MKT3-1000EG30; MKT3-1200EG30 (reserved super high fan speed) 12 Wiring Diagrams
-
Wiring diagrams
MKT3-1400EG30 (reserved high fan speed) Wiring Diagrams 13
-
9. Capacity Tables
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Cooling Capacities
-
таблицы и схемы — в просмотре
-
Heating Capacities (with fan at high speed and 12Pa/30Pa static pressure for relative models)
Remark: Δt:WaterTemperature Difference (℃) ; 3 TH: Total Heating Capacity (kW); WF: Water Flow (m /h); WPD: Water Pressure Drop (kPa) Air inlet temp. (20℃ DB) Model Water inlet temp. (℃) Δt 1000 1200 1400 TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD TH WF WPD 10 0.53 0.05 0.1 1.85 0.16 1.3 3.23…
-
10.Static Pressure Graphs
How to read the diagram: The vertical axis is the External Static Pressure (Pa) while the horizontal axis represents the Air Flow (m3/h). The fan performance curves are for the“1-Super High”, “2-High”, “3-Medium” and “4-Low” fan speed. The dotted line stands for reserved fan speed. MKT3-200G12…
-
Static pressure graphs
-
таблицы и схемы — в просмотре
-
11. Exploded Views
MKT3-200G12 MKT3-200G30 No. Part 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 1 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporator assembly 1 11 Right panel 1 12 Middle clapboard assy 1 13 Rear below cover…
-
MKT3-200EG30
No. Part 1 Motor ass'y 1 2 Fan ass'y 1 3 Middle clapboard assy 1 4 Left panel 1 5 Drain tray assy 1 6 Evaporator assembly 1 7 Right panel 1 8 Top cover ass'y 1 9 Electric heater 1 10 Installing board 1 11 Electric control box cover 1 12 Electric control assembly 1 12.1 Electric control mounting…
-
MKT3-300G12
MKT3-600G12 MKT3-300G30 MKT3-600G30 Third-generation 3-row Ducted FCU MKT3-400G12 MKT3-400G30 Name MKT3-500G12 MKT3-500G30 No. Part Quantity 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 2 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9…
-
MKT3-300EG30
MKT3-400EG30 MCAC-KTSM-2012-10 MKT3-500EG30 MKT3-600EG30 No. Part 1 Motor ass'y 1 2 Fan ass'y 2 3 Middle clapboard assy 1 4 Left panel 1 5 Drain tray assy 1 6 Evaporator assembly 1 7 Right panel 1 8 Top cover ass'y 1 9 Electric heater 1 10 Installing board 1 11 Electric control box cover 1 12…
-
MKT3-1400G12 MKT3-1400G30 MKT3-1000G30 No. Part 1 Top panel assy 1 2 Motor ass'y 2 3 Fan ass'y 4 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Installing board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporator assembly 1 11 Right panel 1 12 Middle clapboard assy 1 13 Rear…
-
No. Part 1 Motor ass'y 2 2 Fan ass'y 4 3 Middle clapboard assy 1 4 Left panel 1 5 Drain tray assy 1 6 Evaporator assembly 1 7 Right panel 1 8 Top cover ass'y 1 9 Electric heater 1 10 Installing board 1 11 Electric control box cover 1 12 Electric control assembly 1 12.1 Electric control mounting…
-
12. Installation
12.1 Installing site Install the unit where installation and maintenance space is enough. Install the unit where the ceiling is horizontal and enough to bear the weight of the indoor unit. Install the unit where the air inlet and outlet are not baffled and are the least affected by external…
-
Old concrete roughcast
Use embedded bolts and embedded pulling plugs. Steel beam and girder structure: Set and use supportive angle steel. New concrete roughcast: Set it with embedded bushes or embedded bolts. 2) Suspending the indoor unit Use tools such as pulleys to hoist the indoor unit to the pendant bolt. Use…
-
Two grooves
The extended drain pan Rope Push it this way Water pipes Please hang up the extended drain pan to the pipes or ceiling by a rope. 12.4Installing water pipe With air release valve, the other side is water inlet pipe. When connect water collector, set the tightening torque to 6180~7540N.cm…
-
2. Drain test
Before the test, ensure that the drain pipes are smooth and the adapters are sealed. Newly built rooms should undergo the drain test before the ceiling is laid. 12.6 Wiring installation CAUTIONS: The air conditioner should use separate power supply with rated voltage. The external power…
-
13. Accessories
