Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Канальные сплит-системы MDV серии MDHA-150HRN2 / MDOV-150HN2. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
1. Model Names of Indoor/Outdoor Units
1.2 Model Names of Units with Cooling and heating: Indoor unit Type High-static pressure duct type Outdoor unit Capacity Model Power supply Model Power supply kW kBtu/h MDHA-150HRN2 220~240V-1N-50Hz MDOV-150HN2 380~415V-3N-50Hz 44 150 2. External Appearance 2.1 Indoor Units MDHA-150HRN2 2.2 Outdoor…
-
2. Specifications
Model MDHA-150HRN2 Power supply - 220~240V-1Ph-50Hz Btu/h 150000 W 43900 Input power W 16000 EER W/W 2.74 Btu/h 165000 w 48500 Input power W 16500 COP W/W 2.94 Indoor air flow(Hi/Med/Lo) 3 m /h 8000/6750/5500 Indoor standard ESP Pa 196 Indoor noise level(Hi/Med/Lo) dB(A) 49/47/45 Type - R407C…
-
6.3 MDHA-150HRN2
4 MCAC-UTSM-2012-07
-
7. Capacity Table
7.5 MDHA-150HN2 Air flow Outdoor ambient temp DB 21/15 24/17 Indoor Air Entering Temp. (DB/WB) ºC 27/19 29/19 32/23 CFM ºC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC Air flow CFM Outdoor ambient temp DB ºC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC CFM ºC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 21/15…
-
8. Air flow rate- Static pressure curve
Static Pressure (Pa) 8.5 MHA-150H 220 Lo 5500 6000 Med 6500 7000 Hi 7500 8000 8500 9000 9500 Air Flow (m 3/h) KW: Rated Motor Output (KW) FLA: Full Load Amps. (A) 9. Electric Characteristics Indoor Unit Power Supply IFM Model Hz Voltage Min. Max. MCA MFA kW FLA MTA-150HR 50 220-240 Note: MCA: Min.…
-
10. Sound Levels
Concealed Duct Type Discharge Duct Suction 1.4m Microphone 8 Unit Number Model Noise level under three speeds of fan (dB(A)) 5 MHA-150HR 49
-
12. Troubleshooting
Infrared signal receiver Operation lamp Manual Switch Timer lamp Alarm lamp PRE-DEF lamp(cooling and heating type) or fan only lamp(cooling only type) Type TME. Light ☆ DEF. Light - ALARM Light - Remarks Room temp. sensor error OPT. Light - Evaporator temp. sensor error ☆ - - - Manual reset…
-
Symptoms
The unit does not work Causes Power supply fails. Operate after power resumes. Power switch is not connected. Connect the power supply properly. Fuse blows out or circuit breaker snaps off. The unit starts or stops frequently fails. controller. Temperature setting is higher than the Temperature…
-
Symptoms
Causes Check whether the mode marked on the screen is “AUTO”. The fan speed When the “AUTO” mode is selected, the unit will change the fan speed automatically. When the “DEWET” mode is selected, cannot be changed 50Hz Split AC Handling methods Check whether the mode marked on the screen is “DEWET”.…
-
Operation lamp flashes
All lamps flashing at 5Hz Judge 1: The PRO terminal on PCB of indoor unit without connecting to grounding wire Validate: Check whether the PRO terminal on PCB of indoor unit without connected to grounding wire. No Connect it to grounding wire. Yes Judge 2: Optical coupler on PCB malfunction…
-
Operation lamp flashes
Timer lamp flashing at 5Hz Room temperature sensor malfunction Judge 1: Check the room temperature sensor Is break off. Yes Connects it well. No Judge 2: Check the room temperature sensor is abnormal. Validate: Check whether the resistance of the temperature sensor is correct according to Annex 1.…
-
Operation lamp flashes
Operation lamp flashing at 5Hz Evaporate temperature sensor is abnormal. Judge 1: Check evaporate temperature sensor is break off. Yes Replace temperature sensor No Judge 2: Evaporate temperature sensor is abnormal. Validate: Check whether the resistance of the room temperature sensor is correct…
-
Operation lamp flashes
Defrosting lamp flashing at 5Hz Condenser temperature sensor malfunction Yes Replace temperature sensor Judge 1: Check condenser temperature sensor is break off. No Judge 2: Condenser temperature sensor is abnormal. Validate: Check whether the resistance of the condenser temperature sensor is…
-
11.1 E1 malfunction
LED indicate E1 Fault of indoor temperature sensor T1 Judge 1: Whether the indoor temperature sensor T1 is break off. Yes Connects it well. No Judge 2: Whether the indoor temperature sensor T1 is malfunction. Validate: Check whether the resistance of the temperature sensor is correct according to…
-
11.2 E2 malfunction
LED indicate E2 Fault of indoor temperature sensor T2 Judge 1: Whether the indoor temperature sensor T2 is break off. Yes Connects it well. No Judge 2: Whether the indoor temperature sensor T2 is malfunction. Validate: Check whether the resistance of the temperature sensor is correct according to…
