Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Колонные сплит-системы MDV серии MFA / MON. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
Model Names of Indoor/Outdoor Units
MCAC-UTSM-2009-03 1. Model Names of Indoor/Outdoor Units 1.1 Indoor Units Model name Dimension (mm) Net/Gross weight (kg) Power supply MFA-12HRN1 Width: 700 Height: 600 Depth: 210 15/20 220~240V-1ph-50Hz MFA-18HRN1 Width: 700 Height: 600 Depth: 210 15/20 220~240V-1ph-50Hz MFA-12HRN1-Q Width: 700…
-
Nomenclature
3. Nomenclature 3.1 Indoor Unit M F A - 12 H R N1 - Q Q: Quickly Coupling Refrigerant Type N1 : R410A Control Mode R: Remote Control Function Code C: Cooling Only H: Cooling & Heating Capacity (× 1000Btu/h) Product Series A: 1st Designed Product Category F: Console Type Midea 3.2 Outdoor Unit M O N…
-
Features
MCAC-UTSM-2009-03 4. Features 1. Achieves set temperature more quickly ——air supplying from top and bottom or from top only ——air inlet from four directions 2. Compact unit body, space saving ——this unit body is very thin and harmonious with room. It is beautiful, elegant and space saving. ——light…
-
Specifications
MCAC-UTSM-2009-03 1. Specifications Model MFA-12HRN1 MFA-18HRN1 MFA-12HRN1-Q 220044000090 220044100280 220044000100 V-ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Capacity Btu/h 12000 18000 12000 Input W 1096 1650 1101 Capacity Btu/h 13380 19600 13300 Input W 1122 1715 1117 Model RD-280-20-8A…
-
Dimensions
2. Dimensions 3. Service Space Indoor Units 7
-
4. Wiring Diagrams
4.1 MFA-12HRN1 MFA-18HRN1 4.2 MFA-12HRN1-Q 8 Indoor Units
-
Air Velocity and Temperature Distributions
5. Air Velocity and Temperature Distributions Discharge angle 60 Airflow velocity Temperature Indoor Units 9
-
6. Capacity Tables
-
6.2 MFA-18HRN1
-
6.3 MFA-12HRN1-Q
-
Electric Characteristics
7. Electric Characteristics Indoor Units Model Power Supply Indoor Fan Motor Hz Voltage Min. Max. MCA MFA kW FLA MFA-12HRN1(-Q) 50 220-240V 198V 254V 0.1 15 0.02 0.08 MFA-18HRN1 50 220-240V 198V 254V 0.156 20 0.02 0.125 Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) KW: Fan Motor Rated…
-
9. Exploded View
9.1 MFA-12HRN1 MFA-18HRN1 18 No. Part Name Quantity No. Part Name Quantity 1 Panel frame ass'y 1 14.1 Main control board ass'y 1 2 Base ass'y 1 14.2 Wire joint 1 3 Filter 1 14.3 Dial-up board ass'y 1 4 Air fresh net 2 14.4 Display board ass'y 1 5 Formaldehyde-killer 2 14.5 Room temp sensor ass'y 1 6…
-
9.2 MFA-12HRN1-Q
No. Part Name Quantity No. Part Name Quantity 1 Panel frame ass'y 1 14.2 Wire joint 1 2 Base ass'y 1 14.3 Dial-up board ass'y 1 3 Filter 1 14.4 Display board ass'y 1 4 Air fresh net 2 14.5 Room temp. sensor ass'y 1 5 Formaldehyde-killer 2 15 Wire clamp 1 6 Air guide ring ass'y 1 16 Motor bracket 1 7…
-
Accessories
MCAC-UTSM-2009-03 10. Accessories 10.1 MFA-12HRN1/ MFA-18HRN1 Name Installation fittings Remote controller & Its Frame Shape Quantity Hook 2 Remote controller 1 Frame 1 Mounting screw(ST2.9×10-C-H) 2 Alkaline dry batteries (AM4) 2 Installation manual 1 Owner's manual 1 Others 10.2 MFA-12HRN1-Q Name…
-
Specifications
MCAC-UTSM-2009-03 1. Specifications Model Code Power supply Max. input consumption MON-12HN1 MON-18HN1 MON-12HN1-Q 220075100200 220075200460 220075100210 V-ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 W 1500 2000 1500 Max. input current A 7.5 12 7.5 Starting current A 29.9 31.8 29.9 PA140X2C-4FT…
-
Dimensions
