1. Nomenclature
-
2. Features
2.1 New panel The panel has digital display function, which can show temperature and warning message. 2.2 Compact design Slim body needs only 170 mm space above the ceiling. 170mm UItra Thin 2.3Improved air quality Two folding type air filters and two standard formaldehyde absorption nets improve…
-
3. Specifications
-
4. Dimensions 290 425 1054 1015 Screw fixing size:290 Ceiling cutting size:430 Please use the installation paper plate to make sure the position of the installation screws. 4×Φ10 Screw fixing size:1015 Ceiling cutting size: 1100 5
-
5. Service Spaces
Please avoid installing in the following places : A place with flammable gas or material. A saline place such as a seashore vicinity. A place with sulphur gas. A place with oil gas,such as kitchen. A place with high-humidity air. An unbearable place. A place where high-frequency waves are generated.…
-
6. Wiring Diagrams
WIRING DIAGRAM TRANS TO WIRE CONTROLLER P CODE MAIN BOARD CN1 CN12 CN4 WHITE V WIRING PLATE FAN1 INDOOR FAN CAPACITOR CN1-22 P.C BOARD SOCKETS TRANS POWER TRANSFORMER FAN1 INDOOR FAN MOTOR K3 M WATER LEVEL SWITCH SWING MOTOR P PUMP T1 ROOM TEMPERATURE T2-C PIPE TEMPERATURE XP1-6 CONNECTORS XS1-5…
-
7. Capacity Tables
-
The Second Generation Of One-way Cassette FCU 7 0.50 0.50 0.06 0.14 1.72 1.51 0.21 1.68 1.66 1.66 0.20 1.56 2.14 1.33 0.26 2.60 3.64 1.89 0.45 7.50 8 / / / / 1.47 1.44 0.16 0.94 1.54 1.54 0.17 1.02 2.06 1.34 0.22 1.83 3.49 1.81 0.37 5.28 9 / / / / 1.32 1.29 0.13 0.60 1.37 1.37 0.13 0.65 1.97 1.32…
-
14 15 The Second Generation Of One-way Cassette FCU 5 0.99 0.99 0.17 0.99 2.31 1.95 0.40 5.36 2.19 2.11 0.38 4.81 2.81 1.75 0.48 7.92 4.67 2.41 0.80 21.89 6 0.60 0.60 0.09 0.25 2.05 1.89 0.29 2.94 2.03 1.99 0.29 2.88 2.57 1.65 0.37 4.62 4.44 2.34 0.64 13.78 7 0.49 0.49 0.06 0.12 1.82 1.82 0.22 1.69…
-
8. Exploded View
No. 1 1.1 1.2 1.3 1.4 1.5 1.6 Part Name E-part box ass'y Electric control box of fire protection shell welded pieces Middle wiring board Power transformer Motor capacitor Main control board ass'y Electronic control box Drainage pump bracket Water Level Switch Drainage pump shock pad Drainage pump…
-
9. Installation
9.1 Installation space ≥100 ≥170 170 ■ Please avoid installing in the following places ●A place with flammable gas or material. ●A saline place such as a seashore vicinity ●A place with sulphur gas. ●A place with oil gas, such as kitchen. ●A place with high-humidity air. ●An unbearable place. ●A…
-
9.2 Unit installation
Screw fixing size:290 Ceiling cutting size:430 ■ Please use the installation paper plate to make sure the positions of the installation screws. 4×Φ10 Screw fixing size:1015 Ceiling cutting size: 1100 ■ Please accord to the follow figure’s requirements to design the length of the suspender bolt.…
-
●For finished concrete bricks
Install the hanging hook with expansible bolt into the concrete deep to 45~50mm to prevent loose. ●Steel roof beam structure Install the supporting angle steel. Hanging screw bolt Hanging bolts Supportinganglesteel ■ Hoisting the indoor unit ●Adjust the height of screw 2, to make the difference…
-
■ Panel component installation
■ Remove the air return grille, filter screen, screw hidden cover. ●As the grille switch arrow indication direction to pull the lock catch, remove the air return grille. ●Pull the buckle as figure display, remove the filter screen. ●Open the air leading bar, remove three screw hidden covers. ●Take…
-
●Install the panel component, and wiring
●Two buckles on the panel component are used for assisting the panel installation, the installing method of the buckle as the follow figure display. ●Panel component wiring: open the electric control panel, connect the wiring terminal of the control display box and the motor connecting terminal of…
-
■ Install the screw hidden cover
Screw hidden cover ■ Install back the filter screen and the air return grille ■ Panel component wiring must accord to the figure display, otherwise will cause the abnormal operation. Connecting wire installation must follow the figure display, otherwise will cause the electric control box cover…
-
●Single air conditioner drainage
Gradient is more than 1/100 ■ Drainage system design requirement ●Between climbing section length (L) and pipe inner diameter (d)should satisfy the relation: L*d*d≤650000 (L and d units are mm).that is water in the climbing section can not more than 500 ml, otherwise will cause poor drainage…
-
■ Drainage system design requirement
●Drainage pipe can use PVC pipe, recommended to use the pipe of 25 mm inner diameter, water pipe should has thermal insulation layer. ●The user can purchase the pipe of suitable length in the dealer place or in a local after-sale service center place, or directly to purchase in the market. ●Insert…
-
●Avoid the damage to screw thread of evaporator, do not overexertion, when screwing. For avoid non-screw up or damage of screw thread, two spanners must be used simultaneously. ●Lag the connection pipes and any valves with anti-condensation material 10 mm thick or install the auxiliary. ●Ensure all…
-
10. Troubleshooting
10.1 Troubles and causes of air conditioner: Symptoms Causes Solution Unit does not start Power failure. Power switch is off. Fuse of power switch may have burned. Batteries of remote controller exhausted or other problem of controller. Wait for the comeback of power. Switch on the power. Replace…
-
10.2 Troubles and causes of remote controller
Symptoms Causes Solution Check whether the MODE indicated on the display is "AUTO" When the automatic mode is selected, the air conditioner will automatically change the fan speed. Check whether the MODE indicated on the display is "DRY" When dry operation is selected, the air conditioner…
-
10.3 Malfunctions and malfunction code
If anything happens like the situation described below, please shut off the power supply of the unit and contact with the custormer service center immediately. NO. Malfunction running lamp timer lamp defrosting lamp alarm lamp alarm lamp 1 Room temperature sensor checking channel is abnormal × ☆ × ×…