Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Сплит-системы серии MTB-76HWN1, MOV-76HN1-R, MTB-96HWN1, MOV-96HN1-R, MTB-120HWN1, MOV-120HN1-R, MHB-76HWN1, MOV-150HN1-R, MHB-96HWN1, MOV-192HN1-R, MHA-150HWN1, MHA-192HWN1, MFA2-76HRN1, MFA2-96HRN1. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
Split Type TempMaker series Technical Manual Applicable Model: Indoor unit MTB-76HWN1 MTB-96HWN1 MTB-120HWN1 MHB-76HWN1 MHB-96HWN1 MHA-150HWN1 MHA-192HWN1 MFA2-76HRN1 MFA2-96HRN1 Outdoor unit MOV-76HN1-R MOV-96HN1-R MOV-120HN1-R MOV-150HN1-R MOV-192HN1-R Midea reserves the right to discontinue, or…
-
Part. 1 General information
1. Model Names of Indoor/Outdoor Units 3 2. External Appearance 3 3. Nomenclature 4 2
-
1. Model Names of Indoor/Outdoor Units
Indoor unit Type Model Medium static pressure duct type Outdoor unit Power supply Model Capacity Power Cooling Heating supply kW kW MTB-76HWN1 MOV-76HN1-R 22.3 25 MTB-96HWN1 MOV-96HN1-R 28.1 31.1 MTB-120HWN1 MOV-120HN1-R 35.0 38 22.3 25 28.1 31.1 MHB-76HWN1 MOV-76HN1-R 220-240V~, MOV-96HN1-R…
-
2.2 Outdoor unit
MOV-76, MOV-96 MOV-120 MOV-150 MOV-192 3. Nomenclatures 3.1 Indoor unit: M T B – 76 H W N1 Refrigerant type: R410A Controller type W: Wired controller R: Remote controller Heat pump Cooling capacity (76×1,000Btu/h) Series number: A, A1, A2……, B, B1, B2…… Indoor unit T: Med-static pressure duct type…
-
3.2 Outdoor unit
-
1. Features
High capacity of cooling and heating, and energy saving. Thin size, even can installed at limited place. All round steel shell, for high quality protection of transportation. Convenient installation, hidden in the ceiling, unit installation is not hindered by the location of lighting…
-
2. Specifications
Model Power supply MTB-76HWN1 MTB-96HWN1 \ MTB-120HWN1 220-240V~, 1Ph, 50Hz Btu/h 76,000 96,000 120,000 W 22,300 28,100 35,000 Input W 7,500 9,600 11,900 EER W/W 2.97 2.93 2.94 Btu/h 85,300 106,000 129,700 W 25,000 31,100 38,000 Input W 8,300 10,300 12,700 COP W/W 3.01 3.02 2.99 Rated input (Indoor…
-
3. Dimensions (Unit: mm)
MTB-76HWN1, MTB-96HWN1, MTB-120HWN1 Pipe side view Top view 4. Service Spaces Top view 9 MCAC-UTSM-2014-03
-
5. Refrigerant circuits
MTB-76HWN1, MTB-96HWN1, MTB-120HWN1 10
-
MTB-76HWN1, MTB-96HWN1, MTB-120HWN1
11 MCAC-UTSM-2014-03
-
7. Capacity Tables
-
Gross Cooling Capacity (kW)
-
MTB-96HWN1
-
Gross Cooling Capacity (kW)
-
MTB-120HWN1
-
Gross Cooling Capacity (kW)
-
8. Static Pressure Curves
-
MTB-120HWN1
9. Electric Characteristics Model Indoor Unit IFM Hz Voltage Min. Max. MCA MFA kW FLA MTB-76HWN1 50 220-240V 198V 254V 6.2 20 0.5 4.96 MTB-96HWN1 50 220-240V 198V 254V 8.33 20 0.6 6.66 MTB-120HWN1 50 220-240V 198V 254V 10 30 1.1 8 Note: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) IFM…
-
10.Sound Levels
Concealed Duct Type Discharge Duct Suction 1.4m Microphone Model Noise level MTB-76HWN1 56 dB(A) MTB-96HWN1 56 dB(A) MTB-120HWN1 63 dB(A) 11. Accessories Name 20 Qty. Purpose Owner’s manual 1 Installation manual 1 Restriction assembly 1 Connect to system. Water connective pipe 1 Connect to water…
-
1. Features
High capacity of cooling and heating, and energy saving. Thin size, even can installed at limited place. All round steel shell, for high quality protection of transportation. Convenient installation, hidden in the ceiling, unit installation is not hindered by the location of lighting…
-
2. Specifications
Model Power supply MHB-76HWN1 \ MHB-96HWN1 MHA-150HWN1 220-240V~, 1Ph, 50Hz MHA-192HWN1 220-240V~, 1Ph, 50Hz Btu/h 76,000 96,000 150,100 192,000 W 22,300 28,100 44,000 56,300 Input W 7,500 9,600 16,300 22,000 EER W/W 2.97 2.93 2.70 2.56 Btu/h 85,300 106,000 160,300 200,000 W 25,000 31,100 47,000…
-
3. Dimensions (Unit: mm)
MHB-76HWN1, MHB-96HWN1 Pipe side view Top view MHA-150HWN1, MHA-192HWN1 Pipe side view 24
-
Top view
4. Service Spaces Top view 25 MCAC-UTSM-2014-03
-
5. Refrigerant circuits
MHB-76HWN1, MHB-96HWN1: MHA-150HWN1, MHA-192HWN1: 26 R410A 380~415V 3Ph 50Hz TempMaker Series Split AC
-
MHB-76HWN1, MHB-96HWN1
27 MCAC-UTSM-2014-03
-
MHA-150HWN1, MHA-192HWN1
-
7. Capacity Tables
-
Gross Cooling Capacity (kW)
-
MHB-96HWN1
-
Gross Cooling Capacity (kW)
-
MHA-150HWN1
-
Gross Cooling Capacity (kW)
-
MHA-192HWN1
-