2. Dimensions 2.1 MON-12HN1 MON-12HN1-Q 2.2 MON-18HN1 Outdoor Units 19
-
Service Space
MCAC-UTSM-2009-03 3. Service Space 4. Piping Diagrams Indoor units Outdoor unit condenser temp. sensor T3 4-way valve T2 evaporator temp. sensor filter one way valve Throttle capiliary stop valve T1 room temp. sensor stop valve compressor 20 Outdoor Units
-
5. Wiring Diagrams
5.1 MON-12HN1 Outdoor Units 21
-
5.2 MON-18HN1
22 Outdoor Units
-
5.3 MON-12HN1-Q
Outdoor Units 23
-
Electric Characteristics
MCAC-UTSM-2009-03 6. Electric Characteristics Outdoor Unit Model Power Supply Compressor OFM Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA MON-12HN1 50 220~240V 198V 254V 6.6 13 15 29.9 5.3 0.024 0.275 MON-18HN1 50 220~240V 198V 254V 9.8 18 20 31.8 7.81 0.053 0.592 MON-12HN1-Q 50 220~240V 198V…
-
Sound Levels
8. Sound Levels Outdoor Unit Microphone H 1.0m Note: H= 0.5 × height of outdoor unit Outdoor Units Model Noise level dB(A) MON-12HN1 52.8 MON-18HN1 55.5 MON-12HN1-Q 52.6 25
-
9. Exploded View
9.1 MON-12HN1 No. Part Name Quantity No. Part Name Quantity 1 Fan motor 1 9 High pressure valve ass'y 1 2 Motor bracket ass'y 1 9.1 High pressure valve 1 3 Rear net 1 9.2 Strainer 1 4 Condenser ass'y 1 9.3 One way valve 1 4.1 Condenser 1 10 Base ass'y 1 4.2 Condenser output pipe 1 11 Grille 1 4.3…
-
9.2 MON-18HN1
No. Part Name Quantity No. Part Name Quantity 1 Top cover ass'y 1 18 Grille 1 2 Foam 1 19 Small handle 1 3 Motor bracket ass'y 1 20 E-part box ass'y 1 4 Rear net frame 1 20.1 Wire joint, 4p 1 5 Fan motor 1 20.2 Compressor capacitor 1 6 Axial flow fan 1 20.3 Electric installation board 1 7 Compressor…
-
9.3 MON-12HN1-Q
No. 1 Part Name Quantity No. Fan motor Motor bracket ass'y 1 3 Rear net 1 4 Condenser ass'y 1 4.1 Condenser 1 4.2 Condenser output pipe 4.3 4.4 Part Name Quantity Big handle 1 8 Drainage cover 1 9 Valve plate 1 10 High pressure valve ass'y 1 10.1 One way valve 1 1 10.2 Filter ass'y 1 Condenser…
-
10. Troubleshooting
10.1 Indoor Unit Malfunction Indoor unit display panel No. Running lamp Timer lamp Defrosting lamp Malfunction 1 ☆ × × Room temp. sensor checking channel is abnormal 2 × × ☆ Evaporator temp. sensor checking channel is abnormal 3 ☆ ☆ ☆ Condenser temp. sensor checking channel is abnormal 4 × ☆ ×…
-
2. Defrosting lamp flash at 5Hz
Defrosting lamp flash at 5Hz Judge: Evaporator temp. sensor checking channel is abnormal Validate: Check whether the resistance of the evaporator No Replace the evaporator temp. sensor temp. sensor is correct according to Annex 1 Yes Replace the indoor main board 3. Running lamp, Timer lamp…
-
4. Timer lamp flash at 5Hz
Timer flash at 5Hz In-outdoor unit communication malfunction Yes Judge 1: Check whether the wiring of communication line is break off Connect the wiring well No Yes Judge 2: Check whether the wiring of L, N and S is wrong No Connect the wiring of L, N and S rightly Replace the PCB Outdoor Units 31
-
5. Running lamp and Defrosting lamp flash at 5Hz, the Timer lamp light
Running lamp and Defrosting lamp flash at 5Hz, the Timer lamp light DC fan malfunction Yes Judge 1: Check whether the wiring of DC fan is break off Connect the wiring well No Yes Replace the DC fan Judge 2: Check whether the DC fan is failure No Replace the indoor main board 6. Running lamp and…
-
10.2 Outdoor Unit Malfunction
