Фанкойлы настенного типа MDV серии MDKG R3. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
MCAC-KTSM-2012-03
50Hz Wall Mounted FCU (R3 type panel) 1. Introduction Fan coil unit is a kind of compound device which assemble fan and heat-exchang coil together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an important component of AC devices. Fan coil unit has…
-
3. Product Schedule
Model Type MDKG-250R3 MDKG-300R3 MDKG-400R3 MDKG-500R3 MDKG-600R3 Wall mounted Air volume (CFM) Power supply 220~240V-1Ph-50Hz 4. External Appearance Product Schedule 4
-
5. Features
New panel supplies more choice for customs. Multi-connection outlet pipe method: left/right/rear, more flexible for installation. Left piping Left back piping Right back piping Right piping Wind direction adjustment can be in horizontal and vertical way for auto swing louver Vertical air…
-
6. Specifications
Model MDKGAir flow Cooling Heating 250R3 300R3 400R3 H/M/L m3/h 425/360/320 510/430/380 680/580/510 H/M/L CFM 250/210/190 300/250/220 400/340/300 H/M/L kW 2.63/2.41/2.16 2.97/2.47/2.12 3.28/2.83/2.41 Water flow rate H l/h Water pressure drop H kPa 29.4 35.6 43.5 H/M/L kW 3.36/3.1/2.79 3.91/3.26/2.77…
-
Model MDKGAir flow
Cooling Heating m3/h 850/720/640 1020/870/770 H/M/L CFM 500/420/380 600/510/450 H/M/L kW 4.25/3.85/3.32 5/4.47/3.97 Water flow rate H l/h 731 860 Water pressure drop H kPa 31.8 42.5 H/M/L kW 5.81/5.17/4.43 6.7/6/5.28 H kPa 30.2 39.7 Capacity Capacity Power supply V/ph/Hz Power input Sound pressure…
-
7. Dimension
-
8. Wiring Diagrams
Wiring Diagrams 11
-
10. Capacity Tables
-
MDKG-300R3
-
MDKG-400R3
-
MDKG-500R3
-
MDKG-600R3
-
Heating Capacity
-
11. Sound Levels
Test condition Unit Number Model Sound pressure level under three speeds of fan (dB(A)) H M L 1 MDKG-250R3 MDKG-300R3 MDKG-400R3 MDKG-500R3 MDKG-600R3 Capacity Tables 19
-
12. Exploded View
MDKG-250R3 MDKG-300R3 MDKG-400R3 No. Part Name Quantity No. Part Name Quantity 1 Filter 2 14 Louver 1 2 Evaporator I 1 15 Panel dalle 1 3 Evaporator II 1 16 Panel 1 4 Evaporator Ⅲ 1 17 Panel frame ass'y 1 5 Coil temp sensor 1 18 Stepper motor 2 6 Evaporate connect board 1 19 Screw cover 3 7 Display…
-
No. Quantity No. 1 Filter Part Name 2 14 Air outlet frame mount ass'y Part Name Quantity 1 2 Evaporator I 1 15 Louver board 1 3 Evaporator II 1 16 Louver 1 4 Evaporator Ⅲ 1 17 Panel dalle 1 5 Coil temp sensor 1 18 Panel 1 6 Evaporate connect board 1 19 Stepper motor 2 7 Cross fan 1 20 Screw cover 3…
-
13. Installation
13.1 Precautions Be sure to be in conformity with the local, national and international laws and regulations. Read "PRECAUTIONS" carefully before installation. The following precautions include important safty items. Observe them and never forget. Keep the installation manual in a handy place for…
-
cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle. Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it…
-
13.2 Accessory
Name 1. Screw ST3.9x25 for installation board Shape Quantity 3 Function Secure the installation board 2. Plastic expanded tube 3 3. Wrapping tape 1 4. Drain pipe 1 5. Wall conduit cover 1 6. Remote controller (including operation manual) 1 7. Frame 1 Hold the remote controller 8. Mounting screw…
-
A saline place such as coast
A place full of sulfide gas such as hot-spring resort. Places where there are high frequency machines such as wireless equipment, welding machine, and medical facility. A place there is no combustive gases and volatile matter. A place of special environmental conditions. Indoor unit installation…