Gross Cooling Capacity (kW)
-
8. Static Pressure Curves
-
MHA-150HWN1
MHA-192HWN1 38
-
9. Electric Characteristics
Indoor Unit Model Power Supply Hz Voltage Min. Max. MCA MFA kW FLA MHB-76HWN1 50 220~240V 198V 254V 8.33 20 0.6 6.66 MHB-96HWN1 50 220~240V 198V 254V 11.5 20 1.1 9.2 MHA-150HWN1 50 220~240V 198V 254V 12.5 20 0.9 10 MHA-192HWN1 50 220~240V 198V 254V 19.7 20 1.8 15.75 Note: MCA: Min. Current Amps. (A)…
-
11. Accessories
Name Qty. Purpose Owner’s manual 1 Installation manual 1 Wired controller owner’s manual 1 Water connective pipe 1 Connect to water drainage pipe. Copper nut 2 Connect to refrigerant pipe Wired controller 1 40
-
1. Features
High capacity of cooling and heating, and energy-saving. Thin size, even can installed at limited place. All round steel shell, for high quality protection of transportation. Auto swing louver, wide angle and long distance of air supply. Available for wireless remote control and screen…
-
2. Specifications
Model MFA2-76HRN1 MFA2-96HRN1 \ 220-240V~, 1Ph, 50Hz 220-240V~, 1Ph, 50Hz Btu/h 76,000 96,000 W 22,300 28,100 Input W 7,500 9,600 EER W/W 2.97 2.93 Btu/h 85,300 106,000 W 25,000 31,100 Input W 8,300 10,300 COP W/W 3.01 3.02 Rated input (Indoor unit) W 700 700 Rated current (Indoor unit) A 3.0 3.0 \…
-
3. Dimensions (Unit: mm)
-
4. Service Spaces
Top view Front view 45 MCAC-UTSM-2014-03
-
5. Refrigerant circuits
-
MCAC-UTSM-2014-03
-
Gross Cooling Capacity (kW)
-
таблицы и схемы — в просмотре
-
8. Electric Characteristics
Indoor Unit Model Power Supply IFM Hz Voltage Min. Max. MCA MFA kW FLA MFA2-76HRN1 50 220~240V 198V 254V 3.55 20 0.3 2.84 MFA2-96HRN1 50 220~240V 198V 254V 3.55 20 0.3 2.84 Note: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A) IFM: Indoor Fan Motor kW: Fan Motor Rated Output (kW) FLA: Full Load…
-
1. Specifications
Model MOV-76HN1-R MOV-96HN1-R Power supply \ 380-415V~, 3Ph, 50Hz 380-415V~, 3Ph, 50Hz Ambient temp in cooling °C 17~46 17~46 Ambient temp in heating °C -7~24 -7~24 Rated input (Outdoor unit) W 11,700 14,400 Rated current (Outdoor unit) A 19.3 23.7 dB(A) 68 68 Type ×Qty. \ Scroll ×1 Scroll ×1 Brand…
-
Model
MCAC-UTSM-2014-03 MOV-120HN1-R MOV-150HN1-R Power supply \ 380-415V~, 3Ph, 50Hz 380-415V~, 3Ph, 50Hz Ambient temp in cooling °C 17~46 17~46 Ambient temp in heating °C -7~24 -7~24 Rated input (Outdoor unit) W 17,300 26,900 Rated current (Outdoor unit) A 28.6 47.9 dB(A) 69 70 Type ×Qty. \ Scroll ×1…
-
Model
MOV-192HN1-R Power supply \ 380-415V~, 3Ph, 50Hz Ambient temp in cooling °C 17~46 Ambient temp in heating °C -7~24 Rated input (Outdoor unit) W 32,200 Rated current (Outdoor unit) A 53.8 dB(A) 73 Type ×Qty. \ Scroll ×3 Brand \ Hitachi Model \ E655DH-65D2YG(GC) Capacity W 17,100 Input W 5,700 Rated…
-
2. Dimensions (Unit: mm)
MOV-76HN1-R, MOV-96HN1-R Top view 57 MCAC-UTSM-2014-03
-
MOV-120HN1-R
Top view 58
-
MOV-150HN1-R
Top view MOV-192HN1-R 59 MCAC-UTSM-2014-03
-
Top view
3. Service Spaces Notes: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. 2. If miscellaneous articles are piled around the outdoor unit, such articles must be 400mm below the top of the outdoor unit. 60
-
4. Wiring Diagrams
-
MOV-150HN1-R
-
MOV-192HN1-R
63 MCAC-UTSM-2014-03
-
5. Electric Characteristics
-
1. Notes
CAUTION: Transport the air conditioner with the original package. Do not throw the remote controller and wired controller. If the air conditioner needs to be installed on a metal part of the building, electric insulation must be performed, and the installation must meet the relevant technical…
-
Place like kitchen where oil permeates. Place where strong electromagnetic waves exist. Place where flammable gases or materials exist. Place where acid or alkali gases evaporate, or other special environments. Install the unit in a dry and well ventilated place. Install the unit where the…
-
MTB-76HWN1, MTB-96HWN1, MTB-120HWN1, MHB-76HWN1, MHB-96HWN1
MTA-150HWN1, MTA-192HWN1 When the pandant bolt is fixed in wooden structure, please put rectanglar sticks across the beams, and set pendant bolts. 68
-
MCAC-UTSM-2014-03 When in the new concrete roughcast environment, please use embedded bolts, embedded pulling plugs and stick harness. On steel bar have some holes to hang pipe and embed screw bolts. . When in steel beam and girder structure, set and use supportive angle steel. After install the…
