Floor Standing Type Air Conditioner
-
Safety Precautions
1 Safety Precautions Precaution To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service unit, be sure to read this service manual at first. Installation…
-
Safety Precautions
Install the drain hose to ensure that water is drained away properly. Keep level even when installing the product. Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods. Use two or more people to lift and transport the product. Do not install the…
-
Outer Dimensions
2 Out Dimensions Indoor Unit Dimension Mode 60K 3 Width (mm) 600 Height (mm) 1900 Depth (mm) 358
-
таблицы и схемы — в просмотре
-
External view and display External view This unit consists of indoor unit and outdoor unit. Indoor Unit Air Outlet Decor ative LED Outdoor Unit Control Panel Air Inlet Refrigerant Pipe Drain Pipe Note: All the pictures in this manual are for explanation purpose only. They may be slightly different…
-
Display panel
MO DE LO CK LE D TEM P ADJ USTI NG B UT TON MO DE LOC K BUTT ON SWIN G/FR ESH LED TEMP O C ON/ OF F BU TT O N TIME ADJ UST IN G BUTT ON RU NN IN G TES T B UTTON M OD E SLELECT BU TTO N C ON FIRM/C A NC EL T IMER/CLOC K A LTE R B UTT ON BUTT ON FA N SPEED SEL ECT BUTT ON S WIN G/ FR ESH BUTT ON…
-
B
-
таблицы и схемы — в просмотре
-
PCB drawing & Wiring diagram
5 PCB drawing & wiring diagram MDFE-60ARN1 Indoor unit Outdoor unit 9
-
Installation detail Installation place 6.1.1 Indoor Unit A place which provides the spaces around the indoor unit as required above in the diagram. A place where is no obstacle near the inlet and outlet area. A place which can bear the weight of the indoor unit. A place which allows the air filter…
-
Select a place that is easy to connect indoor unit's pipe and electric wires
Avoid a place where combustible gas may leak or stay. Keep it in mind that water may drain out of the outdoor unit while in "Heat" mode. 6.1.2.2 If the outdoor unit is to be installed on a roof or where no constructions are around, you should avoid hard wind blows directly to the air outlet, because…
-
Safety Lock
Screws 3.9×25 Screws 3.9 ×25 Air Outlet Air Inlet 2 Screw hole (on the unit) M8 Screws Firmly fix the unit to the wall and in the ground to avoid accidental falling. 6.1.4 Dismounting the air-inlet grid Please take off the air-inlet grid before connecting the pipes/wires. Pull down the two knobs on…
-
Pipe/ wire-hole positions on both sides
Drain Pipe Refrigerant Pipe Reamer Joint Reamer Joint Wiring Holeφ35 Refrigerant/drain Pipe holeφ80 Pipe/ wire-hole position on the bottom Wiring Holeφ35 Refrigerant/ drain Pipe hole Refrigerant/ drain Pipe hole 6.1.6 Ship the a/c to the installation place originally packed; Be careful while hanging…
-
Refrigerant pipe connecting
6.1.7 Pipe length and the elevation The correct refrigerant quantity filled in the 5-meter-long pipe of the outdoor unit is marked on the Product Data Plate. If you have to use longer pipe for every meter plus pipe, the refrigerant should be added according to the following calculation. Capacity…
-
outdoor unit and the pipe-jointing nut on the indoor unit(please keep them care
fully). Please connect the refrigerant pipe according to the manual, the pipe-jointing nut should be screw tightly and no leakage. Note: you need two wrenches to make balance. d. When the connecting of refrigerant pipe is finished, before power on the system, you should vacuum the indoor unit…
-
6.1.9 Air Purging
When Using the Vacuum Pump (For method of using a manifold valve, refer to its operation manual.) a. Completely tighten the flare nuts, A, B, C, D, connect the manifold valve charge hose to a charge port of the low-pressure valve on the gas pipe side. b. Connect the charge hose connection to the…
-
After the Drain Pipe has been connected, please check if the water drains out of the pipe efficiently and has no leakage. Refrigerant pipe and Drainpipe should be heat-insulated to avoid condensing and water-dropping later on. Wiring Please refer to the Wiring Diagram. (Wiring size:≥2.5mm 2) 2…
-
Electronic function
7 Electronic function Performance Index No. 1 2 Item Applicable Voltage Range A/C Frequency 3 Working environment temperature Index 342-418V 50Hz 18°C~43°C(Cooling) -7°C ~24°C(Heating) Main data Introduction Ts: Set temperature, T1: Room temperature T2: Evaporator pipe temperature Operation Modes…
-
Electronic function
7.1.3 Dehumidifying Mode 7.1.3.1 Indoor fan speed is low. 7.1.3.2 If certain protective condition is met, operation will be carried out. 7.1.4 Auto Mode 7.1.4.1 Under auto mode, the indoor fan is set to be auto. 7.1.4.2 When entering auto mode, the heating, fan only or cooling operation will be…
-
Characteristic of temperature sensor
8 Characteristic of temperature sensor Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ -10 62.2756 17 14.6181 44 4.3874 -9 58.7079 18 13.918 45 4.2126 -8 56.3694 19 13.2631 46 4.0459 -7 52.2438 20 12.6431 47 3.8867 -6 49.3161 21 12.0561 48 3.7348 -5 46.5725 22 11.5 49 3.5896 -4 44 23…
-
Trouble shooting Protective Function 9.1.1 3-minute delay for the compressor start-up At the beginning of energizing or after the stop of the compressor, 3-minute delay will be needed to start the compressor. When switching over between cooling/heating mode, the compressor stops automatically. 9.1.2…
-
protection signal
The A/C will recover if outdoor errors are eliminated after the outdoor protection occurs. 9.1.6 LEDs for the indication of outdoor trouble In normal operation, LEDs emit no light and they will flash at a frequency of 5 Hz when trouble occurs. Their codes are listed in the following table: Type…
-
Number Display
code 1 E01 Problem What to do Open-circuit and short-circuit of temperature sensors Over current of compressor (reserved) Protect of outdoor Overload of compressor (reserved) Contact service people P03 Too low a temperature of indoor evaporator Contact service people P04 Too high a temperature of…