Инструкция на Фанкойлы MDV (сервис мануалы)
Фанкойлы MDV серии MKT 4. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. Introduction
Fan coil unit is a kind of compound device which assemble fan and heat exchanger (coil) together. Fan coil with fresh air supply system is a main type of central air-conditioner system, so it is an important component of AC devices. A cooling (heating) supply system usually consists of fan coil…
-
3. Product Schedule
Model External Static pressure Air volume (Pa) (CFM) MKT4-200G30 200 MKT4-300G30 300 MKT4-400G30 400 MKT4-500G30 500 MKT4-600G30 30 Power supply 600 MKT4-800G30 800 MKT4-1000G30 1000 MKT4-1200G30 1200 MKT4-1400G30 1400 MKT4-1500 30 1500 MKT4H-1500G50 50 1500 MKT4-2000 30 2000 MKT4H-2000G50 50 2000…
-
5. Features
1. 2. 3. 4. 5. 6. 7. Wider external static pressure supplying. 30Pa ESP is standard, 12Pa and 50 Pa can be customized. Left or right hand piping connections, field convertible. Quiet operation A patent design is able to prevent abnormal noise caused by blowing fins. Superior air distribution As the…
-
Washable filter Iron frame filter is standard, aluminum frame filter can be customized. Multi-direction pull-out filter can be customized. 9. Optional wired controller Optional wired controller offers simple and flexibility in controlling the unit. Features 5
-
6. Specifications
Model MKT4- 200G30 300G30 400G30 H/M/L m /h 3 340/255/170 510/385/255 680/510/340 H/M/L CFM 200/150/100 300/225/150 400/300/200 Pa H/M/L kW 2.5/2.16/1.87 3.3/2.85/2.47 4.4/3.72/3.22 Water flow rate H l/h Water pressure drop H kPa 2.6 5 8.1 H/M/L kW 4.1/3.51/3.03 5.8/5.05/4.35 7.1/6.11/5.33 H kPa 2.2…
-
Specifications
Model MKT4- 500G30 600G30 800G30 H/M/L m /h 3 850/640/425 1020/765/510 1360/1020/680 H/M/L CFM 500/375/250 600/450/300 800/600/400 Pa H/M/L kW 4.8/4.18/3.64 6.2/5.38/4.65 8.8/7.43/6.57 Water flow rate H l/h 826 1066 1514 Water pressure drop H kPa 9.8 15.4 12.3 H/M/L kW 8.5/7.04/6.28 10.5/9.03/7.77…
-
Specifications
Model MKT4- 1000G30 1200G30 1400G30 H/M/L m /h 3 1700/1275/850 2040/1530/1020 2380/1785/1190 H/M/L CFM 1000/750/500 1200/900/600 1400/1050/700 Pa H/M/L kW 9.5/8.18/7.06 11.8/9.82/8.74 13/11.23/9.83 Water flow rate H l/h 1634 2030 2236 Water pressure drop H kPa 18 21.2 24.7 H/M/L kW 16.3/13.45/12.05…
-
Specifications
Model MKT4- 1500 Air flow 3 Cooling Water flow rate Water pressure drop Capacity Heating Water pressure drop 2550/2100/1300 3400/2550/1700 3400/2550/1700 H/M/L CFM 1500/1240/760 1500/1240/760 2000/1500/1000 2000/1500/1000 Pa H/M/L kW 13.5/11.5/10.1 13.5/11.5/10.1 18/15.3/13.5 18/15.3/13.5 H l/h 2322…
-
7. Dimensions
F A B (Air return port) Electriccontrol box Intlet Outlet Air exhaust valve Condensation water draining port 4-10X16Hoisting hole Unit: mm Model 200-Model 300-Model A 545 645 B 484 C 400-Model 600-Model 800-Model 1000-Model 1200-Model 1400-Model 745 965 1265 1370 1660 1826 1205 1310 1600 1766 1233…
-
8. Wiring Diagrams
MKT4-300G30 MKT4-400G30 MKT4-500G30 MKT4-1200G30 (reserved super high fan speed) Motor MKT4-800G30 Black 3 Red Yellow 4 5 Black Red Yellow Orange Motor Yellow/green Low speed Blue 2 Medium speed Orange High speed 1 MKT4-600G30 Blue MKT4-200G30 MKT4-1000G30 Earth wire Zero line Power Three-speed…
-
Wiring diagrams
MKT4-1400G30 (reserved high fan speed) Motor Red Orange Yellow Orange Red Yellow Blue Yellow/green Low speed Blue 2 Medium speed 1 High speed Black Black Motor Earth wire Zero line Power Three-speed switch Live line Note: Black: supper high fan speed; Orange: high fan speed; Blue: medium fan…
-
Wiring diagrams
MKT4-1500, MKT4 H-1500G50, MKT4-2000, MKT4 H-2000G50 Wiring Diagrams 13
-
9. Capacity Tables
-
Cooling Capacities (with fan at high speed and 30Pa static pressure)
-
таблицы и схемы — в просмотре
-
Cooling Capacities (with fan at high speed and 30Pa static pressure)
-
таблицы и схемы — в просмотре
-
Cooling Capacities (with fan at high speed and 30Pa static pressure)
-
таблицы и схемы — в просмотре
-
Cooling Capacities (with fan at high speed and 30Pa static pressure)
-
таблицы и схемы — в просмотре
-
Third-generation 4-row Ducted FCU 4 16.54 10.05 3.56 91.5 15.19 11.05 3.27 77.2 16.27 10.50 3.50 88.5 17.22 10.05 3.70 99.2 18.08 5 15.82 9.70 2.72 53.5 14.47 10.79 2.49 44.8 15.51 10.17 2.67 51.5 16.54 9.68 2.84 58.5 17.38 15.02 2.99 64.6 6 15.12 9.43 2.17 34.0 13.77 10.42 1.97 28.2 14.82 9.82 2.12…
-
DB:26.7 WB:19.4
-
TH
-
10. Static Pressure Graphs
-
Static pressure graphs
-
Static pressure graphs
