Midea Commercial Air Conditioner
R410A DC Inverter V4 Plus Outdoor Unit 50Hz Technical Service Manual R410A Heat Pump Type DC Inverter VRF
-
1. Features
1.1 Energy saving V4+ realized the industry's top class energy efficiency by adoption of brushless reluctance DC compressor control,DC Fan motor and improved heat exchanger. 1.1.1 High efficiency DC inverter compressor New structure-enhanced mid-frequency performance Specially designed scroll…
-
1.2.3 Flexible piping design
Piping length Permitted value (m) Total pipe length 500 Max. actual pipe length 150 Max. equivalent pipe length 175 Equivalent pipe length from the first indoor branch to the 40 farthest indoor unit Level difference between Outdoor unit is down: 70m outdoor unit and indoor unit Outdoor unit is up…
-
1.4 Enhanced comfort
1.4.1 Night silent operation mode Midea's Night Silent Mode feature which is easily set on the PCB board allows the unit to be set to vary time 1→X: 6 hours, Y:time 10 hoursoptimizing -Model 2→X: Y: 10 hours options during Non-Peak and Peak-Model operation the8 hours, units noise output. Capacity %…
-
1.5 Convenient installation & maintenance
1.5.1 Auto addressing Outdoor unit can distribute address for each indoor unit automatically. Wireless and wired controllers can enquire and modify each indoor unit’s address. 1.5.2 Simple communication wiring Centralized controller (CCM03) can connect from indoor side or outdoor side (XYE…
-
2. Outdoor units
-
3. Indoor units lineup
Cassette type One-way cassette Capacity Compact four-way Two-way cassette cassette Four-way cassette (×100W) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Duct type Capacity Low static Medium static pressure duct pressure duct High static pressure duct (×100W) ● 15 18 ● 22 ● ● 28 ● ● 36 ●…
-
Indoor units lineup
Floor-standing/Ceiling & Floor/Console Cased floor-standing Uncased floor-standing Ceiling & floor console 22 ● ● ● 28 ● ● ● 36 ● ● ● ● 45 ● ● ● ● 56 ● ● ● 71 ● ● ● 80 ● ● ● Capacity (×100W) 90 ● 112 ● 140 ● 160 ● Wall mounted/Fresh air processing unit Capacity (×100W) Wall mounted Wall mounted Wall…
-
4. Nomenclature
4.1 Outdoor unit MDV – 252 (8) W / D R N1 i (B) Series code i: Individual module Omit: Combinable module Refrigerant type N1: R410A Power supply R: 380-415V, 3Ph, 50Hz Inverter Type D: DC Inverter Omit: AC Inverter Outdoor Unit Cooling Capacity (HP), (only for combinable type) Cooling Capacity…
-
Part 2 Selection Procedure
1. Introduction 11 2. Unit selection (Based on cooling load) 15 10 Selection Procedure
-
1 Introduction
1.1 Model Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load, calculate the maximum air-conditioning load for each room or zone. Selection of an air conditioning…
-
1.3 Outdoor Unit Selection
Allowable combinations are indicated in INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE. In general, outdoor unit can be selected as follows though the location of the unit, zoning and usage of the rooms may be considered. The indoor and outdoor unit combination is determined that the sum of…
-
INDOOR UNIT CAPACITY INDEX
Unit Size Model 15 Model 18 Model 22 Model 28 Model 36 Model 45 Model 56 Model 71 Model 80 Model 90 Capacity Index (kW) 1.5 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 Unit Size Model 112 Model 140 Model 160 Model 200 Model 250 Model 280 Model 400 Model 450 Model 560 Capacity Index (kW) 11.2 14.0 1.3Actual…