-
will gether on the air heat exchanger and lead to fault and water leak of the air conditioner
In order to suppress noise effectively, install noise suppression and sound insulation devices, especially in the noise-sensitive spaces such as meeting rooms. For connection of the flange plane, use non-flammable canvas adapter to prevent transmission of vibration. Use M6×20 screws (configured…
-
View of top side (Unit: mm)
View of air inlet side MHA-150HWN1 View of air outlet side (Unit: mm) 71 MCAC-UTSM-2014-03
-
View of air inlet side (Unit: mm)
MHA-192HWN1 View of air outlet side (Unit: mm) View of air inlet side (Unit: mm) 2.3 Install the drainage pipe Install a drain stream trap in the drainpipe to prevent water from overflowing. In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform 72
-
condensate prevention and heat insulation properly
If it is forecast that high humidity and temperature environment (condensate temperature is over 23°C) may exist in the ceiling, e.g., inside the ceiling with slab, (ceiling which is in the same environment as the outdoor air), it is necessary to apply 10mm or thicker adiabatic wool (16~20kg/m2)…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC For anti-fall down, please conduct the follow measure: a. Fix the feet on the floor after select a proper place for installation, since the height of the unit casing is very high. b. The right and left sides as weel as rear can be fixed, it is…
-
3.2 Install the drainage pipe
There is natural drain, it is should be confirmed that the height of drain pipe is not higher than water collection tray. The number of bends and folds of the drain pipe should not exceed 2. Try to avoid bends in order to prevent trash accumulation. Charge water into water collection tray…
-
MOV-76HN1-R
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC MOV-120HN1-R MOV-96HN1-R MOV-150HN1-R MOV-192HN1-R In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. If miscellaneous articles are piled around the outdoor unit, such articles must be 400 mm…
-
MOV-192HN1-R
As the following shown picture, leave an interval between the multi-outdoor unit. Snow protection facilities must be installed in the snowfall areas. In order to prevent influence caused by snow, set up raised pavilion, and install snow protection sheds at the air inlet and air outlet. The snow…
-
5. Connection of Refrigerant Pipe
Schematic diagram of connection between indoor unit and outdoor unit: MTB-76HWN1 + MOV-76HN1-R MTB-96HWN1 + MOV-96HN1-R MHB-76HWN1 + MOV-76HN1-R MHB-96HWN1 + MOV-96HN1-R MTB-12HWN1 + MOV-120HN1-R 79 MCAC-UTSM-2014-03
-
MHA-150HWN1 + MOV-150HN1-R
MHA-192HWN1 + MOV-192HN1-R MFA2-76HRN1 + MOV-76HN1-R MFA2-96HRN1 + MOV-96HN1-R The refrigerant pipe adapter is located inside the outdoor unit. So remove the right front board first, and remove M5 screws. When the pipe is connected from the front side, the pipe can be led out through the right…
-
must be filled in. Otherwise, the oxidized chips may block refrigerating circulatory system
Trash and foreign matters may come into the pipe in the process of installing the refrigerant pipe. Be sure to blow them off with nitrogen before connecting the pipe to the outdoor units. Use high-pressure nitrogen to clean the pipelines. Do not use the refrigerant of the outdoor unit for…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC Allowed length of refrigerant pipe and height difference. Allowed value Max. actual length of pipe (L) Max. height difference between indoor and outdoor unit 50m Outdoor unit (upper) 25m Outdoor unit (lower) 30m Max. number of bends 15 Do not…
-
MCAC-UTSM-2014-03 Braze the liquid line to the high pressure valve (liquid valve) at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to continue flowing. Carefully remove the rubber plugs from the evaporator liquid and vapor connections at the indoor unit. …
-
just touches the chamfered retaining wall
Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be replaced to prevent leaks. Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result. After the pipes between the indoor unit and the outdoor…
