Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Канальные сплит-системы MDV серии MDTA, MDFA 76-96-120. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
1.2 Model Names of Units with Cooling and heating
-
2.2 Outdoor Unit
-
2. Specifications
Model Code MDTA-76CRN2 MDTA-76HRN2 MDTA-96CRN2 MDTA-96HRN2 220070900201 220070900191 220070900181 220070900171 Power supply - Rated input power W 11500 11500 14500 14700 Rated current A 28.1 Capacity Btu/h W 75,100 22000 75,100 22000 92,800 27200 91,400 26800 Input W 7500 7500 9200 9200 EER W/W 2.93…
-
Model
Code MDTA-120CRN2 MDTA-120HRN2 220070900161 220070900151 Power supply - Rated input power W 18000 18000 Rated current A 28.7 28.7 Capacity Btu/h W 116,000 34000 116,000 34000 Input W 11900 11900 EER W/W 2.86 2.86 Capacity Btu/h W 139900 41000 Input W 12600 COP W/W 3.25 Indoor air flow 3 m /h 6800…
-
3. Dimensions
-
≥500mm
4. Service Space ≥600mm Electric control box Inspection hole Top view Side view Canvas adapter Muffle Air outlet Muffle Air inlet Inspection hole Air duct system 10 Air filter
-
5. Refrigerant cycle diagrams
5.1 Cooling only: MDTA-76CRN2, MDTA-96CRN2, MDTA-120CRN2 Cooling Stop valve HP Switch Stop valve T3 Outdoor heat-exchanger Indoor unit Discharge temp. sensor Capillary Indoor heat-exchanger Compressors LP Switch T2 Liquid-gas seperator T4 5.3 Cooling and heating: MDTA-76HRN2, MDTA-96HRN2…
-
6. Wiring Diagrams
6.1 MDTA-76CRN2, MDTA-96CRN2 12
-
6.2 MDTA-76HRN2, MDTA-96HN2
6.3 MDTA-120CRN2 13
-
6.4 MDTA-120HRN2
-
7. Capacity Table
-
Outdoor DB(°C)
Indoor WB(°C) CFM DB(°C) 40.60 16.10 TGC SHC 46.10 19.40 PI TGC SHC 22.80 PI TGC SHC 16.10 PI TGC SHC 51.70 19.40 PI SHC PI 16.10 TGC SHC PI TGC SHC 22.80 SHC 23.9 18.41 15.09 8.49 19.98 11.29 8.73 21.25 4.91 8.88 16.9 13.9 8.68 18.4 10.4 8.94 19.6 4.5 9.19 16.1 13.2 10.67 17.3 9.8 11.03 18.4 4.3…
-
7.1 96 kBtu/h
-
Outdoor DB(°C)
40.60 Indoor WB(°C) CFM 16.10 46.10 19.40 22.80 16.10 51.70 19.40 22.80 16.10 19.40 22.80 DB(°C) TGC 23.9 23.8 19.5 10.85 25.4 14.3 11.09 26.7 6.2 11.24 22.3 18.3 11.04 23.8 13.5 11.3 25.0 5.8 11.55 19.6 16.1 12.37 20.9 11.8 12.73 21.9 5.1 12.98 26.7 24.3 22.1 10.88 25.9 16.8 11.12 27.2 11.7 11.27…
-
7.3 120 kBtu/h
-
Outdoor DB(°C)
40.60 Indoor WB(°C) CFM 16.10 46.10 19.40 22.80 DB(°C) TGC 23.9 29.8 24.4 14.37 31.4 17.7 14.61 32.6 SHC PI TGC SHC PI TGC SHC 16.10 PI TGC SHC 51.70 19.40 PI TGC SHC 22.80 PI TGC 7.5 14.76 28.3 23.2 14.56 29.8 16.8 14.82 31.0 SHC 16.10 PI TGC SHC 19.40 PI TGC SHC 22.80 PI TGC 7.2 15.07 29.5 24.2…
-
8. Air flow rate- Static pressure curve
8.1 76kBtu/h 200 Low Static Pressure (Pa) 180 Medium High 3250 3500 3750 4000 4250 4500 4750 5000 5250 5500 Air Flow (m 3/h) 8.2 96kBtu/h 200 Static Pressure (Pa) 180 Low Medium High 3800 4050 4300 4550 4800 5050 5300 5550 5800 6050 6300 Air Flow (m 3/h) 8.3 120kBtu/h 200 Static Pressure (Pa) 180…
-
9. Electric Characteristics
Indoor Unit Power Supply IFM Model Hz Voltage Min. Max. MCA MFA kW FLA MDTA-76CRN2 50 220-240 1.42 6.66 MDTA-76HRN2 50 220-240 1.42 6.66 MDTA-96CRN2 50 220-240 1.8 8.6 MDTA-96HRN2 50 220-240 1.8 8.6 MDTA-120CRN2 50 220-240 198 254 11.25 20 2.1 10 MDTA-120HRN2 50 220-240 198 254 11.25 20 2.1 10 Note…
-
10. Sound Levels
-
12. Troubleshooting
Infrared signal receiver Operation lamp Manual Switch Timer lamp Alarm lamp PRE-DEF lamp(cooling and heating type) or fan only lamp(cooling only type) Room temp. sensor error OPT. Light - TME. Light ☆ DEF. Light - ALARM Light - Manual reset Evaporator temp. sensor error ☆ - - - Manual reset…
-
If the air conditioner fails and does not meet the above phenomena, check the system as the following table: Symptoms Causes The unit does not work Air Power supply fails. Operate after power resumes. Power switch is not connected. Connect the power supply properly. Fuse blows out or circuit breaker…