-
1.4.2Heating capacity modification
Modification coefficient of the length and high difference of refrigerant pipe: L: Refrigerant pipe equivalent length H: Height difference between outdoor and indoor 14 Selection Procedure
-
2 Unit selection (Based on cooling load)
2.1Given condition 2.1.1Design condition (Cooling: Indoor 20°C (WB), Outdoor 35°C (DB)) 2.1.2Cooling load Location Room A Room B Room C Room D Room E Room F Load (kW) 2.1 2.8 3.5 4.6 5.8 7.2 2.1.3 Power supply unit: Outdoor 380~415V-3Ph-50Hz, Indoor 220~240V-1Ph-50Hz. 2.1.4Pipe length: 50m…
-
2.4 Conclusion
Generally, we think this result is acceptable, so we have accomplished the calculation. But if you consider this result is not acceptable, you can repeat the above process. Remark: In this sample, we don’t consider the other capacity modification index and assume 1.0 as them value. For more details…
-
1. Specifications
-
Number of rows
Tube pitch(a)×row pitch(b) mm 25.4×22 25.4×22 25.4×22 Fin spacing mm 1.6 1.6 1.6 Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum Ф7.94 Ф7.94 Ф7.94 Inner-grooved Inner-grooved Inner-grooved 1924.5×1252.5 1924.5×1252.5 2661.5×1252.5 m /h 11700 11700 15600 External static pressure Pa…
-
Model
-
Tube pitch(a)× row
pitch(b) mm 25.4×22 25.4×22 Fin spacing mm 1.6 1.6 Hydrophilic aluminum Hydrophilic aluminum Ф7.94 Ф7.94 Inner-grooved Inner-grooved 2661.5×1252.5 2661.5×1252.5 22 22 Fin type Tube outside diameter mm Tube type Coil length ×height mm Number of circuits 3 Outdoor air flow m /h 15600 15600 Pa 0~20…
-
2. Dimensions
2.1 8HP/10HP Dimensions: 22 Specification & Performance
-
Liquid side
(The connected pipe diameter Φ12.7) Gauge point Detect the pressure/ Refrigerant replenishment Oil balancer For parallel connect the modular units Gas side (The connected pipe diameter Φ25.4) Specification & Performance 23
-
24 Specification & Performance
-
Liquid side
(The connected pipe diameter Φ15.9) Gauge point Detect the pressure/ Refrigerant replenishment Oil balancer For parallel connect the modular units Gas side (The connected pipe diameter Φ31.8) 2.3 Valve explanation Connect the liquid pipe (accessory, field installation) Oil balance pipe (only for…
-
2.4 Position of foot screw bolt (Unit: mm)
-
3. Piping Diagrams
DC Fan SV6 SV1 M Stop Valve (High Pressure) EXV A Heat Exchanger High Pressure Accumulator Stop Valve (Low Pressure) One-way Valve ST1 SV5 Oil Balance One-way Valve High Pressure Sensor SENP Oil Separator One-way Valve Compressor FIX Compressor INVERTER High Pressure Switch HPS SV4 Gas-liquid…
-
Key Components
Oil Separator: is used to separate oil from high pressure & high temperature refrigerant gas that is pumped out from compressor.The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon. High pressure accumulator: is used to store the surplus liquid…
-
4. Electric Characteristics
Outdoor Unit Model Power Supply Compressor Hz Voltage Min. Max. MCA TOCA MFA MSC MDV-252(8)W/DRN1(B) 50 380~415 342 440 19.1 20.8 25 MDV-280(10)W/DRN1(B) 50 380~415 22.1 MDV-335(12)W/ DRN1(B) 50 380~415 342 440 23.4 23.7 MDV-400(14)W/ DRN1(B) 50 380~415 342 440 33.9 MDV-450(16)W/ DRN1(B) 50 380~415…
-
5. Wiring Diagrams and Field Wiring
5.1 Wiring Diagrams for 8~16HP 30 Specification & Performance
-
5.2 Field Wiring