-
Drilling a hole
Determine the pipe hole position using the installation board, and drill the pipe hole (N95mm) so it slants slightly downward. Always use a wall hole conduit when piercing metal lath, ply wood or metal plate. 13.4.3 Connective and drain pipe installation Drain pipe installation Run the drain…
-
. . . 43 Indoo . . . . . Fix the end of the connective pipe. (Refer to Tightening Connection in WATER PIPING INSTALLATION) Cautions: Connect the indoor unit first, then the outdoor unit. Bend and arrange the pipe carefully. Do not allow the piping to let out from the back of the indoor unit. …
-
13.5 Water pipe installation
Connection of the water pipe should be done by professionals. Double-span should be used when connecting pipes of Indoor Unit. At the first debugging, completely expel air from coils via expelling valve. 3-way valve (4.ports) discharge valve conector 13.6 Wiring chart The wiring diagram please…
-
Single phase indoor unit
Y/G RED Y E 1 2 L N BL AC K RED X XT3 INDOOR UNIT POWER 220-240V~50Hz RED XT1 BL AC K RED Ground wiring (mm2) BLAC K Below 20m Below 50m 220-240V/1 ph/50Hz 15/15 Twisted pairwire 2.5 mm2 Twisted pairwire 6 mm2 2.5 WHITE BLUE Power supply Circuit breaker/fuse (A) Indoor unit power wiring To…
-
Toggle switch set
~ ~ ~ ~ SW1 7 B C DE BCDE 789A B CDE BCDE BCDE 789A 789A 78 9A BCDE 32~47 789A BCD E 16~31 F012 F01 23 789A ON 00~15 F012 34 56 F0 ON 2 2 F01 F012 789A ON 1 F0 ENC2 3456 ON Network address code 48-63 Functions of anti-cold wind and anti-hot wind Toggle switch set Function selection SW2 Anti-cold…
-
13.7 Troubleshooting
Malfunction code EE E2 E3 Malfunction Water-level alarm malfunction T2 evaporator sensor malfunction T1 evaporator sensor malfunction EE: Water-level alarm malfunction Exist Water-level switch connecting wire between switch and main board gets loose Reconnect and ensure that the connection is…
-
E2: T2 evaporator sensor malfunction
T2 Connecting wire between sensor and mainboard gets loose Exist Reconnect and ensure that the connection is reliable. OK Temperature sensor circuited or punctured is short- Exist Replace sensor OK Error Chip fault, or chip foot sheds off, or chip is inverted (correct mode is semicircular bent…
-
13.7.1 Troubles and causes of air conditioner
If one of the following malfunctions occur, stop operation, shut off the power, and contact with your dealer. The operation lamp is flashing rapidly (twice every second) This lamp is still flashing rapidly after turn off the power and turn on again. Remote controller receives malfunction or…
-
13.7.2 Troubles and causes of remote controller
Before asking for serving or repairing, check the following points. Symptoms Causes Check whether the MODE indicated on the display is "AUTO" The fan speed can not be changed. Solution When the automatic mode is selected, the air conditioner will automatically change the fan speed. Protection…
-
14.2.3 Central Controller: CCM03
Installation 44
-
Liquid crystal matrix display description
1. 2. 3. The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different sizes (as shown in the above figure). The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+ and 48+ on the left Side, which indicate…
-
Query page description
1) 2) 3) The LCD displays the query page, and the air conditioner with the address of 08 is being queried. Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on, indoor temperature 22°C, set temperature 20°C, cooling mode “lock”. In the matrix, only the big and small…