-
Doors or windows of the room are not closed
tightly. The system is lack of refrigerant. Symptoms Causes Check whether the mode marked on the screen is “AUTO”. The fan speed Fix the leakage places, and charge the proper quantity of refrigerant. Handling methods When the “AUTO” mode is selected, the unit will change the fan speed automatically.…
-
All lamps flashing at 5Hz
Judge 1: The PRO terminal on PCB of indoor unit without connecting to grounding wire Validate: Check whether the PRO terminal on PCB of indoor unit without connected to grounding wire. No Connect it to grounding wire. Yes Judge 2: Optical coupler on PCB malfunction Validate: Check whether the…
-
Timer lamp flashing at 5Hz
Room temperature sensor malfunction Judge 1: Check the room temperature sensor Is break off. Yes Connects it well. No Judge 2: Check the room temperature sensor is abnormal. Validate: Check whether the resistance of the temperature sensor is correct according to Annex 1. Yes Replace indoor PCB. 28…
-
Operation lamp flashing at 5Hz
Evaporate temperature sensor is abnormal. Judge 1: Check evaporate temperature sensor is break off. Yes Replace temperature sensor No Judge 2: Evaporate temperature sensor is abnormal. Validate: Check whether the resistance of the room temperature sensor is correct according to Annex 1. No Replace…
-
Defrosting lamp flashing at 5Hz
Condenser temperature sensor malfunction Yes Replace temperature sensor Judge 1: Check condenser temperature sensor is break off. No Judge 2: Condenser temperature sensor is abnormal. Validate: Check whether the resistance of the condenser temperature sensor is correct according to Annex 1. Yes…
-
1. Features
1. The appearance is novel, luxurious, refined. 2. High capacity of cooling/heating, efficient, and energy-saving. 3. Adopt advanced and high efficient scroll compressor, wide angle and long distance air supply. 4. Remote control standard, screen control optional. 5. Easy installation and…
-
2. Specifications
Model MDFA-76CRN2 220043900081 Code Power supply - Rated input power W Rated current Capacity Cooling Input EER Capacity Heating Input COP MDFA-76HRN2 220043900071 220~240V-1Ph-50Hz 11500 11500 MDFA-96CRN2 220043900061 MDFA-96HRN2 220043900051 220~240V-1Ph-50Hz 14500 14700 A 18.5 18.5 28 28.1 Btu/h…
-
Notes
1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref.…
-
4. Service Space
-
5. Refrigerant cycle diagrams
5.1 Cooling only: MDFA-76CRN2, MDFA-96CRN2 Cooling Stop valve HP Switch Stop valve T3 Outdoor heat-exchanger Indoor unit Discharge temp. sensor Capillary Indoor heat-exchanger Compressors LP Switch T2 Liquid-gas seperator T4 5.2 Cooling and heating: MDFA-76HRN2, MDFA-96HRN2 Cooling HP Switch 4-way…
-
6. Wiring Diagrams
6.1 MDFA-76CRN2, MDFA-96CRN2 CN20 37
-
6.2 MDFA-76HRN2, MDFA-96HRN2
CN20 38
-
7. Capacity Tables
-
Outdoor DB(°C)
40.60 46.10 51.70 Indoor WB(°C) CFM DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI 23.9 18.3 15.0 7.59 19.9 11.2 7.83 21.2 4.9 7.98 16.8 13.8 7.78 18.3 10.4 8.04 19.5 4.5 8.29 16.1 13.2 9.68 17.3 9.8 10.03 18.4 4.3 10.28 26.7 18.7 17.0 7.61…
-
7.2 96kBtu/h
-
Outdoor DB(°C)
40.60 Indoor WB(°C) CFM 16.10 46.10 19.40 22.80 16.10 51.70 19.40 22.80 16.10 19.40 22.80 DB(°C) TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI TGC SHC PI 23.9 24.0 19.7 9.49 25.6 14.5 9.73 26.8 6.2 9.88 22.5 18.5 9.68 24.0 13.6 9.94 25.2 5.8 10.18 20.2 16.5…
-
8. Electric Characteristics
Indoor Unit Power Supply IFM Model Hz Voltage Min. Max. MCA MFA KW FLA MDFA-76CRN2 50 220-240 198 254 3.25 8 0.59 2.773 MDFA-76HRN2 50 220-240 198 254 3.25 8 0.59 2.773 MDFA-96CRN2 50 220-240 198 254 3.25 12 0.59 2.773 MDFA-96HRN2 50 220-240 198 254 3.25 12 0.59 2.773 Note : MCA: Min. Current Amps.…
-
9. Sound Levels