13.1 Standard accessories Accessory name Qty. Shape Usage Owner’s & installation manual 1 / Installation guide Extended drain pan 1 Connect drain water from valve kit 13.2 Optional accessories Accessory name PCB control kit CE-FCUKZ-01 Remote controller R05/BGE Remote controller R51/E Wired…
-
1. Specifications
Model CE-FCUKZ-01 CE-FCUKZ-02 Available appliance 2-pipe ducted FCU 4-pipe ducted FCU Power supply 220-240V-1Ph-50Hz Operation range Room temperature 17℃-30℃ Inlet water temperature 3℃-75℃ Temperature controlling precision ±1℃ Dimension (W×H×D) 310×76×290 Packing Size (W×H×D) 384×174×359 2. Internal…
-
5. Address setting
Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner in LAN is set by code switch on Network Interface Module (NIM), and the set range is 0-63. Functions of cold-air proof and heat-air proof can be selected. 6. Trouble-shooting…
-
E2: T2 evaporator sensor malfunction
T2 Connecting wire between sensor Exist Reconnect and ensure that the and mainboard gets loose connection is reliable. OK Exist Temperature sensor Replace sensor is short-circuited or punctured OK Error Chip fault, or chip foot sheds off, or chip is Reinstall chip, or install other chip with same…
-
13.2.2 Optional remote controller : R05/BGE
1. Part names Operation section Display section Accessories 41
-
2. How to operate
1. MODE: Once pressing, running mode will be selected in the following sequence: AUT TO → COOL → DRY Y → HEAT → FA AN NOTE: No heating mode for cool only type unit. 2. FAN SPEED: Fan speed will be selected in following sequence once pressing this button: AUTO →LOW →M ED →HIGH 3. Adjust: Decrease the…
-
13.2.3 Optional remote controller : R51/E
1. Part names 2. How to operate 1. TEMP DOWN Button: Push the TEMP DOWN button to decrease the indoor temperature setting or to adjust the timer in a counter-clockwise direction. 2. MODLE SELECT Button: Each time you push the button, a mode is selected in a sequence that goes from AUTO, COOL, DRY…
-
13.2.4 Optional wired controller for ducted units without electric heater :KJR-18B/E
1. Models KJR-18B/E is a thermostat that has developed into 4 types. Each type has its own features to suit different environment. Models Features KJR-18B/E-A Only control 3-speed fan, when the temperature reaches the set-point, it will close the Fan. KJR-18B/E-B KJR-18B/E-C KJR-18B/E-D Control…
-
Third-generation 3-row Ducted FCU Install the back base 4) 4. Wiring diagrams : KJR-18B/E-A KJR-18B/E-B KJR-18B/E-C Wire Connection KJR-18B/E-D N(220VAC) N(220VAC) L (220VAC) L (220VAC) Valve Val 2 Val 1 Fan L N Val Hi Med Fan Low Val2 Val1 L N Hi 2-wireNCvalve system Val1: For heating Val2: For…
-
KJR-21B/D is available for ducted FCU with electric heater. It has large LCD
display which can dispaly: working mode (cooling, heating and ventilation), fan speed, room temperature, setting temperature, etc. The buttons on the panel are : on/off ( ) , mode exchange ( M ), timer (), fan speed ( ) and temperature adjustment () Function : Specifications : Available for…
-
Wiring diagram
220V AC 50Hz N L L RH Thermostat Touching machine Val Aux heating Valve Low Med Hi Fan N How to operate On/off Press“ ”to turn on, press“ ”again to turn off. Temperature Press“”to reduce temperature,press“” to raise temperature;each time, temperature will change 1℃. setting Cooling Press “M” until…
-
13.2.6 Optional central controller: CCM03
-
Accessories
Third-generation 3-row Ducted FCU 49
-
Liquid crystal matrix display description
1. 2. 3. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure). The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+ and 48+ on the left Side, which indicate…
-
Query page description
1) 2) 3) The LCD displays the query page, and the air conditioner with the address of 08 is being queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature 22°C, set temperature 20°C, cooling mode “lock”. In the matrix, only the big and small…
-
1. Specifications (DDSTF-01)
Working voltage: AC230±10%, 50/60Hz (24V can be customized). Power consumption: 4W (only when you open and close the valve). Nominal pressure: 1.6MPa. Applied medium: cold or hot water, 50% glycol water liquor. Medium temperature : 2-75℃ Environment temperature : -5-50℃ 2. Parts introduction…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.