2. External Appearance
MRA MRC { SHAPE \* MERGEFORMAT }
-
3. Model Number Nomenclature
-
4. Feature & Benefits
4.1. The adoption of anticorrosive-box The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint. The appearance is stylish and be easy for maintenance. (Has been 1000 hours salt spray test) 4.2. The adoption of credible protection system 4.2.1. The…
-
5. Specifications
Table 1 Sale Model Power supply Capacity Input Rated current Capacity Heating Input Rated current Max. input consumption Max. current Starting current Model Type Brand Capacity Input Compressor Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand…
-
Table 2
Sale Model Power supply Cooling Heating Capacity Input Rated current Capacity Input Rated current Max. input consumption Max. current Starting current Compressor Indoor fan motor Indoor coil Model Type Brand Capacity Input Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor…
-
Table 3
Sale Model Power supply Capacity Input Rated current Capacity Heating Input Rated current Max. input consumption Max. current Starting current Model Type Brand Capacity Input Compressor Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Indoor fan…
-
Table 4
Sale Model Power supply Capacity Input Rated current Capacity Heating Input Rated current Max. input consumption Max. current Starting current Model Type Brand Capacity Input Compressor Rated current(RLA) Locked rotor Amp(LRA) Thermal protector Capacitor Refrigerant oil Model Type Brand Indoor fan…
-
1. Dimensional Drawings
a) MRA Package net dimensions: Width 1290mm; Depth 1030mm; Height as the following chart: Capacity(Btu/h) A(Height) 24000~36000 630 mm 48000~60000 830 mm { SHAPE \* MERGEFORMAT }
-
b) MRC
{ SHAPE \* MERGEFORMAT }
-
2. Wiring Diagrams
a) 50HZ (MRA/MRC) MDRA -24HWN2 { SHAPE \* MERGEFORMAT }
-
MDRA-36HWN2
MDRA-48HWN2 { SHAPE \* MERGEFORMAT } MDRA-60HWN2 { SHAPE \* MERGEFORMAT }
-
R22 Rooftop Package Unit 50/60Hz
-
MDRA-36HWN2
-
MDRA-60HWN2
-
MDRC -36HWN2
Cooling Heating MDRC-48HWN2 Cooling Heating { SHAPE \* MERGEFORMAT }
-
MDRC -60HWN2
Cooling Heating { SHAPE \* MERGEFORMAT }
-
4. Electrical Data
a) 50Hz Power Supply Compressor Evaporator fan motor Condenser fan motor Model MCA TOCA MFA MSC RLA IPT Qty FLA IPT Qty FLA IPT Qty MDRA -24HWN2 12.0 2.45 1 2.8 0.65 1 1.2 0.24 1 MDRA-36HWN2 6.8 3.8 1 2.8 0.65 1 1.2 0.24 1 MDRA-48HWN2 7.2 4.45 1 3.8 0.86 1 1.2 0.24 1 MDRA-60HW 9.3 5.45 1 3.8 0.86 1…
-
5. Refrigerant Cycle Diagram
a) Cooling Only High Pressure Switch Condenser Comp Capillary Low Pressure Switch Evaporator b) Heat Pump High Pressure Switch Comp 4-way Valve Condenser Capillary Low Pressure Switch Evaporator { SHAPE \* MERGEFORMAT }
-
7. Installation
a) Accessories Standard accessories: Name of accessories Quantity Outline Manual 1 ―― Drain outlet 1 Snap ring 1 Drain pipe 1 b) General Information Important: read this entire manual before beginning installation procedures. Caution: Bodily injury can result from high voltage electrical components…
-
Notice
Warnings and cautions appear at appropriate locations throughout this manual. Read these carefully. Warning: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Caution: Indicates a potentially hazardous situation which, if not avoided, may…
-
d) Locations and Recommendations
i. Horizontal Airflow Application These units are designed certified for outdoor installations. These units may be installed directly on wood flooring or on Class A, Class B, or Class C roof covering material. Location of the unit must allow service clearance around it. Clearance of the unit must be…
-
a local engineer
See the unit's nameplate for the absolute minimum clearance between the unit and any combustible surface(s). e) Installation Rooftop Units For roof top applications using a field fabricated frame and ducts, use the following procedure: The frame must be located and secured by bolting or welding to…
-
Ground Level -- Horizontal Units
For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of the supply and return air ducts are as short as possible. Proceed with the…
-
Attaching Downflow Ductwork to Roof Curb Supply and return air flanges are provided on the roof curb for easy duct installation. All ductwork must be run and attached to the curb before the unit is set into place. Follow these guidelines for ductwork construction: Connections to the unit should be…
-
Note
Knock down the control box access panel, first twist off screws and then up it, the control box access panel is getting out. g) Start–Up Packaging and Components Is the unit properly located and level with the proper clearance? Is the duct work correctly sized, run, taped, insulated , and…
-
h) Maintenance
Routine Maintenance by Owner You can do some of the periodic maintenance functions for your unit yourself; this includes cleaning the permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and conducting a general unit inspection on a regular basis Cleaning the Air Filter 1.…
-
● The air-in side should face up when using vacuum cleaner
● The air-in side should face down when using water. Caution: Do not dry out the air filter under direct sunshine or with fire. 3. Re-install the air filter Condenser Coil Unfiltered air circulates through the unit's condenser coil and can cause the coil's surface to become clogged with dust, dirt…
-
8. System Operation
a) LED Display The control would display any fault code that is currently active using the LED. The control will display the fault code, when the LEDS are flashing quickly; there is something wrong with the system. Refer to below table for detail fault code. Function: 1. the compressor and indoor…