No. LED1 LED2 LED3 Malfunction 1 ☆ × ☆ In-outdoor unit communication malfunction 2 × ☆ ☆ T3 condenser pipe temp. sensor malfunction × Extinguish, ☆ Flash 1. LED1 and LED3 flash LED1 and LED3 flash In-outdoor unit communication malfunction Yes Judge 1: Check whether the wiring of communication line…
-
2. LED2 and LED3 flash
LED2 and LED3 flash T3 condenser pipe temp. sensor malfunction No Connect it well Check whether the temp. sensor is connected well Yes No Check whether the resistance of the temp. sensor is correct according to Annex 1 Replace the temp. sensor Yes Replace the PCB 34 Outdoor Units
-
Appendix Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K)
℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm -20 115.266 20 12.6431 60 2.35774 100 0.62973 -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5000 62 2.19073 102 0.59386 -17 96.3423 23 10.9731 63 2.11241 103 0.57683 -16 89.5865 24 10.4736 64 2.03732 104 0.56038 -15 84.2190 25 10.000 65 1.96532 105…
-
Installation Place
1. Installation Place 1.1 The indoor Unit 5. There is enough room for installation and maintenance. 6. The air outlet and the air inlet are not impeded, and the influence of external air is the least. 7. The air flow can reach throughout the room. 8. The connecting pipe and drainpipe could be…
-
Installation of Indoor Unit
MCAC-UTSM-2009-03 2. Installation of Indoor Unit 2.1 Service Space The indoor unit should be installed in a location that meets the following requirements: There is enough room for installation and maintenance. (Refer to the following figure ) The outlet and the inlet are not impeded…
-
Installation of Indoor Unit
2.2 Installation the main body z Fix the hook with tapping screw onto the wall z Hang the indoor unit on the hook. (The bottom of body can touch with floor or suspended, but the body must install vertically.) Installation 39
-
Installation of outdoor unit
MCAC-UTSM-2009-03 3. Installation of outdoor unit 3.1 Necessary space for Installation and Maintenance If possible, please remove the obstacles nearby to prevent the performance from being impeded by too little of air circulation. The minimum distance between the outdoor unit and obstacles described…
-
4. Installation of the Connecting Pipe
Caution: For your safety, always wear safety eye wear and work gloves when connecting the pipes. 4.1 MFA-12HRN1-Q (Quick connecter) Remove the water tray before performing the connection. Installation 41
-
To connect the couplings
Step 1: Ensure that the handle on the male coupling is in a reclined position away from the mating male coupling. Step 2: Retract the “Release Sleeve” on female coupling, insert the male coupling located on the indoor unit into the female coupling. Step 3: Release the “Release Sleeve” to the lock…
-
4.2 MFA-12HRN1and MFA-18HRN1
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements: Capacity(Btu/h) 12000 18000 The max. height drop 5m 10m The length of refrigerant pipe Less than 15m Less than 20m The number of bends…
-
How to take indoor unit apart to connect the pipes
1. Open the front panel Slide the two stoppers on the left and right sides until they click. 2. Remove the front panel Remove the string. Allowing the front panel to fall forward will enable you to remove it. 44 Installation
-
3. Remove the face plate
Remove the four screws. Opening bottom of face plate for a angle that is 30 degree, then the top of face plate will be take up. How to take outdoor unit apart to connect the pipes Remove the water tray How to connect the pipes 1. Flaring: Cut a pipe with a pipe cutter. Installation 45