-
spool of valve B counter-clockwise for 45 degrees and stay for about 10 seconds, and
then close the spool of valve B tightly. Detect leak for all adapters at A, B, C and D. After making sure that no leak exists, open the maintenance orifice nut of valve A. After all air is expelled, tighten the maintenance orifice nut of valve A. Open the spools of valves A and B completely. …
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose of the manifold valve to the maintenance orifice of valve A (Tighten both valve A and valve B). Connect the filler hose adapter to the vacuum pump. Open the low…
-
MCAC-UTSM-2014-03 After vacuum, according to the diameter and length of the connective pipe of liquid side between the indoor unit and outdoor unit, calculate the refrigerant replenishment quantity. The refrigerant for replenishment is R410A. Diameter of liquid-side pipe Quantity of refrigerant…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC In order to keep the refrigerant density below the threshold value, please install a mechanic ventilation device. (Perform ventilation often.) In case frequent ventilation is impossible, please install the leakage detection alarm device linked with…
-
also be applied to the refrigerant joint and the pipe joint
Note: the heat insulation of drain pipe refer to the installation of indoor unit. Please use heat-resistant materials as heat insulation material of the air-side pipe. (e.g., EPT) Cover heat insulation materials separately at the liquid side and the air side. Moreover, perform heat insulation…
-
wiring according to the national rule
The appliance shall be installed in accordance with national wiring regulations. 7.2 Specifications of power supply Type Model Power Indoor unit MTB-76HWN1 MHB-76HWN1 MOV-76HN1-R 220-240V~, 1Ph, 50Hz 380-415V~, 3Ph, 50Hz 20A/10A 60A/40A 3×2.5mm (Includes grounded wire) \ \ 5×6mm Switch capacity of…
-
Type
Indoor unit Outdoor unit Model MHA1-150HWN1 MOV-150HN1-R Power 220-240V~, 1Ph, 50Hz 380-415V~, 3Ph, 50Hz 20A/12A 70A/50A 3×2.5mm (Includes grounded wire) \ \ 5×16mm Switch capacity of the main power supply / Fuse Indoor unit power cable 2 Outdoor unit power cable includes grounded wire Connective…
-
7.3 Schematic diagram
7.4 Electric wire diagram When connect the wire, pay attention to the phase sequence of the power supply. If the phase sequence is reversed, the compressor will not start. Meanwhile, the fault indicator of the outdoor electric control board will light up. After shifting the phase sequence, power on…
-
Floor standing type
93 MCAC-UTSM-2014-03
-
8. Duct Design Scheme
It is only available for duct type indoor unit. Examples of construction and ventilation pipeline design scheme (Flowering hidden series.) Construction and ventilation pipeline design scheme 94
-
Methods of configuring and selecting installation
Material name Characteristics, advantages and other contents ` 1. Install the filter at the main body grille in case the store height is low, and at the main body of the indoor unit in case the store height is high. 1 2. It cleans conveniently at the time of installing/uninstalling the filter. 3.…
-
1. Fixed model that diffuses air at a 360 angle
2. The outline size should increase when the air volume is over 350CMH. (For above 303), i.e., when about 9 diffusers are required, the 7 outline size should increase. 3. The diffuser pipes should preferably have the same length after branching, and the minimum length of the ventilation pipes is 5m.…
-
1. Low noise compared with other air outlets. Applicable to tall buildings
that require a long distance of air conditioning. 2. Select the ventilation pipe connection caliber according to the 12 distance and the air speed. 3. Applicable to store height of over 5m (for design of tall stores such as temple, consult manufacturer). 1. Flanges and pipelines connected to the…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC Use the remote controller or wired controller to let the air conditioner run in the cooling mode. Inspect the following items according to the operation manual. If any fault occurs, remove the fault first. Check the indoor unit: Whether any…
-
must be performed by professional maintainers