a) Terminal of Outdoor unit b) Wiring between Indoor and Outdoor unit Note: 1. The signal wire between outdoor units, indoor and outdoor units and indoor units has polarity. When connecting, be careful to prevent error connection. 2 2. Signal wire shall adopt three-core shielded wire with a diameter…
-
6. Operation Limits
Cooling Heating -5 -10 -15 -20 -5 -10 10 20 Range for continuous operation 35 25 Range for intermittent operation Outdoor temperature (℃ DB) 40 30 Outdoor temperature (℃ WB) 45 Range for intermittent operation Range for continuous operation Indoor temperature (℃ WB) Indoor temperature (℃ DB) Notes…
-
7. Capacity Tables
-
70% 34 MCAC-VTSM-2013-08 10 17.01 2.03 20.25 2.45 23.58 2.91 25.20 3.14 26.82 3.38 30.15 3.86 31.86 4.00 12 17.01 2.06 20.25 2.50 23.58 2.96 25.20 3.20 26.82 3.44 30.15 3.93 31.41 3.97 14 17.01 2.10 20.25 2.55 23.58 3.02 25.20 3.26 26.82 3.51 30.15 4.01 31.05 3.95 16 17.01 2.14 20.25 2.60 23.58 3.08…
-
Note: 1, R410A DC Inverter V4 Plus 50Hz 23 11.88 1.57 14.22 1.88 16.47 2.21 17.64 2.41 18.81 2.62 21.06 3.06 23.40 3.55 25 11.88 1.60 14.22 1.96 16.47 2.35 17.64 2.57 18.81 2.79 21.06 3.28 23.40 3.79 27 11.88 1.69 14.22 2.08 16.47 2.51 17.64 2.74 18.81 2.98 21.06 3.50 23.40 4.05 29 11.88 1.80 14.22…
-
8HP heating mode
-
Note: 1, MCAC-VTSM-2013-08 -5 -5.6 21.29 6.70 20.10 6.25 18.90 5.80 18.22 5.57 17.62 5.69 16.42 4.94 -3 -3.7 21.29 6.31 20.10 5.89 18.90 5.47 18.22 5.26 17.62 5.06 16.42 4.67 0 -0.7 21.29 5.74 20.10 5.37 18.90 4.99 18.22 4.81 17.62 4.63 16.42 4.28 3 2.2 21.29 5.25 20.10 4.91 18.90 4.58 18.22 4.41…
-
10HP cooling mode
-
70% 40 MCAC-VTSM-2013-08 14 18.90 2.57 22.50 3.12 26.20 3.70 28.00 4.00 29.80 4.30 33.50 4.92 34.50 4.84 16 18.90 2.62 22.50 3.18 26.20 3.77 28.00 4.07 29.80 4.39 33.30 4.98 34.00 4.93 18 18.90 2.67 22.50 3.24 26.20 3.84 28.00 4.15 29.80 4.47 32.90 5.14 33.60 5.18 19 18.90 2.72 22.50 3.31 26.20 3.96…
-
Note: 1, R410A DC Inverter V4 Plus 50Hz 27 13.20 2.08 15.80 2.55 18.30 3.08 19.60 3.36 20.90 3.66 23.40 4.29 26.00 4.97 29 13.20 2.20 15.80 2.71 18.30 3.27 19.60 3.58 20.90 3.89 23.40 4.57 26.00 5.31 31 13.20 2.33 15.80 2.87 18.30 3.48 19.60 3.80 20.90 4.14 23.40 4.87 26.00 5.66 33 13.20 2.47 15.80…
-
10HP heating mode
-
Note: 1, MCAC-VTSM-2013-08 -9.8 -11 23.75 9.11 23.45 9.10 22.05 8.43 21.25 8.10 20.55 8.15 19.16 7.15 -9.5 -10 24.35 9.19 23.45 8.84 22.05 8.18 21.25 7.87 20.55 7.78 19.16 6.95 -8.5 -9.1 24.84 9.24 23.45 8.60 22.05 7.97 21.25 7.66 20.55 7.56 19.16 6.77 -7 -7.6 24.84 8.82 23.45 8.21 22.05 7.62 21.25…
-
12HP cooling mode
-
70% 46 MCAC-VTSM-2013-08 14 22.61 3.23 26.92 3.93 31.35 4.65 33.50 5.03 35.65 5.40 40.08 6.18 41.28 6.09 16 22.61 3.29 26.92 4.00 31.35 4.74 33.50 5.12 35.65 5.51 39.84 6.26 40.68 6.20 18 22.61 3.35 26.92 4.07 31.35 4.83 33.50 5.22 35.65 5.62 39.36 6.46 40.20 6.51 20 22.61 3.42 26.92 4.16 31.35 4.98…
-
Note: 1, R410A DC Inverter V4 Plus 50Hz 27 15.79 2.61 18.90 3.21 21.90 3.87 23.45 4.22 25.00 4.60 28.00 5.39 31.11 6.25 29 15.79 2.77 18.90 3.40 21.90 4.11 23.45 4.50 25.00 4.89 28.00 5.74 31.11 6.67 31 15.79 2.93 18.90 3.61 21.90 4.38 23.45 4.78 25.00 5.21 28.00 6.12 31.11 7.11 33 15.79 3.11 18.90…
-
12HP heating mode
-
Note: 1, MCAC-VTSM-2013-08 -9.8 -11 28.27 10.76 27.91 10.75 26.25 9.96 25.30 9.57 24.47 9.63 22.81 8.44 -9.5 -10 28.98 10.86 27.91 10.44 26.25 9.67 25.30 9.29 24.47 9.19 22.81 8.21 -8.5 -9.1 29.58 10.92 27.91 10.16 26.25 9.41 25.30 9.05 24.47 8.93 22.81 8.00 -7 -7.6 29.58 10.43 27.91 9.70 26.25 9.00…
