2. External Appearance
12.5~25Ton:
-
3. Model Number Nomenclature
M R C Ti - 250 C W N2 Refrigerant N2: R407C W: Wired Controller Function Code C: Cooling Only H:Cooling and Heating Cooling Capacity(12.5 Ton) Product Series T: T3 Condition Product Design Sequence B: Optional two air outlet ways:side and below C: One air outlet way:side Rooftop Package MDV
-
4. Feature & Benefits
1. The adoption of anticorrosive-box The reinforced anticorrosion by using galvanization armor plate and coated with man-composed paint. The appearance is stylish and be easy for maintenance. (Has been 1000 hours salt spray test) 2. The adoption of credible protection system 2.1 The protection of…
-
5. List of Functions
5.1 STANDARD SPECIFICATIONS A. General Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground. The packaged unit consists of scroll compressors, cooling coil, condenser coil, control wiring and interconnecting piping- all factory assembled and mounted…
-
selected to operate at 25% below first critical speed. Pillow block bearing are selected for at 200,000 hours average life at design operating conditions. Shaft is turned, ground and polished from solid steel. Fans and pulleys are keyed to shaft and designed for continuous operation at maximum motor…
-
Nominal ton
-
таблицы и схемы — в просмотре
-
8. Wiring Diagrams
8.7 MRCTi-250CWN2
-
9. Performance Data
Cooling capacity for 25Ton: Air Flow CFM Ent DB (℉) Entering Wet Bulb (℉) 73 Ambient Temperature(℉) Notes: 9500 75 80 10000 MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC 1. All capacities are gross and have not considered…
-
Heating capacity for 25Ton
Net Capacities(kW)-10000 CFM Peak Net Heating(kW) at Indicated Dry Bulb(℃) Outdoor Temp(℃) 70% RH Notes: Peak Total Power(KW) at Indicated Dry Bulb(℃) -15 49.5 46.5 45.5 44.8 23.0 25.3 26.8 28.3 -12 53.3 51.0 50.0 49.5 23.5 25.8 27.0 28.8 -9 56.5 55.0 54.5 54.5 23.8 26.0 27.3 29.3 -6 59.3 57.5 57.0…
-
10. Electrical Data
Evaporator fan Condenser fan VOL Hz Ph Max. l Min. STC RNC IPT RNC IPT RNC IPT Auxiliary h IPT i MRCTi-250CWN2 380-415 50.2 27.2 10 7.5 6.5 3.4 MRCTi-250HWN2 380-415 50.2 27.2 10 7.5 6.5 3.4 Model Applicable Unit main power Compressor motor VOL: Unit Power Supply Rated (plated) Voltage (V) Note: Hz…
-
11. Parameter and Pressure Chart for Air Volume
11.11 Model: 25Ton Parameter table for indoor unit air volume: Static pressure (Pa) Air flow (CFM) 12450 11400 11125 10000 10325 10200 9900 9790 9300 8600 Brake power (kW) 6.4 6 5.8 5.7 5.53 5.4 5.24 5.17 5.01 4.7 Fan speed (rpm) 1000 1002 1003 1005 1006 1008 1010 1015 1017 1022 Static pressure (Pa)…
-
12. Refrigerant Cycle Diagram
Cooling only type(6.2 and above): Condenser T3 Pressure check port Pressure check port High pressure switch Low pressure switch TP Comp B Low pressure switch Pressure check port Pressure check port T2 T2 Evaporator Capillary Comp A High pressure switch Capillary TP T3
-
Cooling and Heating type
T3 T3 Condersor High-pressure switch TP High-pressure switch TP Low-pressure switch Low-pressure switch Comp B Comp A Capillary (Thermal expansion valve for optional) Four-way valve Four-way valve Evaporator T2 T2 TP: Compressor discharge temperature sensor in system A and B T2: Indoor coil…
-
13. Operation Limit
13.1 Cooling only and cooling with auxiliary heater Outdoor temperature(℃ DB) Cooling only and cooling only with auxiliary heater Standard operation Indoor temperature(℃ WB) Temperature Outdoor temperature Indoor temperature Without auxiliary electric heater models 18℃~52℃ 17℃~30℃ With auxiliary…
-
Temperature
Model Cooling model Outdoor temperature Indoor temperature 18℃~52℃ 17℃~30℃ Outdoor temperature Indoor temperature -5℃~24℃ 17℃~30℃ Heating model Standard operation Indoor temperature(℃ WB) Temperature Model Heating model
-
14. Installations
14.1 Service Space 1. The recommended clearances for single-unit installations are illustrated in following Fig. These minimum requirements are not only an important consideration when determining unit placement, but they are also essential to ensure adequate serviceability, maximum capacity, and…
-
Typical rooftop application with frame:
-
Typical rooftop application with frame
14.3 Ground Level Horizontal Units For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure. Be sure the outdoor portion of the supply and return air ducts are as…
-
Typical ground level application
14.4 Installation of condensate drain piping 14.5 Ductwork 1. Attaching horizontal ductwork to unit 1) All conditioned air ductwork should be insulated to minimize heating and cooling duct losses. Use a minimum of two (2) inches of insulation with a vapor barrier. The outside ductwork must be…
-
2) When attaching ductwork to a horizontal unit, provide a flexible watertight connection to prevent noise transmission from the unit to the ducts. The flexible connection must be indoors and made out of heavy canvas. Note: Do not draw the canvas taut between the solid ducts. 2. Attaching downflow…
-
15. Wired Controller
1. Standard unit with Midea’s wired controller: KJR-12B/DP (T)-E KJR-12B/DP (T)-E 2. Optional well-known brand thermostat controller: KJR-23B: For cooling only and cooling with auxiliary heater KJR-25B: For Cooling and heating KJR-23B KJR-25B
-
Note:When select KJR-12B wire controller, please make sure SW3 have been set at“ON”, otherwise it
-
16. Error Code
16.1 Error Code for 5ton and below No. Code LED1(Red) LED2(Yellow) LED3(Green) 1 Standby OFF OFF ON 2 Function ON ON ON Flash Flash Flash Flash Flash OFF 3 Phase-missing Phase-error Indoor Ambient Temp. Sensor T1 Failure 4 High Pressure Protection Vent Protection 5 Indoor Coil Temp. Sensor T2…
-
Protection
Protection for condenser Hi-temp. in sys. B P9 Auto reset Protection Anti-freezing protection for evaporator in sys. A Pc Auto reset Protection Anti-freezing protection for evaporator in sys. B Pd Auto reset Protection Defrosting dF Auto reset 17. Accessories Name Quantity Manual 1 Drain outlet 1…
-
18. Maintenance and Upkeep
Regular maintenance and upkeep Some regular maintenance and upkeep have been carry on by user, includes: change the one-time dust filter, clean casing, wash condenser and replace a new belt, as well as do some test for the equipment. Model 6.2 Ton 7.5 Ton 12.5 Ton 15 Ton 25 Ton A 328mm 555mm Model…
-
Regulating belt of rate of tension, inner fan Refer to the following Fig. fixed bolt of electric motor’s supporting slide was loosened, following electric motor was droved, belt of rate of tension will begin change. Method of belt tensioning using belt tension indicator Calculate the deflection in…
-
Appendix 1: Indoor Temp. and Pipe Temp. Sensor Resistance Value Table (℃--K)