This phenomenon may also occur when the air conditioner shifts from defrosting operation to heating operation. That is because the moist generated by defrosting is expelled as steam. Noise of air conditioner When the air conditioner runs in the cooling, dry or heating mode automatically, grave…
-
10.2 Faults of air conditioner and cause
If any of the following exceptions occur, operation of the air conditioner will be immediately stopped. Turn off the power switch, and check it. The Run indicator blinks quickly (2 blinks per second.). After turning off the power switch and then turning it on again, that indicator still blinks…
-
Symptom
The cooling effect is poor. Symptom The unit keep starting up and shutting down frequently. Possible causes MCAC-UTSM-2014-03 Way of handing The condenser or evaporator is too dirty. Clean the heat-exchanger. The filter is blocked. Clean the filter. The intake orifice or exhaust orifice of the…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC The transmitting symbol ▲ does not blink. Symptom Check item Cause Pressing ON/OFF button, the remote controller signal cannot be transmitted. Check whether the batteries of remote controller are low. When the batteries are exhausted, the signals…
-
10.4 Duct type indoor unit malfunction and protection codes
Names of indicators in receiving kit Display content All lamps flashing at 5Hz Timer lamp flashing at 5Hz Operation lamp flashing at 5Hz Defrosting lamp flashing at 5Hz Alarm lamp flashing at 5Hz Fault or protection meaning Lack of neutral line. T1, room temperature sensor, fault of open circuit…
-
Timer lamp flashing at 5Hz, Operation lamp flashing at 5Hz
Defrosting lamp flashing at 5Hz For these series products, if the condenser temperature sensor malfunction is displayed, it is enough to check whether wiring has problem. If the wiring is correct, the PCB should be replaced. Operation lamp and timer lamp flashing at 5Hz 10.5 Floor standing type…
-
E0
E1, E2 P1, P2 They are the normal protection. Under the cooling mode, when the pipe’s temperature of evaporator is too low, the protection will be triggered to avoid ice covering the evaporator. Under the heating mode, once the pipe’s temperature is too high, the P2 protection will be triggered. 105
-
10.6 Outdoor unit malfunction and protection codes
Type LED1 LED2 Phase sequence or lack of phase. ● ☆★ Communication error. ● ☆☆★ Condenser temperature sensor error. ● ☆☆☆★ Ambient temperature sensor error ● ☆☆☆☆★ System low pressure protection. O ☆★ Three times low pressure protections within 1 hour. ☆ ☆★ System hi-pressure protection…
-
Communication error
Condenser temperature sensor error Ambient temperature sensor error 107 MCAC-UTSM-2014-03
-
System low pressure protection
Three times low pressure protections within 1 hour 108
-
System high pressure protection
109 MCAC-UTSM-2014-03
-
Hi-temperature protection of compressor discharger
Current overload protection Note: The value of current protection is 26A for 76000Btu/h outdoor unit, 28A for 96000Btu/h outdoor unit, 110
-
30A for 12000Btu/h outdoor unit, 26A for 15000Btu/h outdoor, 28A for 192000Btu/h outdoor unit
High temperature protection of condenser 11. Maintenance Operation required before leaving the unit idle for a long period. Let the air conditioner run in the fan mode for about half a day, and let its interior be fully dry. Switch off the power by the button in remote controller, and then cut…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC Startup after a long period out of service. Check the following issues: Check whether the air inlet or outlet of the indoor unit and outdoor unit is blocked. Remove foreign substance if any. Check whether the ground wire is connected properly. Check…
-
Part. 6 Controller
1. Wireless Remote Controller (Standard for floor-standing) 114 2. Wired Controller: KJR-29B (Standard for duct) 120 3. 113 Centralized Controller: MD-CCM03(A) (Optional) 132
-
1. Wireless Remote Controller (Standard for floor-standing)
1.1 Remote controller specifications Model R51/E Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it Gets 11m) Environment Temperature Range -5°C~60°C Performance Features 1. Operating Mode: Cooling, Heating, Dry, Fan and Auto. 2. Timer…