-
14HP cooling mode
-
70% 52 MCAC-VTSM-2013-08 14 27.00 4.40 32.14 5.34 37.43 6.32 40.00 6.84 42.57 7.35 47.86 8.41 49.28 8.28 16 27.00 4.48 32.14 5.44 37.43 6.45 40.00 6.97 42.57 7.50 47.57 8.51 48.57 8.43 18 27.00 4.56 32.14 5.54 37.43 6.57 40.00 7.10 42.57 7.65 47.00 8.79 48.00 8.86 20 27.00 4.65 32.14 5.66 37.43 6.77…
-
Note: 1, R410A DC Inverter V4 Plus 50Hz 27 18.86 3.55 22.57 4.36 26.14 5.26 28.00 5.74 29.86 6.25 33.43 7.33 37.14 8.49 29 18.86 3.77 22.57 4.63 26.14 5.59 28.00 6.12 29.86 6.65 33.43 7.81 37.14 9.08 31 18.86 3.98 22.57 4.91 26.14 5.96 28.00 6.50 29.86 7.08 33.43 8.33 37.14 9.67 33 18.86 4.23 22.57…
-
14HP heating mode
-
Note: 1, MCAC-VTSM-2013-08 -9.8 -11 33.92 13.40 33.49 13.38 31.50 12.40 30.36 11.92 29.36 11.98 27.37 10.51 -9.5 -10 34.78 13.51 33.49 12.99 31.50 12.03 30.36 11.57 29.36 11.44 27.37 10.22 -8.5 -9.1 35.49 13.59 33.49 12.64 31.50 11.71 30.36 11.26 29.36 11.12 27.37 9.95 -7 -7.6 35.49 12.98 33.49…
-
16HP cooling mode
-
70% 58 MCAC-VTSM-2013-08 14 30.38 5.01 36.16 6.08 42.11 7.20 45.00 7.79 47.89 8.37 53.84 9.58 55.44 16 30.38 5.10 36.16 6.20 42.11 7.35 45.00 7.94 47.89 8.54 53.52 9.69 54.64 9.43 9.60 18 30.38 5.20 36.16 6.31 42.11 7.48 45.00 8.09 47.89 8.71 52.88 10.01 54.00 10.09 20 30.38 5.29 36.16 6.44 42.11…
-
Note: 1, R410A DC Inverter V4 Plus 50Hz 27 21.22 4.04 25.39 4.97 29.41 5.99 31.50 6.54 33.59 7.12 37.61 8.35 41.78 9.67 29 21.22 4.29 25.39 5.27 29.41 6.37 31.50 6.97 33.59 7.58 37.61 8.90 41.78 10.34 31 21.22 4.53 25.39 5.59 29.41 6.78 31.50 7.41 33.59 8.07 37.61 9.49 41.78 11.02 33 21.22 4.82…
-
16HP heating mode
-
Note: 1, MCAC-VTSM-2013-08 -11.8 -13 35.95 15.06 35.95 15.36 35.00 15.00 33.73 14.42 32.62 13.70 30.41 12.69 -9.8 -11 37.69 15.31 37.22 15.30 35.00 14.17 33.73 13.62 32.62 13.70 30.41 12.01 -9.5 -10 38.64 15.45 37.22 14.85 35.00 13.75 33.73 13.22 32.62 13.07 30.41 11.68 -8.5 -9.1 39.43 15.53 37.22…
-
8. Sound Levels
-
9. Outdoor Fan Performance
Static pressure (Pa) 9.1 8,10HP Curve diagram of static pressure, air flow volume: Static pressure(Pa) 0 10500 10700 10900 11100 11300 11500 11700 1190012000 Air volume(m 3/h) 9.2 12,14,16HP Curve diagram of static pressure, air flow volume: 14600 14700 14800 14900 15000 15100 15200 15300 15400…
-
10. Accessories
10.1 Standard accessories No Name Quantity Purpose / 1 Installation manual of outdoor unit 1 2 Operation manual of outdoor unit 1 It’s necessary general accessories 3 Operation manual of indoor unit 1 It’s necessary general accessories 4 Screw bag 1 5 Straight screwdriver 1 Dialing 6 Gauge joint 1…
-
11. Functional Parts And Safety Devices
Item Compressor Symbol Name Inverter Inverter compressor E405DHD-36D2Y E405DHD-36D2Y E405DHD-36D2Y FIX1 Fixed speed compressor E605DH-59D2Y E655DH-59D2Y E655DH-59D2Y Compressor Safety OLP CCH MDV-252(8)W/DRN1(B) MDV-280(10)W/DRN1(B) MDV-335(12)W/DRN1(B) Open temperature Starting current 160±5℃…
-
1. Installation Introduction
1.1 Select the Refrigerant Piping for V4+ modular type 1.1.1 Length and drop height permitted of the refrigerant piping Table 4-1 Item Permitted length ≤30HP Total pipe length(actual length) Pipe length Farthest pipe length(m) Level difference ≤350m ≤500m >30HP Actual length ≤150m Equivalent length…
-
