Инструкция на Полупромышленные и промышленные кондиционеры MDV (сервис мануалы)
Колонные кондиционеры серии MFS2i-24ARN1, MFS2i-48ARN1. Сервис мануал.
Смотрите также: Коды ошибок →
Загружаем документ…
Текст инструкции
-
SERVICE MANUAL
MIDEA AIRCONDITIONER FLOOR STANDING TYPE Model: MFS2i-24ARN1 MFS2i-48ARN1
-
1. Safety Precautions
1.1 Precaution To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service unit, be sure to read this service manual at first. 1.2 Installation For electrical…
-
1.4 Operational
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft). Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system. Do not block the inlet or outlet of air…
-
2. Dimension
-
2.2 Outdoor Unit
-
3. Refrigerant cycle diagram
3.1Heat pump mode 5
-
4 . Wiring diagram
4.1 MFS2i-24ARN1 Indoor Unit Outdoor Unit 6
-
MFS2i-48ARN1 Indoor Unit Outdoor Unit 7
-
5.Installation details
5.1 Installation place 5.1.1 Indoor Unit a. A place which provides the spaces around the indoor unit as required above in the diagram. b. A place where is no obstacle near the inlet and outlet area. c. A place which can bear the weight of the indoor unit. d. A place which allows the air filter to be…
-
Caution
Installation in the following places may cause trouble. If it is unavoidable to use in such places, please consult with the dealer. a. A place full of machine oil. b. A saline place such as coast. c. Hot-spring resort. d. A place full of sulfide gas. e. A place where there are high frequency…
-
2. Dismounting the air-inlet grid
Please take off the air-inlet grid before connecting the pipes/wires. Pull down the two knobs on the grid, take off the two screws, then the air-inlet grid goes free. 3. Take the Pipe Clip off before connecting the pipes and wiring; fit it when these finished. Use accessories to connect the…
-
5.2.2 Outdoor Unit
1. Ship the a/c to the installation place originally packed; 2. Be careful while hanging the unit because the center of gravity of the unit is not centralized; 3. Do not make the angle of inclination more than 45 degrees while shipping;(Avoid horizontal storage) 4. Be sure the electric insulation…
-
5.3 Refrigerant pipe connection
5.3.1 Pipe length and the elevation The correct refrigerant quantity filled in the 5-meter-long pipe of the outdoor unit is marked on the Product Data Plate. If you have to use longer pipe for every meter plus pipe, the refrigerant should be added according to the following calculation. Pipe size…
-
a)
Only the correctly installing of indoor and outdoor unit done, can the refrigerant pipe be connected. b) The cut-off valves are completely close before ex-work. Before connecting the refrigerant pipe, be careful to check whether the valves are completely close. c) The connecting procedure of…
-
Notes for the bendable pipe
a. The bendable pipe should be used on the indoor side; b. Bend angel may not exceed 90 degrees; c. The bend location should be made on the center of the pipe if possible, as for bend radius, the bigger the better; d. The bendable pipe may not be bent for more than 3 times. Bend the thin pipe a.…
-
refrigerant oil;
2.Check and make sure there is no leakage by soap-water or leakage-checker after connecting; 3.Be sure the connecting joint on the indoor side is insulated. 4.Use two wrenches to connecting the pipes. Additional Outside diameter Torque tightening torque mm inch N.cm N.cm Ф9.52 3/8 3270 3990 Ф12.7…
-
5.3.3 Air purging with vacuum pump
Air and moisture in the refrigerant system have undesirable effects as below: ● ● ● ● ● Pressure in the system rises. Operating current rises. Cooling or heating efficiency drops. Moisture in the refrigerant circuit may freeze and block capillary tubing. Water may lead to corrosion of parts in the…
-
nut of the Lo valve on the gas pipe side and check the air is entering. (Operation noise of
the vacuum pump changes and a compound meter indicates 0 stead of minutes) 5. After the evacuation is complete, fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Make evacuation for 15 minutes or more and check the compound meter indicates -76cmHg. 6.…
-
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait…
-
5.3.5 Re-air purging (Re-installation)
Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed. 3. Air purging. Open the valves on the charging cylinder and the…
-
Close the valve on the charging cylinder and discharge the refrigerant until the gauge
indicates 0.3 to 0.5 Mpa. 6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems. 7. Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten…
-
3. Open the valves (Low side) on the charge set and discharge the refrigerant until