-
2. MODE Select Button: Each time you push the button, a mode is selected in a sequence that
goes from AUTO, COOL, DRY, HEAT and FAN as the following figure indicates: 3. SWING Button: Push this switch button to change the louver angle. 4. RESET Button: When the RESET button is pushed, all of the current settings are cancelled and the control will return to the initial settings. 5. ECONOMIC…
-
1.3 Names and functions of indicators on remote controller
①TRANSMISSION Indicator: This indicator lights when remote controller transmits signals to indoor unit. ② MODE Display: Show the current operation modes-- AUTO, COOL, DRY and HEAT. HEAT is only available for heat pump model. ③ LOCK display: To displayed by pushing the LOCK button. Push the LOCK…
-
MCAC-UTSM-2014-03 To install batteries, slide back the cover of the battery compartment and install the batteries according to the directions (+and -) shown on the Remote Controller. ※ To replace the old batteries, use the same method as mentioned above. Notes: 1. When replacing batteries do not use…
-
HEATING mode, the most comfortable settings are 28°C or below
※ Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW. ※ Push the ON/OFF button. The operation lamp lights and the air conditioner start to operate per your settings. Push the ON/OFF button again to stop this unit operation. Notes: The FAN ONLY mode cannot be used to control the…
-
MCAC-UTSM-2014-03 Push the TIMER button and the remote controller will show the last set time for the START operation and the signal "h" will be shown on the display panel. You are now ready to readjust the TIMER OFF to stop the operation. ※ Push the TEMP button to cancel the TIMER ON setting. The…
-
2. Keep the Remote Controller away any liquids
3. Protect the Remote Controller from high temperatures and exposure to radiation. 4. Keep the indoor receiver out of direct sunlight or the air conditioner may malfunction. 5. Keep controller away from EMI (Electro-Magnetic Interference) supplied by other household appliances. 2. Wired Controller…
-
2.2 Wired controller outlook
2.3 Operation instructions 1) Remote signal receiving function: the wired controller can be a remote signal receiving device, it is possible to use the wireless remote controller to control the air conditioner through the wired controller when the system have been powered on. Notes: The wired…
-
3) Set the operating mode
Press the mode button to set the operating mode, after each button press the operating mode will circle as follow: Notes: When the controller has been set to cool only, then there is no HEAT mode. 4) Fan speed setting Under COOL, HEAT and FAN modes, press the fan speed button can adjust the fan…
-
Under the timer on setting status, press the timer/clock setting button
timer off setting status, and the screen will display and , then enter into the . The setting method of timer off is the same as the timer on. Under timer setting state, set the timer on and the timer off to be 0.0h can cancel timer on and time off. Notes: If the wired controller has been set timer…
-
Under the locking state, the wired controller will not respond to the buttons pressing and the
control instruction from the wireless remote controller. Simultaneously press the temperature adjusting buttons and again can cancel the locking state. 10) Air filter cleaning reminding function The wired controller records the total running time of the indoor unit, when the accumulated running time…
-
2.4 Installation of wired controller
1) Safety precaution Stated below are important safety issues that must be obeyed. Confirm there is no abnormal phenomena during test operation after complete. Installation by other persons may lead to imperfect installation, electric shock or fire. Improper installation may lead to electric…
-
3) Supplied assemblies on the site
Qty (Embedded into wall) Specification (Only for reference) Remarks 4-core shielded cable 1 0.5mm2×4 The longest is 15m. 86 Electrician box 1 \ \ Wiring tube (Insulating sleeve and tightening screw.) 1 \ \ Name 4) Installation procedure The installation manual contains information about the…
-
