Part 1 General information
1. MCCU introduction Midea R407C MCCU (Compressor Condensing Unit) can be free connected with other indoor coils through a set of connection accessories (supplied by factory). There are 2 air discharge types, 7 sizes and totally 14 models for MCCU. They are designed to work in a wide ambient…
-
3. Product lineup
-
4. Nomenclature
-
6. Refrigerant cycle diagram
Cooling only: 4.1 MCCU-7CN2 HP Switch Stop valve Outdoor heat-exchanger Stop valve Accumulator Cooling Sight glass Filter drier Compressor LP Switch TXV Solenoid valve Connection accessories Indoor unit 4.2 MCCU-10CN2,MCCU-14CN2 Cooling Stop valve HP Switch Stop valve T3 Outdoor heat-exchanger Sight…
-
4.3 MCCU-16CN2
Cooling Stop valve HP Switch Stop valve T3 Outdoor heat-exchanger Sight glass Discharge temp. sensor Filter drier Compressor LP Switch TXV Liquid-gas seperator Solenoid valve Connection accessories Indoor unit 4.4 MCCU-22CN2, MCCU-28CN2, MCCU-35CN2 Cooling Stop valve HP Switch Stop valve T3 Outdoor…
-
4.5 MCCU-45CN2
Cooling Heating T3 HP Switch 4-way valve Stop valve Stop valve Outdoor heat-exchanger Sight glass Discharge temp. sensor TXV Check valve Compressor LP Switch Liquid-gas seperator Filter drier TXV Check valve Solenoid valve Connection accessories Indoor unit Cooling and heating: 4.6 MCCU-7HN2 Cooling…
-
Cooling T3 Stop valve Outdoor heat-exchanger 4-way valve Stop valve Heating Sight glass TXV Check valve HP Switch Filter drier Discharge temp. sensor TXV Compressor Check valve LP Switch Solenoid valve Connection accessories Indoor unit 6.8 MCCU-16HN2 Cooling T3 HP Switch Muffler 4-way valve Stop…
-
Cooling T3 Stop valve Outdoor heat-exchanger HP Switch Muffler 4-way valve Stop valve Heating Sight glass Discharge temp. sensor TXV Check valve Compressor LP Switch Liquid-gas seperator Filter drier TXV Check valve Solenoid valve Connection accessories Indoor unit 6.10 MCCU-35HN2 Cooling T3 HP…
-
6.11 MCCU-45HN2
Cooling T3 HP Switch 4-way valve Stop valve Outdoor heat-exchanger Stop valve Heating Sight glass Discharge temp. sensor TXV Check valve Compressor LP Switch Liquid-gas seperator Filter drier TXV Check valve Solenoid valve Connection accessories Indoor unit 11
-
7. Connection accessory list
For cooling only units: Capacity kW Qty. Model Qty. Model Qty. Model Qty. Thermal expansion valve Model Qty. Sight glass Model Solenoid valve Solenoid valve coil Drier filter 7 SGN+10s 1 EVR6 1 018F6251 1 DTG63016-33C 1 TGEZ2.5 1 10 SGN+10s 1 EVR6 1 018F6251 1 DTG63016-33C 1 TGEZ2.5 1 14 SGN+12s 1…
-
8. Specifications – Cooling only
-
(Continued)
-
Specifications – Cooling and heating
Model MCCU-7HN2 MCCU-10HN2 MCCU-14HN2 MCCU-16HN2 220-240V/1N/50Hz 380V/3N/50Hz 380V/3N/50Hz 380V/3N/50Hz ℃ -10~45 -10~45 -10~45 -10~45 Power supply Ambient temp. range Cooling Heating Capacity W 7000 10000 14000 16000 Rated input W 3133 4333 4956 6033 Max. input W 3500 5800 6400 7400 2.23 2.31 2.83…
-
(Continued)
-
9. Dimensions
-
Technical Mannual MCAC C-UTSM-20112-05 d un nits—22kW, 28kW cooliing only unitts 9.2 Dimensionss of vertical discharge Fig. 1-4 9.3 Dimensionss of vertical discharge d un nits—22kW, 28kW cooliing and heating units 1615 Fig. 1-5 18
-
9.4 Dimensionss of vertical discharge
-
10. Wiring diagram- cooling only
10.1 MCCU-7CN2 20
-
10.2 MCCU-10CN2
