Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Сплит - системы MDV серии MDCA3 кассетного типа. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
Features
1. Featurres 1.1 New pa anel 360°surrrounding air outlet desig gn, affords ccomfortable feeling f 1.2 Compa act design The bod dy size is 570×260×57 5 70mm, it’s jjust smallerr than the ceiling c boarrd, so it’s very v easy for f installatio on and will not n damage the decorattion. The panel…
-
Indoor model
Outdoor model MDCA3-12HRN1 MDOU-12HN1-L MDCA3-18HRN1 MDOU-18HN1 Power supply V-ph-Hz 220~240-1-50 220~240-1-50 Capacity Input Cooling Current EER Capacity Input Heating Current COP Model Qty Indoor fan motor Input Capacitor Speed(Hi/Med/Lo) Number of rows Tube pitch(a)x row pitch(b) Fin spacing…
-
Dimensio
ons 2. 2 Dimensions U Unit: mm d 1 Installation hook pitch dimensions 2 Indoor unit dimensionss ensions 3 Decoration panel dime 4 Refrigerantt piping 5 Installation hook (×4) ening dimenssions 6 Ceiling ope acket 7 Hanger bra ng 8 False ceilin Fo our-way Casssette Type(Com mpact) 77
-
Service Space
3. 3 Service e Space 78 8 Four-w way Cassette Type(Compa act)
-
Wiring Diagram
ms 4. 4 Wiring Diagram ms MDCA3-12HR M RN1 MDCA3-18HRN1 A 1 Fo our-way Casssette Type(Com mpact) 79
-
Electric Characcteristics
-
Field Wiring
8. 8 The Sp pecificatiion of Po ower Model Power 12000--18000 Btu/h Phase Frequenc cy and Voltage e Cirrcuit Breaker/ Fuse (A) 82 2 220-2240V, 50Hz 20/16 2 3×2.5 Ground Wiring W 2.5 Outdoor Unit U Power Wiring 3×2.5 Strong Ellectric Signal 2×1.0 Weak Ele ectric Signal 2×0 .5 /2×0.75 Indoorr Unit…
-
Field Wiriing
9. 9 Field W Wiring MDCA3-12HR RN1 MDCA3-18HRN1 1 Fo our-way Casssette Type(Com mpact) 83
-
Dimensions
-
Service Space
2. Service Space (Wall or obstacle) Air inlet More than 30cm Air inlet More than 60cm Maintain channel More than 60cm Air outlet Outdoor Units More than 30cm More than 200cm 87
-
Piping Diagrams
3. Piping Diagrams INDOOR OUTDOOR LIQUID SIDE CHECK VALVE (Heating Model only) 2-WAY VALVE T3 Condenser temp. sensor CAPILIARY TUBE HEAT EXCHANGE (EVAPORATOR) HEAT EXCHANGE (CONDENSER) T1 Room temp. sensor T4 Ambient temp. sensor T2 Evaporator temp. sensor GAS SIDE 4-WAY VALVE 3-WAY VALVE COOLING…
-
Wiring Diagrams
4. Wiring Diagrams MDOU-12HN1 Outdoor Units 91
-
Wiring Diagrams
MDOU-18HN1 92 Outdoor Units
-
Electric Characteristics
-
Operation Limits
6. Operation Limits Temperature Mode Cooling operation Heating operation 17℃~32℃ 0℃~30℃ Room temperature 18℃~43℃ (-7℃~43℃:For the models with low temperature cooling system) Outdoor temperature -7℃~24℃ Cooling STD Heating Outdoor temperature(℃ DB) Outdoor temperature(℃ DB) With Low Ambient Cooling…
-
Sound Levels
7. Sound Levels Outdoor Unit Microphone H 1.0m Note: H= 0.5 × height of outdoor unit Model Noise level dB(A) MDOU-12HN1-L MDOU-18HN1-L Outdoor Units
-
3.5 Compact cassette indoor unit installation
3.5.1 Service space for indoor unit 3.5.2 Bolt pitch 3.5.3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible…
-
In
ndoor unit insta allation Face F the con ncave side of o the installation hookss toward the e expansible e hooks. Deetermine the e length of th he in nstallation ho ooks from th he height of ceiling, then n cut off the unnecessarry part. Iff the ceiling is extremely high, plea ase determin ne the…
-
Insulation Wo
ork 3.5.5 Install the panel Remove R the grille Hang H the pan nel to the ho ooks on the mainbody. Tighten T the sscrews unde er the pane el hooks till the panel closely stick k on the ceilling to avoid d condensa ate water. w In nstallation 123
-
Indoor unit installation
Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively. Note: The panel shall be installed after the wiring connected. 124 Installation
-
Insulation Wo
-
Outdoor unit installation (Side Discharge Unit)
4.3 Install the Unit Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. Never hold the inlet of the outdoor unit to prevent it from deforming. Do not touch the fan with hands or other objects. Do not lean it more than 45, and do not…
-
5.2.5 Insulate the copper pipe
Before test operation, the joint parts should not be heat insulated. 5.2.6 Flare the pipe Insert a flare nut into the pipe before flaring the pipe According to the following table to flare the pipe Pipe diameter Flare dimension A (mm) Min Max 1/4" (6.35) 8.3 8.7 3/8" (9.52) 12.0 12.4 1/2"…
-
Drainage pipe installation
6.1 Installation principle Ensure at least 1/100 slope of the drainage pipe Adopt suitable pipe diameter Adopt nearby condensate water discharge 6.2 Key points of drainage water pipe installation 6.2.1 Considering the pipeline route and elevation Before installing condensate water pipeline…
-
Attention: Adopt PVC40 or bigger pipe to be the main pipe
6.2.3 Individual design of drainage pipe system The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe and drainage pipe in building. The drainage pipe of the indoor unit with water pump should be apart from the one without water pump. 6.2.4…
-
Drainage pipe installation
Indoor unit More than 50mm Plug More than 25mm Water storage pipe 6.2.7 Lifting pipe setting of indoor unit with water pump The length of lifting pipe should not exceed the pump head of indoor unit water pump. Pump head of big four way cassette: 750mm Pump head of compact four way cassette: 500mm…
-
6.2.9 The end of drainage pipe shall not contact with ground directly