the gauge indicates 0.05 to 0.1Mpa. If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to apply an evacuation.…
-
4. Disconnect the charge hose from the vacuum pump
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle. 5.3.8 Gas charging Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.If the refrigerant…
-
refrigerant
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time (approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the…
-
5.5 Wiring
Please refer to the Wiring Diagram. Note: The power supply of the air conditioner is different according to the models. Please refer to the WIRING DIAGRAM pasted on the indoor and outdoor units before wire connection. 5.6 TEST RUN Perform test operation after completing gas leak and electrical…
-
6.External view and display
6.1 External view This unit consists of indoor unit and outdoor unit. Note: The above air conditioner's outer shape is based on the standard model, so it may be different from the one you purchased. Air Outlet Control Panel(LCD) Air Inlet Drain Pipe Refrigerant Pipe Let the conditioned air go out…
-
6.2 CONTROL PANEL
Control Buttons and Functions 7.Operation characteristics Mode Cooling Drying Heating operation Temperature operation operation Room temperature 17℃~32℃ 17℃~30℃ 17℃~32℃ Outdoor temperature 18℃~43℃ -7℃~24℃ 18℃~ 43℃ CAUTION: 1. If air conditioner is used outside of the above conditions, certain safety…
-
8.Electronic function
8.1 Main data Introduction Ts : Set temperature, T1 : Room temperature T2: Evaporator pipe temperature T3: Condenser pipe temperature T4: Outdoor ambient temperature 8.2 Operation Modes and Functions 8.2.1Manual Operation 8.2.2 Heating Mode 8.2.2.1 Four-way valve opens at once , while defrosting…
-
list 1
Room temperature up Room temperature down Condition Indoor fan speed T2<25°C Off 25°C <T2<32°C Low T2>32°C Set fan speed T2>22°C Set fan speed 22°C >T2>20°C Low T2<20°C Off 8.2.3 Defrost (only available to heating mode) 8.2.3.1 Defrosting Conditions Starting Of Defrosting Condition (meet one of the…
-
8.2.3.3 Ending Of Defrosting Condition (meet one of the following is ok)
(1)Time of defrosting lasts 10 minutes. (2) Temperature of outdoor coil T3 is up to 8°C and continues to 80 seconds. (3) Temperature of outdoor coil T3 is up to 15°C. 8.2.4 Cooling Mode 8.2.4.1 Four-way valve is closed. If four-way valve is open before the machine enters cooling mode, then four-way…
-
8.2.5 Dehumidifying Mode
8.2.5.1 Indoor fan speed is low. 8.2.5.2 Four-way valve is closed,. the compressor and outdoor fan will operate the same as in cooling mode. 8.2.6 Auto Mode 8.2.6.1. Under auto mode, the indoor fan is set to be auto and the temperature is 24°C. 8.2.6.2 When entering auto mode, the heating, fan only…
-
9.Characteristic of temperature sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ -10 62.2756 17 14.6181 44 4.3874 -9 58.7079 18 13.918 45 4.2126 -8 56.3694 19 13.2631 46 4.0459 -7 52.2438 20 12.6431 47 3.8867 -6 49.3161 21 12.0561 48 3.7348 -5 46.5725 22 11.5 49 3.5896 -4 44 23 10.9731 50 3.451 -3 41.5878 24 10.4736…
-
Room temperature up
Room temperature down 10.1.3 Condition Outdoor fan Compressor T2>56°C Off On T2>62°C Off Off T2>50°C Off Off T2<50°C On On Evaporator Protection against low temperature 10.1.3.1 Only available under cooling and dehumidifying status. 10.1.3.2 Protection principle: Condition Outdoor fan Compressor…
-
Self-diagnosis Codes Contents P4 Protection of temperature of indoor evaporator P5 Protection of temperature of outdoor condenser P9 Defrosting or anti-cold air E1 Open-circuit and short-circuit of indoor temperature sensors T1 E2 Temp. sensor T2 on indoor evaporator is open circuit or short circuit…
-
Troubles and Solutions Before calling for service, please review the following list of common problems and solutions. Problem Possible Cause Solutions Air conditioner does not operate at all Power failure Wait for power restoring The power supply is disconnected. Switch on the main power switch The…
-
The following displays indicate an error or problem(24K)
Number Display code Problems What to do E1 E2 E3 Temperature Sensor is off or short-circuit. Contact service people The temperature of the evaporator of indoor unit is too low or high (For the protection feature, the compressor turns off automatically) The temperature of the evaporator of indoor…
-
The following displays indicate an error or problem(48K)
Number Display code Problems What to do 1 E1 E2 E3 Temperature Sensor is off or short-circuit. Contact service people 2 E6 Outdoor unit protection Contact service people The temperature of the evaporator of indoor unit is too low or high (For the protection feature, the compressor turns off…