21 R407C MCCU Technical Manual
-
10.3 MCCU-14CN2
-
10.4 MCCU-16CN2
23 R407C MCCU Technical Manual
-
10.5 MCCU-22CN2
-
10.6 MCCU-28CN2
25 R407C MCCU Technical Manual
-
10.7 MCCU-35CN2
-
10.8 MCCU-45CN2
27 R407C MCCU Technical Manual
-
Cooling and heating
10.9 MCCU-7HN2 28
-
MCCU-14HN2 MCAC-UTSM-2012-05 30
-
MCCU-22HN2 MCAC-UTSM-2012-05 32
-
C-UTSM-20112-05
11 Exploded view- coo oling only 11.1 MCCU-7CN2 No o. P Part Name QTY BOM Co ode No. Parrt Name QTY BOM Code e 1 Motor 1 202400400 0724 14.2 E-part box 1 20124820000 09 2 Motor b bracket 1 201245320 0906 14.3 Motor capa acitor 1 20240110035 53 3 Rear ne et 1 201148200 0003 14.4 Contactor 1…
-
11.2 MCCU-10CN2
No. 37 Part Name R407C MCCU Technical Manual QTY BOM Code No. Part Name QTY BOM Code 1 Motor 1 202400440401 11.4 Wire joint, 5p 1 202301450039 2 Motor bracket assy’ 1 201275590020 11.5 AC contactor 1 202300850046 3 Rear net 1 201148700000 11.6 Main control board assy’ 1 201347890001 4 Condenser…
-
11.3 MCCU-14CN2
No. BOM Code No. Motor 1 202400440401 11.5 Motor bracket assy’ 1 201275590020 11.6 3 Rear net 1 201148700000 11.7 Part Name MCAC-UTSM-2012-05 QTY Part Name QTY BOM Code AC contactor 1 202300850046 Main control board assy’ 1 201347890001 Wire joint,4p 1 202301450003 Condenser assy’ 1 201575690018…
-
11.4 MCCU-16CN2
No. QTY BOM Code No. Condenser assy’ 1 201575890056 19 Motor bracket assy’ 1 201275600085 19.1 3.1 Motor 1 202400400185 20 3.2 1 2 Part Name R407C MCCU Technical Manual Part Name QTY BOM Code High pressure valve assy’ 1 201675890381 Low pressure valve 1 201600720098 Discharge pipe assy’ 1…
-
Part
Name R407C MCCU Technical Manual QTY BOM Code No. Part Name QTY BOM Code 1 top cover welding part 1 201275990072 12.12 Three-phase power protection devices 1 202301600518 2 low pressure valve assy’ 1 201675990295 13 front-right support pillar 1 201275990070 2.1 Pipe joint 1 201601200004 14…
-
2 Part R407C MCCU Technical Manual Name Welding together pieces of roof Low-pressure valve assembly 2.1 Pipe joint 2.2 Cube Valve 3 Electronic control mounting plate 4 box QTY BOM Code No. Part 1 201275990102 13 1 201675990276 1 1 Name QTY BOM Code Front right column 1 201275990109 14 Induction…
-
Part
R407C MCCU Technical Manual Name Qty No. Part Name Qty 1 Vertical plate 1 19 Inlet pipe ass’y of condenser 1 2 Air outlet grille 2 20 Cover to E‐box 1 3 Discharge pipe ass’y 1 21 Fixing plate of E‐box 1 4 Cover ass’y 1 22 E‐box ass’y 1 5 Axial fan 1 22.1 E‐box 1 6 Middle rear vertical plate 1 22.2…
-
Part
Name R407C MCCU Technical Manual QTY BOM Code No. Part Name QTY BOM Code 1 Rear net 2 201295100172 22 Front-right supporting board 1 201295100163 2 Top cover 2 201195100000 23 Separator 1 201601100036 3 Axial flow fan 2 201100300205 24 Net 1 201295100157 5 Cover board 2 201295100149 25 Motor bracket…
-
C-UTSM-20112-05
Coo oling and heating 11.9 9 MCCU-7HN N2 No. Pa art Name QTY BOM Cod de No. Part Name QTY BOM Code 1 Motor 1 2024004007 724 13 E-part box assy’ a 1 20337539001 Motor bra acket 1 2012453209 906 13.1 AC contacto or 1 20230085004 Rear net 1 2011482000 003 13.2 Wire joint, 5p 1 20230145003 Condensser…
-
MCCU-10HN2 No. 49 Part Name R407C MCCU Technical Manual QTY BOM Code No. Part Name QTY BOM Code 1 Motor 1 202400440401 13.3 Wire joint 1 202301450117 2 Motor bracket assy’ 1 201275590020 13.4 Wire joint, 5p 1 202301450039 3 Rear net 1 201148700000 13.5 AC contactor 1 202300850046 4 Condenser assy’ 1…