the both sides of the U-shape branch joint. 5. When the outdoor unit is on the top position and the difference ≥300mm of level is over 20m, it is recommended that set an oil return bend every 10m in the gas pipe of the main pipe, the specification of the ≥300mm oil return bend refers to the figure…
-
1.1.2 Select the refrigerant piping
-
1.1.2.3 Selection of the main pipe (L1)
-
1.1.3 Pipe selection example
-
1.1.3.3 Select main pipe(L1) and outdoor unit pipe(g1-g3,G1),outdoor branch, according to Table 4-5
-
Outdoor
-
Liquid side
Oil balance pipe / (2 pcs) Heat insulation material (2 sets) Installation (4 sets) (6 sets) 75
-
1.2 Installation Procedure
1.2.1 Importance of the Installation Operation Effects of installation issues on equipment: Leakage of refrigerant pipe Insufficient refrigerant Overheated running Compressor fault Filth blockage of refrigerant pipe Product of the chemical reaction between ice or water of throttling parts and the…
-
Air tightness test Check whether the air pressure remains at 4.0Mpa (R410a) after correction is made within 24 hours Vacuum drying Use vacuum pump that has a vacuum degree of less than -775mmHg Recharging refrigerant Record the amount of refrigerant to be recharged on the outdoor unit and document…
-
1.2.6.7 The power wire and signal wire can’t be enlaced together
1.2.7 Lay the indoor pipeline Note: Collocate the air-outlet reasonably to prevent airflow short-circuit. Check the static pressure whether in the allowable range. The air filters should be easy to unpick and wash. Do pressure test on pipeline. 1.2.8 Heat-insulation procedure Refrigerant pipe work…
-
below
No. Name Pipe cutter Steel saw Pipe bender 4 Pipe expander 5 Flaring tool 6 Brazing welder Scraper File/Rasp Injection tube Double-ended pressure gauge Pressure gauge Vacuum gauge 13 Vacuum pump 14 Horizontal rule 10 Specification/Model Spring, mechanic Depend on the pipe diameter specification…
-
1.3.5 Coordination with other sectors
Ensure smooth coordination and meticulous organization between these sectors: air conditioning, civil work, electricity, water supply and drainage, fire protection, decoration, intelligence, etc. Try best to lay pipes of the air conditioning system along the bottom of the beam. If pipes meet…
-
exceeding allowable safety limits in the event of refrigerant leakage
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency. (4)Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electrical shock fire. (5)Install at a…
-
(3) Connect the outdoor unit wires, and then connect the indoor unit wires
You are not allowed to connect the air conditioner with the power source until wiring and piping the air conditioner is done. (4) While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent…
-
2. Units Installation
2.1 Installation of Indoor Unit 2.1.1 Installation procedure Determine the installation position → Scribing and locating → Installing suspension road → Installing the indoor unit 2.1.2 Cautions for installation and check 1) Drawing check: Confirm the specification, model and installation direction…
-
When conveying and hoisting the outdoor unit, keep it upright, ensure that the slope does not exceed 30°, and keep safety in mind. 2.2.3 Selecting installation position 1. Ensure that the outdoor unit is installed in a dry, well-ventilated place. 2. Ensure that the noise and exhaust ventilation of…