Wiring principle sketch: Wiring figure: MCAC-UTSM-2014-03 Connect two terminals of embedded 4-core shielding wire with the switching wires of wired controller and signal receiving board. Make sure the sequence of 4 terminals (A, B, C and D) should correspond to the wire sequence of signal…
-
Use straight head screwdriver to insert into the buckling position in the bottom of wired
controller, and spin the screwdriver to take down the back cover. Pay attention to spinning direction, otherwise will damage the back cover. Use three M4×20 screws to directly install the back cover on the wall. Use two M4×25 screws to install the back cover on the 86 electrician box, and use one…
-
Use cross head screws to fix the wired controller bottom cover in the electrical box through
the screw bar. Make sure the wired controller bottom cover is on the same level after installation, and then install the wired controller back to the bottom cover. Over fasten the screw will lead to deformation of back cover. Neaten the wires of the wired controller There are three positions of…
-
Avoid the water enter into the wired controller, use trap and putty to seal the connectors of
wires during wiring installation. When under installation, reserve certain length of the connecting wire for convenient to take down the wired controller while during maintenance. Wired controller’s front cover installation: After adjusting the front cover and then buckle the front cover. Avoid…
-
Step2: The value of the first code ‘X’ is ‘0’, press the temperature setting buttons
and to adjust the second code value. Step3: After setting the second code value, press Quiet/OK button to switch the first code to the next value. Step4: When the first code value is ‘6’, press Quiet/OK button again to exit the parameters setting. The parameter setting table First code Second code…
-
3. Centralized Controller: MD-CCM03(A) (Optional)
3.1 Centralized controller specifications Model Power Supply Voltage Ambient Temperature Range Ambient Humidity Range MD-CCM03(A) 220~240V 50Hz 1Ph -15°C~43°C RH40%~RH90% Performance Features 1. System composition, centralized control. 2. Keywords and general function description. 3. Technical…
-
single-machine setting is selected, the operation is performed for the air conditioner of the
current address only. If the remote controller of the air conditioner is locked currently, issue the lock command; otherwise, send the lock command. If the single-machine mode is not selected, and the remote controller of one or more currently selected air conditioners is locked, issue the unlock…
-
the key again, and the operation will be performed for all air conditioners in the network
Press it repeatedly to shift between single setting and global setting. 4) QUERY: Any time when pressing the key, the selected operation mode is to query the operation status of the air conditioner. By default, the first in-service air conditioner will be queried. Through the ADD and REDUCE keys…
-
previous air conditioner will be displayed. If it is currently on the first machine, press it again,
and the data of the last machine will be displayed. If this key was held down, the address will decrease one by one. In the setting mode, every time when pressing the key, if it is in single operation mode, the air conditioner of previous in-service address number will be selected. If it is in the…
-
the last page will be displayed. In the setting mode, every time when pressing the key, if it is
in the temperature regulation mode, the set temperature will decrease by 1°C (or 2°C) until the lowest allowed set temperature. If it is in the timing startup/shutdown time setting mode, select the upper-level set time, if no time is set, 0.0 will be displayed, if hold down the key, the upper-level…
-
result is the same as the result of restoring power-on after power failure
16) ON/OFF: Any time when pressing the key, the centralized startup/shutdown operation is performed for all current in-service air conditioners in the centralized controller network. If all in-service air conditioners in the network are in the power-off status, press the key to perform the startup…
-
*: The matrix is composed of 4×16 grids and each grid is composed of two blocks of different sizes