-
MCCU-14HN2 No. BOM Code No. Part Motor 1 202400440401 13.4 Wire joint, 5p 1 202301450039 2 Motor bracket assy’ 1 201275590020 13.5 AC contactor 1 202300850046 3 Rear net 1 201148700000 13.6 Main controller assy’ 1 201347890001 4 Condenser assy’ 1 201575790015 13.7 Wire joint,4p 1 202301450003 5…
-
MCCU-16HN2 Name R407C MCCU Technical Manual No. Part BOM Code No. Part 1 Condenser assy’ QTY 1 201575890058 19.1 Low pressure valve Name 1 QTY 201600720098 BOM Code 2 Motor bracket assy’ 1 201275600085 20 Discharge pipe assy’ 1 201675890379 3.1 Motor 1 202400400185 20.1 Branch pipe 1 201600500210…
-
Rear left vertical supporter 1 201295590027 18 High pressure valve 1 202301820005 2 Front right vertical supporter 1 201295590030 19 High temp. switch 1 202301820008 3 Rear right vertical supporter 1 201295590028 20 Low pressure valve assy’ 1 201657600010 4 Side cover panel 2 201295590012 20.1 Low…
-
Part
R407C MCCU Technical Manual Name Qty No. Part Name Qty 1 Vertical plate 1 21 Fixing plate of E‐box 1 2 Air outlet grille 2 22 E‐box ass’y 1 3 Discharge pipe ass’y 1 22.1 E‐box 1 3.1 Check valve 2 22.2 Transformer 1 4 Cover ass’y 1 22.3 PCB ass’y 1 5 Axial fan 1 22.4 Three‐phase protector 1 6 Middle…
-
22 2 201195100000 23 Front-right board Separator 2 201100300205 24 Net Cover board 2 201295100149 25 6 Middle supporting assy’ 2 201295100167 7 Wind baffle assy’ 1 201295030814 8 E-part box assy’ 1 203375990000 8.1 Main control board assy’ 1 201375990000 8.2 Current detecting board assy’ 1 8.3…
-
Part 2 Installation
1. Note Install the unit where enough space of installation and maintenance is available. Install the unit where the ceiling is horizontal and enough for bearing the weight of the indoor unit. Install the unit where the air inlet and outlet are not baffled and are the least affected by…
-
2. Installation steps
2.1 Installation Check the model and name to avoid mistaken installation. 2.2 Refrigerant pipe The refrigerant pipes must have the specified diameter. Nitrogen of a certain pressure must be filled into the refrigerant pipe before welding. The refrigerant pipe must undergo heat insulation…
-
3. Unit location
≥600mm 3.1 When installing the unit, leave a space for maintenance shown in the following figure. Install the power supply at the side of the outdoor unit. 3.2 Ensure enough space for installation and maintenance. Side discharge units (Fig 2-1 and Fig 2-2): Fix with bolt Fig 2-1 ≥300mm (Wall or…
-
Vertical discharge units (Fig 2-3 and Fig 2-4)
R407C MCCU Technical Manual Air outlet Air inlet Air inlet Fig 2-3 ≥1000 mm ≥500 mm ≥1000 mm ≥1000 mm ≥1000 mm Fig 2-4 Note: 1. In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the outdoor unit. 2. If miscellaneous articles are piled around the outdoor unit…
-
3.4 Unit transportation
Use 4 steel ropes of a Ф6mm or bigger size to hoist the unit and convey it into the room. In order to prevent scratch and deformity the unit, apply a guard board to the surface of contact between the steel ropes and the air conditioner. Remove the cushion for use in the transport after…
-