1m 1m Microphone Unit Number Model Noise level under three speeds of fan (dB(A)) 1 MFA-76C(H)R 53 2 MFA-96(H)R 54 11. Troubleshooting Type Code Remarks EEPROM error E0 Manual reset Room temp. sensor error E1 Manual reset Evaporator temp. sensor error E2 Manual reset Evaporator temp. too low…
-
11.1 E1 malfunction
LED indicate E1 Fault of indoor temperature sensor T1 Judge 1: Whether the indoor temperature sensor T1 is break off. Yes Connects it well. No Judge 2: Whether the indoor temperature sensor T1 is malfunction. Validate: Check whether the resistance of the temperature sensor is correct according to…
-
11.2 E2 malfunction
LED indicate E2 Fault of indoor temperature sensor T2 Judge 1: Whether the indoor temperature sensor T2 is break off. Yes Connects it well. No Judge 2: Whether the indoor temperature sensor T2 is malfunction. Validate: Check whether the resistance of the temperature sensor is correct according to…
-
11.3 P1 malfunction
LED indicate P1 Under heating mode, T2 is on high temperature protection Judge 1: Check whether the evaporator temperature sensor T2 is break off. Yes Connect it well. No Judge 2: Whether the evaporator temperature sensor is malfunction. Validate: Check whether the resistance of the temperature…
-
11.4 P2 malfunction
LED indicate P2 Under cooling mode, T2 is on low temperature protection Judge 1: Check whether the evaporator temperature sensor T2 is break off. Yes Connects it well. No Judge 2: Whether the evaporator temperature sensor is malfunction. Validate: Check whether the resistance of the temperature…
-
1. Specifications
Model Code MDOV-76C-CN2 MDOV-76H-CN2 MDOV-96C-CN2 220075900100 220075900090 220075900060 Power supply - Ambient temp range ℃ 21~52 -10~52 21~52 Rated input W 11500 11500 14500 Rated current A Noise level dB(A) Type - Scroll Scroll Scroll Brand - HITACHI HITACHI HITACHI Model - 403DH-64D2Y…
-
Model
Code MDOV-96H-CN2 MDOV-120C-CN2 MDOV-120H-CN2 220075900050 220075900080 220075900070 Power supply - Ambient temp range ℃ -10~52 21~52 -10~52 Rated input W 14700 18000 18000 Rated current A 28.1 28.7 28.7 Noise level dB(A) Type - Scroll Scroll Scroll Brand - HITACHI HITACHI HITACHI Model…
-
2. Dimension
-
3. Service Space
3.1 MDOV-76C(H)-CN2, MDOV-96C(H)-CN2, MDOV-120C(H)-CN2, Air outlet Air inlet Air inlet ≥1000 mm ≥500 mm ≥1000 mm ≥1000 mm ≥1000 mm Note: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. 2. If miscellaneous articles are piled around the…
-
Foundation of the outdoor unit
676 762 ≥500 mm ≥500 mm M12 foundation bolt 4 screws for 1 unit 56
-
4. Wiring Diagrams
-
5. Electric Characteristics
Outdoor Unit Power Supply Compressor OFM Model Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA MDOV-76C-CN2 50 380-415 342 438 15.75 18.5 21.85 48*2 6.3*2 0.573 2.613 MDOV-76H-CN2 50 380-415 342 438 15.75 18.5 21.85 48*2 6.3*2 0.573 2.613 MDOV-96C-CN2 50 380-415 53*2 8.0*2 0.573 2.613 MDOV-96H-CN2…
-
6. Operation Limits
Temperature range for unit operation: Cooling mode Item Heating mode Model Outdoor Indoor Outdoor Indoor All model 21℃~52℃ 17℃~32℃ -10℃~24℃ 20℃~27℃ 7. Sound Levels Standard of testing Outdoor unit Front Note: H = (h+1) / 2 60 Unit Number Model Noise level (dB(A)) 1 MDOV -76C(H) -CN2 63 2 MDOV…
-
9. Troubleshooting
Type LED1 LED2 Remarks Standby ☆ ☆ - Cooling mode ◆ ◇ - Heating mode ◆ ◆ - Defrosting mode ◇ ◆ - Phase sequence protection ◆ ●★ Manual reset Communication failure ◆ ●●★ Manual reset Outdoor condenser temp. sensor error ◆ ●●●★ Manual reset Outdoor ambient temp. sensor error ◆ ●●●●★ Manual reset…
-
Malfunctions
About the Fault of T3A or T3B, High pressure protection, low pressure protection Please refer to the following: Fault of T3A or T3B Judge 1: Whether the sensor is break off. Yes Connects it well. No Judge 2: Whether the sensor is malfunction. Validate: Short-connect the outdoor ambient temperature…
-
High pressure protection