The matrix include horizontal coordinates 00-15 and vertical coordinates 00+, 16+, 32+ and 48+, which indicate the address of the indoor unit. The sum of the horizontal coordinate and vertical coordinate of the grid is the address of the grid. Each grid corresponds to an indoor unit of this address.…
-
controller is a master, and the air conditioner is a slave. In the LAN composed of computer
and centralized controller, the computer or gateway is a master, and the centralized controller is a slave. The schematic diagram of network control system composition of air conditioner: 2) Keywords and general function description: Power on or reset: When the centralized controller is powered…
-
indicator goes off. If an in-service air conditioner in the network is faulty, or the centralized
controller network itself is faulty, the indicator will blink at 2Hz. If one or more in-service air conditioners in the network are running, including under setting of timing start or shutdown, the indicator will be luminous. Otherwise, the indicator is off. Locking of centralized controller…
-
until the foregoing switch is turned off. If the foregoing two switches are turned on
concurrently, the emergent shutdown switch shall have preference. 3.5 General display data entries 1) General display data is displayed in all display pages. Under the interconnected control of the computer or gateway, the data is displayed in graphic ( ). Otherwise, no data is displayed. If the…
-
R410A 380~415V 3Ph 50Hz TempMaker Series Split AC Indoor temperature display: display range: 00~99°C. The indoor temperature is displayed concurrently. If the temperature is higher than 99°C, 99°C will be displayed. If the temperature value is invalid, ‘--‘ will be displayed. If timing startup or…
-
In the matrix, the bid dots from (00, 16+) to (15, 32+) are luminous, and the small dots
are not luminous. It indicates the 32 air conditioners with the addresses from 16 to 47 are powered off. In the matrix, the big and small dots from (09, 48+) to (12, 48+) are not luminous. It indicates the four air conditioners with the address from 57 to 60 are outside the network. All other big…
-
In the matrix, only the big and small black dots at (00, 00+) and (01, 00+) are luminous
It indicates the in-service and power-on status of the air conditioners with the addresses of 00 and 01. The centralized controller communicates with the computer normally. Description of the setting page The LCD displays the setting page, and queries the air conditioner with the address of 08.…
-
The centralized controller communicates with the computer normally
Fault code table: Fault code Fault content EF Other faults ED Outdoor unit fault protection EA Over-current of compressor (4 times) E9 Fault of communication between main board and display board E7 EEPROM error E6 Zero crossing detection error E5 T3 or T4 temperature sensor fault E4 T2B sensor fault…
-
3.6 Installation
The wireless remote controller is the standard controller for split series air conditioner. Wired controller as optional controller can directly be connected with the display board of the indoor units. Centralized controller should be connected with the main PCB board of the indoor unit through…
-
Connect the network interface module with the port CN20 in the main PCB board of indoor unit through the signal wire, which is as the attachment of the module. Fix the network interface module on the wall near the indoor unit. And set the different address of the indoor unit. 2) The installation of…
-
According to size of the hole in controller body, fix the controller on the place as needed. (Unit
mm) 148
-
3) The wire connection
149 MCAC-UTSM-2014-03
-
4) System wiring instruction
Wiring diagram of building network air conditioning system Wiring diagram with good communication effect Wiring diagram with poor communication effect (not recommended because it may lead to poor communication 150
-
MCAC-UTSM-2014-03 System wiring diagram of centralized monitoring and indoor unit of air conditioner Both of the following wiring modes of centralized monitor and indoor unit are applicable: (Quantity of indoor units connected with each centralized monitor is less than or equal to 64). 151