-
11.3 P1 malfunction
LED indicate P1 Under heating mode, T2 is on high temperature protection Judge 1: Check whether the evaporator temperature sensor T2 is break off. Yes Connect it well. No Judge 2: Whether the evaporator temperature sensor is malfunction. Validate: Check whether the resistance of the temperature…
-
11.4 P2 malfunction
LED indicate P2 Under cooling mode, T2 is on low temperature protection Judge 1: Check whether the evaporator temperature sensor T2 is break off. Yes Connects it well. No Judge 2: Whether the evaporator temperature sensor is malfunction. Validate: Check whether the resistance of the temperature…
-
1. Specifications Model MDOV-150HRN2 Power supply - 380~400V-3N-50Hz Ambient temp range ℃ -10~42 Rated input W 24000 Rated current A 39 Noise level dB(A) 65 Type - scroll Brand - Hitachi Model - 603DH-90C2Y-X10 Qty. - 3 Capacity Btu/h 57322 Input W 5000 Rated current A 9.5 Locked rotor Amp A 70 Type…
-
2. Dimension
2.2 MDOV-150HRN2 1380 830 1630 100 1095 3. Service Space (Air outlet) (Air inlet) 22 (Air inlet)
-
≥1000 mm
≥500 mm ≥1000 mm ≥1000 mm ≥1000 mm Top view of outdoor unit (multi units installed) Note: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. 2. If miscellaneous articles are piled around the outdoor unit, such articles must be 400mm below the…
-
4. Wiring Diagrams
4.5 MDOV - 150HN2 24 MCAC-UTSM-2012-07
-
5. Electric Characteristics
Outdoor Unit Power Supply Compressor OFM Model MDOV-150HN2 Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA 50 380-415 342 438 35.63 39 45 70*3 9.5*3 0.9 6 Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A) RLA: Rated Locked…
-
7. Sound Levels
Standard of testing Front h H 1 m Note: H = (h+1) / 2 Unit Number Model Noise level (dB(A)) 3 MOV-150HR 65 9. Troubleshooting Type LED1 LED2 LED3 Standby ☆ ☆ ☆ Cooling mode X ◆ X Heating mode ◆ X X Phase sequence protection ★ ★ ◆ Outdoor ambient temp. sensor error ◇ ◇ ★ Low or high pressure…
-
10. Malfunctions
About the Fault of T3A or T3B, High pressure protection, low pressure protection. Please refer to the following: Fault of T3A or T3B Judge 1: Whether the sensor is break off. Yes Connects it well. No Judge 2: Whether the sensor is malfunction. Validate: Short-connect the outdoor ambient temperature…
-
Low pressure protection
Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly No Connect it well Yes Judge 2: Whether the low pressure switch is broken Validate: Short connect the low pressure switch socket, check whether the system can run normally Yes Replace low…
-
High pressure protection
No Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the high pressure switch is broken Validate: Short connect the high pressure switch socket, check whether the system can run normally Yes Replace…
-
2. Installation of Indoor Units
2.1 Installation of Duct ≥500mm 2.1.1 Installation Space Ensure enough space required for installation and maintenance. (Fig-1 and Fig-2) ≥600mm Electric control box Inspection hole Fig-1 Fig -2 D B 2.1.2 Install Φ10 Pendant Bolts Or Ground Bolts (Fig-3) Air inlet side C Model MTA-150H B (mm) 739.5…
-
Fig-4
B. New concrete roughcast Use embedded bolts, embedded pulling plugs, and embedded stick harness. (Fig-5) Fig-5 C. New concrete roughcast Set it with embedded bushes or embedded bolts. (Fig-6) Fig-6 D. Steel beam and girder structure Set and use supportive angle steel. (Fig-7) Fig-7 2.1.3 Suspending…
-
Pendant bolt
≥30mm Unit body Fig-8 2.1.4 Design and Connection of Duct The duct design must comply with the national heating air conditioner pipeline design specifications. The duct accessories and materials must be produced by professional manufacturers. In order to prevent air flow shorting, do not keep…
-
3. Installation of Outdoor Units
3.1 Important: Construction Checkpoints 1). Installation Check the model and name to avoid mistaken installation. 2). Refrigerant pipe The refrigerant pipes must have the specified diameter. Nitrogen of a certain pressure must be filled into the refrigerant pipe before welding. The refrigerant…
-
Air outlet
Air outlet Air inlet Fig-14 ≥1000 mm ≥1000 mm ≥200 mm ≥200 mm ≥1000 mm ≥1000 mm Fig-15 NOTE: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. 2. If miscellaneous articles are piled around the outdoor unit, such articles must be 400mm below…
-
735mm
595mm Through hole (15×20 rectangular hole) Fig-17 3.3 Convey Outdoor Unit Use 4 steel ropes of a Ф6mm or bigger size to hoist the outdoor unit and convey it into the room. In order to prevent scratch and deformity the outdoor unit, apply a guard board to the surface of contact between the steel…