n No Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the high pressure switch is broken Validate: Short connect the high pressure switch socket, check whether the system can run normally Yes…
-
Low pressure protection
Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly No Connect it well Yes Judge 2: Whether the low pressure switch is broken Validate: Short connect the low pressure switch socket, check whether the system can run normally Yes Replace low…
-
2. Installation of Indoor Units
2.1 Installation of Duct ≥500mm 2.1.1 Installation Space Ensure enough space required for installation and maintenance. (Fig-1 and Fig-2) ≥600mm Electric control box Inspection hole Fig-1 Fig -2 2.1.2 Install Φ10 Pendant Bolts Or Ground Bolts (Fig-3) MTA-76C(H)R MTA-96C(H)R MTA-120C(H)R MTA-150C(H)R…
-
A. Wooden structure
Put rectangular sticks across the beams, and set pendant bolts. (Fig-4) Fig-4 B. New concrete roughcast Use embedded bolts, embedded pulling plugs, and embedded stick harness. (Fig-5) Fig-5 C. New concrete roughcast Set it with embedded bushes or embedded bolts. (Fig-6) Fig-6 D. Steel beam and…
-
Pendant bolt
≥30mm Unit body Fig-8 2.1.4 Design and Connection of Duct The duct design must comply with the national heating air conditioner pipeline design specifications. The duct accessories and materials must be produced by professional manufacturers. In order to prevent air flow shorting, do not keep…
-
2.2 Installation of Floor-standing
2.2.1 Installation Space For ensure the proper installation Select the enough solid and level sites. Ensure enough space required for installation and maintenance. (Fig-10and Fig-11) Fig-10 Fig-11 For anti-fall down, please conduct the follow measures: See Fig-12 to fix the feet on the floor after…
-
Put down the air intake panel, before electric connection
Uncover the screw-cap in the air intake panel, and then lessen the screws. Take off the air intake panel; ensure which place secure enough will not make risk to the other people. Fig-13 NOTE: Please beware of the foot screw, which may be hurt for the pass-by people, make sure enough security of…
-
In order to prevent disoperation of the air conditioner, do not interleave or entwine the power cable (380~415V/3N/50Hz) with the connection wires (low-voltage wires) of the indoor/outdoor unit. Power on the indoor unit after performing the airtight test and making a vacuum. 7). Trial run…
-
As shown in Fig-16, leave an interval of 500mm between the outdoor units
≥500 mm ≥500 mm M12 foundation bolt 4 screws for 1 unit Fig-16 The distance of the foundation bolt is shown in Fig-17. 676 762 Fig-17 73
-
3.3 Convey Outdoor Unit
Use 4 steel ropes of a Ф6mm or bigger size to hoist the outdoor unit and convey it into the room. In order to prevent scratch and deformity the outdoor unit, apply a guard board to the surface of contact between the steel ropes and the air conditioner. Remove the cushion for use in the…
-
Snow protection
Snow protection shed at the air inlet shed at the air outlet Snow protection shed at the air inlet Fig-19 3.5 Installation of Refrigerant Pipe The refrigerant pipe adapter is located inside the outdoor unit. When the pipe is connected from the front side, the pipe can be let out through the right…
-
Fig-20
Fig-21 NOTE: When welding the refrigerant pipe, in order to prevent internal oxidation of the pipe, nitrogen must be filled in. Otherwise, the oxidized chips may block refrigerating circulatory system. 3.5.1 Size of Outdoor Unit Pipes and Piping Methods 1) Size of outdoor unit pipes and piping…
-
2) Allowed length of refrigerant pipe and height difference (Fig-22)
Height difference between indoor unit and outdoor unit H 30m Outdoor unit Max. pipe length L 50m Indoor unit Fig-22 Table 1: Max. equivalent length of pipe (L) Max. height difference Height difference between indoor unit and outdoor unit (H) 76, 96, 150 kBtu/h 120 kBtu/h 50m 50m Outdoor upper 30m…