MKT4-1400G30 MKT4H-1500G50 160 140 Static pressure, Pa ④ 0 600 ③ ② ① 1000 1400 1800 2200 2600 3000 Air flow, m3/h MKT4H-2000G50 Note: How to read the diagram: The vertical axis is the External Static Pressure (Pa) while the horizontal axis represents the Air Flow (m3/h). The fan performance curves…
-
11. Exploded Views
MKT4-200G30 No. Part 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 1 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Water collector installation board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporater assembly 1 11 Right panel 1 12 Middle clapboard assy 1 13 Rear below…
-
MKT4-300G30
MKT4-400G30 Third-generation 4-row Ducted FCU MKT4-500G30 MKT4-600G30 No. Part 1 Top panel assy 1 2 Motor ass'y 1 3 Fan ass'y 2 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Water collector installation board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporater assembly 1 11…
-
MKT4-800G30
MKT4-1000G30 MCAC-KTSM-2012-10 MKT4-1200G30 MKT4-1400G30 No. Part 1 Top panel assy 1 2 Motor ass'y 2 3 Fan ass'y 4 4 Motor junction box cover 1 5 Wire joint, 5p 1 6 Motor junction box 1 7 Water collector installation board 1 8 Left panel 1 9 Drain tray assy 1 10 Evaporater assembly 1 11 Right panel…
-
MKT4-1500
MKT4H-1500G50 No. Part Name Quantity No. Part Name Quantity 1 Middle beam partition board ass'y 1 11 Plastic Drainage pan 1 2 Drainage pan ass'y 1 12 Installation board 1 3 Right cover ass'y 1 13 Installation board cover 1 4 Evaporator ass'y 1 14 Wire joint 1 5 Drainage pan 1 15 Fan ass'y 2 6 Top…
-
MKT4-2000
MKT4H-2000G50 No. Part Name MCAC-KTSM-2012-10 Quantity No. Part Name Quantity 1 Installation board 1 13 Drainage pan ass'y 1 2 Installation board cover 1 14 Middle beam partition board ass'y 1 3 Wire joint 1 15 Fan ass'y 3 4 Drainage pan ass'y 1 16 Volute shell 3 5 Installing board 1 17 Motor ass'y…
-
12. Installation
12.1 Installation site Install the unit where installation and maintenance space is enough. Install the unit where the ceiling is horizontal and enough to bear the weight of the indoor unit. Install the unit where the air inlet and outlet are not baffled and are the least affected by external…
-
Old concrete roughcast
Use embedded bolts and embedded pulling plugs. Steel beam and girder structure: Set and use supportive angle steel. New concrete roughcast: Set it with embedded bushes or embedded bolts. 2) Suspending the indoor unit Use tools such as pulleys to hoist the indoor unit to the pendant bolt. Use…
-
Two grooves
The extended drain pan Rope Push it this way Water pipes Please hang up the extended drain pan to the pipes or ceiling by a rope. 12.4 Installation water pipe With air release valve, the other side is water inlet pipe. When connect water collector, set the tightening torque to…
-
2. Drain test
Before the test, ensure that the drain pipes are smooth and the adapters are sealed. Newly built rooms should undergo the drain test before the ceiling is laid. 12.6 Wiring installation CAUTIONS: The air conditioner should use separate power supply with rated voltage. The external power…
-
13. Accessories
13.1 Standard accessories Accessory name Qty. Shape Usage Owner’s & installation manual 1 / Installation guide Extended drain pan 1 Connect drain water from valve kit 13.2 Optional accessories Accessory name Qty. PCB control kit CE-FCUKZ-01 Wired controller KJR-18B/E Sharp Usage 1 Electric control 1…
-
2. Internal View
Indoor temp sensor (T1), indoor evaporator mid. temp sensor (T2-H,T2-C), Network interface module To wire controller Valve control signal output Remote ON/OFF dry contact switch, Alarm signal output Power and fan terminal Display board Note: CE-FCUKZ-01 adopts one switch for three-way valve…
-
5. Application of Network control & BMS control
-
13.2.2 Optional wired controller : KJR-18B/E
1. Models KJR-18B/E is a thermostat that has developed into 4 types. Each type has its own features to suit different environment. Models Features KJR-18B/E-A Only control 3-speed fan, when the temperature reaches the set-point, it will close the Fan. KJR-18B/E-B KJR-18B/E-C KJR-18B/E-D Control…
-
Third-generation 4-row Ducted FCU Install the back base 4) Wire Connection Wiring diagrams : KJR-18B/E-A KJR-18B/E-B KJR-18B/E-D KJR-18B/E-C N (220VAC) N (220VAC) L (220VAC) L (220VAC) Valve 2 Valve1 Valve Fan Fan Val2 L N Val Hi Med Val1 L N Hi Med Low Low 2-wire NC valve system (KJR-18B/E-A…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.