-
Insert a flare nut into a pipe and flare the pipe
Refer to the following table for the dimension of flare nut spaces. Pipe gauge Φ6.4 Φ9.5 Φ12.7 Φ15.9 Φ19.1 Tightening torque 15~16N.m (153~163kgf.cm) 25~26N.m (255~265 kgf.cm) 35~36 N.m (357~367 kgf.cm) 45~47 N.m (459~480 kgf.cm) 65~67 N.m (663~684 kgf.cm) Flare dimension (A) Min Max 8.3 8.7 12.0…
-
How to expel the air with a vacuum pump
Stop valve operation introduction 1. Opening stop valve 1) Remove the cap and turn the valve counter clock-wise with the hexagon wrench. 2) Turn it until the shaft stops. Do not apply excessive force to the stop valve. Doing so may break the valve body, as the valve is not a backseat type. Always…
-
Connect the Drain Pipe
MCAC-UTSM-2009-03 4.2.2 Additional Refrigerant Charge Caution: z Refrigerant cannot be charged until field wiring has been completed. z Refrigerant may only be charged after performing the leak test and the vacuum pumping. z When charging a system, care shall be taken that its maximum permissible…
-
Connect the Drain Pipe
5.2 Drainage test 1) 2) Check whether the drainpipe is unhindered. New built house should have this test done before paving the ceiling. 5.3 Install the drain joint of the outdoor unit Fit the seal into the drain elbow, then insert the drain elbow into the base pan hole of outdoor unit, rotate 90°to…
-
6. Wiring
6.1 MFA-12HRN1-Q (Quick connecter) Attention: Make sure the power supply has been cut off when inserting or pulling out the plug connecters. 1) The connection cables of indoor and outdoor units have been connected to the terminals on the control board. 2) Remove the control cover from the outdoor…
-
6.2 MFA-12HRN1 and MFA-18HRN1
Caution: 1) The appliance shall be installed in accordance with national wiring regulations. 2) The air conditioner should use separate power supply with rated voltage. 3) The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor…
-
Dissemble the bolts from the cover. (If there isn't a cover on the outdoor unit, disassemble the bolts from the maintenance board, and pull it in the direction of the arrow to remove the protection board.) 3. Connect the connective cables to the terminals as identified with their respective matched…
-
6.2.3 Wiring figure
Installation 53
-
Note
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased (depend on model).The actual shape shall prevail. 54 Installation
-
Test Operation
7. Test Operation 1. The test operation must be carried out after the entire installation has been completed. 2. Please confirm the following points before the test operation: z The indoor unit and outdoor unit are installed properly. z Tubing and wiring are correctly completed. z The refrigerant…
-
Control
MCAC-UTSM-2009-03 Part 5 Control 1. Wireless remote controller R51D/E 57 56 Control
-
1. Wireless remote controller R51D/E 1.1 Remote Controller Specifications Model R51D/E,R51D/CE Rated Voltage 3.0V(Alkaline dry batteries LR03×2) Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance Signal Range 8m (when using 3.0 voltage, it Gets 11m) -5 C 60 C Environment 1.2 Introduction…
-
9. MCAC-UTSM-2009-03 TIMER ON Button: Press this button to preset the time ON (start to operate). Each press will increase the time ON setting in 30minutes increments. When the setting time displays 10:00, each press will increase the time ON setting in 60 minutes increments. To cancel the time ON…