-
3) Connection between indoor unit and outdoor unit (Fig-23)
76, 96, 120 kBtu/h 150 kBtu/h Fig-23 78
-
3.6 Airtight Test
After the pipes between the indoor unit and the outdoor unit are connected, replenish compressed nitrogen to perform airtight test. NOTE: 2 1. The airtight test is performed by using the compressed nitrogen [2.94MPa (30kg/cm G)]. 2. Tighten the spool of the gas valve and liquid valve before…
-
Outdoor unit
Room in which refrigerant is leaked (All refrigerant is leaked) Fig-24 Fig-25 3.12 Completing the Connection System Name In case multiple systems are set, in order to identify the connection system of the indoor unit and outdoor unit, it is necessary to give name to each system, and mark it onto the…
-
4. Heat Insulation of the Pipe
4.1 Heat Insulation of the Pipe In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform condensate prevention and heat insulation properly. CAUTION: If it is forecast that high humidity/temperature environment (condensate temperature is over 23℃) may exist in…
-
5. Installation of Connective Pipe
5.1 Preparation before Installation Check the height difference between the indoor unit and the outdoor unit, and check the length and number of bends of the refrigerant pipeline, which must meet the following requirements: Max. Height difference 30m (If the height difference is greater than 5m…
-
Fig-27
5.2.2 Deploy the pipelines Drill a porthole on the wall, and put the hole sheath and hole cover through the wall. Place the connective pipe together with the indoor & outdoor connection wires. Use wrapping tape to tie them tight. Do not let air penetrate into it lest condensation and drips of…
-
Fig-29
Tighten the nut Align with the connective pipe Screw up the connection pipe nut manually, and use a spanner to tighten it as shown in Fig-30 Fig-30 NOTE: According to the installation conditions, too large torque will damage the flaring, and too small torque will lead to looseness and leakage.…
-
5.3 Expelling Air
5.3.1. From the following table, select a method of expelling air. Table 4: Length of connective pipe (single pass) Procedure of expelling air Less than 5m Use refrigerant in the outdoor unit 5~15m Use vacuum pump or refrigerant tank. If the air conditioner is relocated, be sure to use a vacuum pump…
-
Manifold valve
Multimeter manometer -76cmHg Lo-handle Filler hose Vacuum pum p Filler hose Hi -handle Lo pressure valve Fig-32 Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose of the manifold valve to the maintenance orifice of valve A (tighten both valve A and…
-
Fig-33
5.4 Leak Detection Use soap water or a leak detector to check whether gas leakage exists at the adapters. 5.5 Heat Insulation Use heat insulation materials to wrap the part protruding outside the flared pipe joint and the refrigerant pipe of the liquid pipe and the gas pipe, and ensure that no gap…
-
7. Electric Connection
7.1 Electric field wiring CAUTION: Use special power supply for the air conditioner. Design power supplies specific to the indoor unit and outdoor unit. The supply voltage must comply with the nominal voltage. The external supply circuit of the air conditioner must have a ground wire, and the…
-
Duct type- cooling and heating type: 76 kBtu/h; 96 kBtu/h; 120 kBtu/h,
Floor standing type- cooling only: 76 kBtu/h; 96 kBtu/h, 89
-
Floor standing type- cooling and heating type:76 kBtu/h; 96 kBtu/h,
-
Appendix 1: Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K) 98 MCAC-UTSM-12 ℃ K Ohm ℃ K Ohm ℃ K Ohm ℃ K Ohm -20 115.266 20 12.6431 60 2.35774 100 0.62973 -19 108.146 21 12.0561 61 2.27249 101 0.61148 -18 101.517 22 11.5000 62 2.19073 102 0.59386 -17 96.3423 23 10.9731 63 2.11241 103…