6.3 Drainage test 6.3.1 Water leakage test After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to check whether there is leakage at joint section. 6.3.2 Water discharge test 1. Natural drainage mode(the indoor unit with outdoor drainage pump)…
-
Vacuum Drying and Leakage Checking
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by turning down power supply and eliminating accumulated water. Note: Drain plug at the main water-containing plate is used for eliminating accumulated water in water-containing plate when maintaining…
-
Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that there is moisture or leak source. 8. Additional refrigerant charge After the vacuum drying…
-
Engineering of electrical wiring
Liquid pipe Insulation meterial Gas pipe The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material. The insulation material at the joint pipe shall be inserted into the gap of the insulation material. The insulation material at the joint pipe…
-
Select different colors for different wire according to relevant regulations. Do not use metal wire tube at the place with acid or alkali corrosion, adopt plastic wire tube to replace it. There must be not wire connect joint in the wire tube If joint is a must, set a connection box at the…
-
1. Electrical Control Function
1.1 Definition T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 1.2 Main Protection 1.2.1 Time Delay at restart for compressor. 1.2.2 Sensor protection at open circuit and breaking…
-
1.3 Operation Modes and Functions
1.3.1 Fan mode (1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/medium/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: T1 27 High 26 Medium 24 Low 1.3.2 Cooling Mode…
-
High
33 30 Low 1.3.2.3 Indoor fan running rules In cooling mode, indoor fan runs all the time and the speed can be selected as high, (medium), low and auto. The auto fan: T1-Ts 4 High 3 Medium 1 Low 1.3.2.4 Low evaporator coil temperature T2 protection For Duct T2 On TE6 TE5 Off When the evaporator coil…
-
T2
On TE6 TE5 Off When the evaporator coil temp.T2 keeps lower than TE5 for 30 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up. Condition 2: T2 On TE6 TE5-2 Off When the evaporator coil temp.T2 keeps lower than TE5-2 for…
-
T3
Off TE12 TE13 On When T3>TE12 for Time1, the compressor will shut off. When T3≤TE13,the compressor will restart. 1.3.3 Heating Mode(For heat pump models) 1.3.3.1 Compressor running rules: Once the compressor starts up, it keeps running 7 minutes, then it will follow the below rules: When indoor room…
-
1.3.3.3 Indoor fan running rules
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function has the priority. For Ceiling & Floor: If the compressor stops caused by the room temperature rising, the indoor fan will follow the below rules. During this period, the anti-cold-wind is…
-
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal heating mode. A: T3 rises to be higher than 20℃. B: The machine has run for 10 minutes in defrosting. Defrosting action: Setting defrosting time 45S 45S Compressor 4 way valve 40S 40S…
-
Compressor off
TE7 Outdoor fan off TE8 Compressor and Outdoor fan off Compressor and Outdoor fan on TE9 Compressor and Outdoor fan on For Duct, Super-slim Cassette, Four-way cassette(compact): Compressor off Outdoor fan off TE9 Compressor on Outdoor fan off TE8 TE10 Compressor on Outdoor fan on TE11 1.3.4…
-
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then turn off automatically when reaching the setting “off” time. 1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then turn on automatically…
-
2. Troubleshooting
2.1 Display board 2.1.5 Display board of four-way cassette(compact) For Four-way cassette(compact) NO. Malfunction Running lamp Timer lamp Defrosting lamp Alarm lamp Display(digital tube) 1 Open or short circuit of T1 temperature sensor X ☆ X X E2 2 Open or short circuit of T2 temperature sensor ☆ X…
-
2.3. Solving steps for typical malfunction
(1) For indoor unit a. Indoor room temperature T1 and sensor evaporator temperature sensor T2 is abnormal Check the connections between temperature sensor and PCB. Are the connections good? No Correct the connections. Yes Measure the resistance value of the sensor via Appendix 1 Is it normal? No…
-
c. EEPROM malfunction
EEPROM: An electrically erasable programmable read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. d. Water-level alarm malfunction 150 Electrical Control
-
For the super-slim cassette with up-down panel
a. Communication error between indoor unit and up-down panel b. Up-down panel is defective Electrical Control 151
-
(2) For the outdoor unit
a. Phase sequence error: Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem cannot be solved, the outdoor PCB is defective b. Overload of current Overload of current Check the current, normally Is the current in rated range? No Yes The…
-
Protection of pressure or temp. Yes Is it k1 or K2 open ? Is temp. protective switch K1 open Is pressure protective switch K2 open Yes Possible reason 1. The wires is loose to K1 2. Air or other gas in the refrigerant. 3. Heat exchanger is dirty 4. Outdoor fan or fan blade is defective 5. Outdoor…
-
f. Open-circuit and short-circuit trouble of T5
Is connection to connector of temp. sensor good? No Yes Check the resistance of the temp. sensor according to Appendix 2 Repair connector Is it the resistance is normal? No Yes Indoor PCB is defective. Replace the sensor g. High temperature protection of condenser High temperature protection of…
-
Appendix 1 Temperature Sensor Resistance Value Table
-
Appendix 2