-
Snow protection
Snow protection shed at the air outlet shed at the air inlet Snow protection shed at the air inlet Fig-19 3.5 Installation of Refrigerant Pipe The refrigerant pipe adapter is located inside the outdoor unit. When the pipe is connected from the front side, the pipe can be let out through the right…
-
Fig-21
NOTE: When welding the refrigerant pipe, in order to prevent internal oxidation of the pipe, nitrogen must be filled in. Otherwise, the oxidized chips may block refrigerating circulatory system. 3.5.1 Size of Outdoor Unit Pipes and Piping Methods 1) Size of outdoor unit pipes and piping methods…
-
76, 96, 15 kBtu/h
Fig-23 3.6 Airtight Test After the pipes between the indoor unit and the outdoor unit are connected, replenish compressed nitrogen to perform airtight test. NOTE: 2 1. The airtight test is performed by using the compressed nitrogen [2.94MPa (30kg/cm G)]. 2. Tighten the spool of the gas valve and…
-
leakage occurs, the density threshold will not be crossed. Additional measures may also be taken
1) Density threshold: Density of the Freon gas that does not harm the human body. Density threshold of R410A: 0.3 [kg/m3] Calculate the total quantity of refrigerant to be replenished (A [kg]). Total refrigerant quantity for 10HP = refrigerant replenishment quantity upon shipment (11[kg]) +…
-
it is necessary to give name to each system, and mark it onto the nameplate on the electric control box cover of the outdoor unit. NOTE: The indoor unit and outdoor unit are categorized into system A and system B. When installing and connecting the indoor unit and outdoor unit, identify the label…
-
5. Installation of Connective Pipe
5.1 Preparation before Installation Check the height difference between the indoor unit and the outdoor unit, and check the length and number of bends of the refrigerant pipeline, which must meet the following requirements: Max. Height difference 30m (If the height difference is greater than 5m…
-
Fig-27
5.2.2 Deploy the pipelines Drill a porthole on the wall, and put the hole sheath and hole cover through the wall. Place the connective pipe together with the indoor & outdoor connection wires. Use wrapping tape to tie them tight. Do not let air penetrate into it lest condensation and drips of…
-
Fig-29
Tighten the nut Align with the connective pipe Screw up the connection pipe nut manually, and use a spanner to tighten it as shown in Fig-38 Fig-30 NOTE: According to the installation conditions, too large torque will damage the flaring, and too small torque will lead to looseness and leakage.…
-
5.3 Expelling Air
5.3.1. From the following table, select a method of expelling air. Table 4: Length of connective pipe (single pass) Procedure of expelling air Less than 5m Use refrigerant in the outdoor unit 5~15m Use vacuum pump or refrigerant tank. If the air conditioner is relocated, be sure to use a vacuum pump…
-
Manifold valve
Multimeter manometer -76cmHg Hi -handle Lo-handle Filler hose Vacuum pum p Filler hose Lo pressure valve Fig-32 Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose of the manifold valve to the maintenance orifice of valve A (tighten both valve A and…
-
5.4 Leak Detection
Use soap water or a leak detector to check whether gas leakage exists at the adapters. 5.5 Heat Insulation Use heat insulation materials to wrap the part protruding outside the flared pipe joint and the refrigerant pipe of the liquid pipe and the gas pipe, and ensure that no gap exists between…
-
7. Electric Connection
7.1 Electric field wiring CAUTION: Use special power supply for the air conditioner. Design power supplies specific to the indoor unit and outdoor unit. The supply voltage must comply with the nominal voltage. The external supply circuit of the air conditioner must have a ground wire, and the…
-
7.2 Power wires
The power wires are as follows: (schematic diagram) Indoor unit Control wire between indoor unit and outdoor unit RCCB Manual switch Indoor unit power supply Outdoor unit 220-240V~ 50Hz RCCB Manual switch Outdoor unit power supply 380-415V 3N~ 50Hz Fig-35 51
-
Appendix 1: Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K) ℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm -20 115.266 20 12.6431 60 2.35774 100 0.62973 -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5000 62 2.19073 102 0.59386 -17 96.3423 23 10.9731 63 2.11241 103 0.57683 -16…