1. Introduction
Fan coil unit is a kind of compound device which assemble fan and surface-type coil heating-exchanger together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an important component of AC devices. Fan coil has horizontal type, vertical type, etc. A…
-
3. Product Schedule
-
5. Features
High air volume, high static pressure, high capacity High-pressure centrifugal fans Easy to clean and change the air filter Flexible control, no standard controller, remote controller and wired controller are optional Standard extended drainage pan for protecting your ceiling better …
-
6. Specifications
800G70 Model MKT3H3 H/M/L m /h H/M/L CFM 1000G70 1200G70 1400G70 1360/1220/1090 1700/1530/1380 2040/1880/1610 2380/2120/1860 Air flow External Static pressure 1000/900/810 Pa Capacity Cooling 800/720/640 1200/1105/950 1400/1250/1095 70 H/M/L kW 6.6/6.37/6.12 8.8/8.19/7.57 10/9.44/8.53 12/11.47/10.24…
-
Specifications
Model MKT3H- 1600G100 1800G100 2200G100 H/M/L m /h 3 2720/2450/2170 3060/2750/2450 3740/3360/2990 H/M/L CFM 1600/1440/1280 1800/1620/1440 2200/1980/1760 Air flow External Static pressure Pa Capacity Cooling 100 H/M/L kW 14.1/13.03/11.87 15.8/14.6/13.46 19.9/18.58/17.24 Water flow rate H l/h 2425…
-
7. Dimension
-
8. Wiring Diagrams
-
9. Capacity Tables
-
Cooling capacity
-
таблицы и схемы — в просмотре
-
Cooling capacity
-
таблицы и схемы — в просмотре
-
Cooling capacity
-
таблицы и схемы — в просмотре
-
Heating Capacity
-
Air inlet temp. (20℃ DB)
-
10. Static Pressure Graph
Static pressure (Pa) How to read the diagram The vertical axis is the External Static Pressure (Pa) while the horizontal axis represents the Air Flow (m3/h). MKT3H-800G70 200 Mid speed 180 160 High speed 140 120 Super-high speed 100 80 Low speed 1000 1200 1400 1600 1800 2000 2200 Air volume(m3/h)…
-
Static pressure (Pa)
MKT3H-1200 G70 200 180 Mid speed High speed 100 Low speed Super-high speed 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 Air volume(m3/h) Static pressure (Pa) MKT3H-1400 G70 Mid speed 140 High speed Super-high speed Low speed 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Air…
-
Static pressure (Pa)
MKT3H-1600 G100 200 180 Mid speed High speed Super-high speed Low speed 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 Air volume(m3/h) Static pressure (Pa) MKT3H-1800 G100 200 180 Mid speed 160 140 High speed 120 Super-high speed 100 Low speed 1500 1800 2100 2400 2700 3000 3300 3600…
-
Static pressure (Pa)
MKT3H-2200G100 Mid speed 140 High speed Super-high speed Low speed 2100 2400 2700 3000 3300 3600 3900 4200 4500 4800 5100 5400 Air volume(m3/h) Static Pressure Graph 21
-
11. Exploded View
MKT3H-800G70 MKT3H-1000G70 MKT3H-1200G70 MKT3H-1400G70 No. Part Name Qua. No. Part Name Qua. No. Part Name Qua. 1 Right fixing board 1 16 Baffle 1 29 Motor up cover 1 2 Volute shell ass'y 1 17 Back upside board ass'y 1 30 Fan motor 1 3 Wind ring ass'y 2 18 Cover plate ass'y 1 31 Board 1 4…
-
No. Part Name Qua. No. Part Name Qua. No. Part Name Qua. 1 Side board ass'y 1 16 Drainage pan ass'y 1 29 Beam ass'y 1 2 Fan ass'y 1 17 Beam ass'y 1 30 Beam ass'y 1 3 Stator 2 18 Back upside board ass'y 1 31 Right wind wheel ass'y 1 4 Cover plate ass'y 1 19 Drainage pan 1 32 Motor up cover 1 5…
-
12. Installation
12.1 Installation of the fan coil unit 26 Precautions before installation. Decide the correct way of conveying the equipment. Try to transport this equipment with the original package. If the air conditioner needs to be installed on a metal part of the building, electric insulation…
-
Suspending the indoor unit Use tools such as pulleys to hoist the indoor unit to the pendant bolt. Use tools such as gradient to settle the indoor unit horizontally. Lack of horizontality may cause water leak. Connect the duct The external static pressure is 70Pa or 100Pa, and the duct length…
-
MCAC-KTSM-2012-03 Drain test Before the test, ensure that the drain pipes are smooth and the adapters are sealed. Newly built rooms should undergo the drain test before the ceiling is laid. 12.4 Wiring Fan coil units model MKT3H-800G70 MKT3H-1000G70 Name of cable Main power cord Cable Qty. 1…