T Manual 4. Installatio on of refrig gerant pip pes 4.1 The T refrigerrant pipe ada apter is located inside th he outdoor unit. u When th he pipe is coonnected fro om the front side, the pipe can be let out throu ugh the right front board d. (Fig 2-8 and a Fig 2-9) So remove the left frontt board…
-
4.6 Size of refrigerant pipes
-
4.8 The max. equivalent length of piping and the max. height difference between indoor unit and outdoor unit should check the following table and sketch. (Fig 2-11) Height difference between indoor unit and outdoor unit H Outdoor unit Max. pipe length L Indoor unit Fig 2-11 Table 1 (Unit: m) Model…
-
5. Piping between outdoor unit and indoor unit
5.1 Preparation before Installation Check the height difference between the indoor unit and the outdoor unit, and check the length and number of bends of the refrigerant pipeline, which must meet the following requirements: Max. Height difference 30m (If the height difference is greater than 5m…
-
5.2.6. Put on an heat resistance envelope at connective pipe adapter of the indoor unit, and wrap it tight with the wrapping tape lest condensate and leakage. 5.3 Expelling Air 5.3.1 Select a method to expel air from the following table: Length of connective pipe (single pass) Less than 5m 5~15m…
-
C-UTSM-20112-05
M Manifold va alve Multimete r manometter -76cmHg Hi -han ndle Lo-handle Filler hose e Vacuum pum p Fil ler hose Lo pressure p va alve Fig 2-13 Loosen L and remove the maintenanc ce orifice nu t of valve A,, and connec ct the filler hhose of the manifold m valvve to the maintena ance…
-
5.5 Heat Insulation
Use heat insulation materials to wrap the part protruding outside the flared pipe joint and the refrigerant pipe of the liquid pipe and the gas pipe, and ensure that no gap exists between them. Imperfect heat insulation may lead to condensate drips. 69
-
6. Field wiring
CAUTION: Use special power supply for the air conditioner. Design power supplies specific to the indoor unit and outdoor unit. The supply voltage must comply with the nominal voltage. The external supply circuit of the air conditioner must have a ground wire, and the power supply ground wire of…
-
Part 3 Trouble shooting
1. Malfunctions If any of the following malfunctions occur, stop operation of the air conditioner immediately. Turn off the power switch, and contact the local after sales service center of manufacturer: The fuse blows out frequently, or the circuit breaker protection occurs frequently. …
-
2. Trouble shooting
About the Fault of temperature sensor, high pressure protection, low pressure protection. Please refer to the following: Fault of temp. sensor Judge 1: Whether the sensor is break off. Yes Connects it well. No Judge 2: Whether the sensor is malfunction. Validate: Short-connect the outdoor ambient…
-
High pressure protection
No Judge 1: Whether the wiring between the high pressure switch and main control board is connected well or correctly Connect it well Yes Judge 2: Whether the high pressure switch is broken Validate: Short connect the high pressure switch socket, check whether the system can run normally Yes Replace…
-
Low pressure protection
Judge 1: The wiring between the low pressure switch and main control board is connected well or correctly No Connect it well Yes Judge 2: Whether the low pressure switch is broken Validate: Short connect the low pressure switch socket, check whether the system can run normally Yes Replace low…