-
angle
4) In order to drain off the water around the equipment, a discharge ditch must be setup around the basement. 5) Please check the affordability of the roofing to ensure the load capacity. 2.2.5 Installation highlights for outdoor unit 1. Install vibration isolator or isolating pad between the set…
-
4) When the outdoor unit is lower than the surrounding obstacle,
Refer to the layout used when the outdoor unit is higher than the surrounding obstacle. However, to avoid cross connection of the outdoor hot air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to facilitate heat dissipation. See the…
-
2.2.7. Mount the air deflector
When installing, takes off the mesh firstly, and then conduct in according of the following two schedules. 2.2.7.1 Installation of 8HP and 10HP. Schedule 1: Schedule 2: Installation 87
-
Schedule 1: Schedule 2: 88 Installation
-
Note: Before install the air deflector, please ensuring the mesh enclosure has been took off; otherwise the air supply efficiency would be block down. Once mounting the shutter to the unit, air volume, cooling (heating) capacity and efficiency would be block down, this affection enhance along with…
-
16HP
MCAC-VTSM-2013-08 14HP 10HP Outdoor unit (40HP) The1st branching tube Indoor unit A Indoor unit B Indoor unit C Remark: All the outdoor units should be installed on the location of same level, or it may cause imbalance of refrigerant distributing and lead the fault of the compressors. Although the…
-
3. Refrigerant Pipe Engineering
3.1. Refrigerant Pipe Processing 3.1.1 Basic requirements 3.1.1.1 Operation procedure Determine the route and size of the pipeline according to the construction drawingMake and installing bracket, hanger and supportMake and arrange pipe accessories Recharge nitrogen gas for protection Brazing…
-
Fix the pipe along the wall according to the pipeline route. Round log should be used at the pipe clip to replace thermal insulation material, ―U‖-shape pipe should be fixed outside the round log, and the round log should be provided with anticorrosion treatment. Pipe Diameter (mm) Less than Ф20…
-
a. Ensure that the distance between the bending point of copper pipe and the horizontal straight pipe section of the adjacent branch pipe is larger than or equal to 1m. b. Ensure that the distance between the horizontal straight pipe sections of the two adjacent branch pipes is larger than or equal…
-
2) When the copper pipe goes outside the wall, ensure that no rain water can enter the pipe, particularly when the pipe is placed upright. 3) Before completing the pipe connection, seal the openings of the pipe with covers. 4) Place the openings of the pipe vertically or horizontally. 5) Before…
-
deform
3. Risk if a saw or cutting machine is used to cut pipe: Copper chip will enter the pipe (in this case, it will be very hard to clean up), or which may even enter the compressor or blocking the throttling unit. 3.1.3.2 Rectify opening of copper pipe 1. Purpose Clear out the burr at the opening of…
-
Pipe
Diameter MCAC-VTSM-2013-08 Torque Legend (kgf-cm) (N-cm) 1/4" (6. 35) 144~176 1420~1720 3/8" (9. 52) 333~407 3270~3990 1/2" (12. 7) 504~616 4950~6030 5/8" (15. 88) 630~770 6180~7540 3/4" (19. 05) 990~1210 9270~11860 Torque spanner Spanner Flaring opening nut Tubing tie-in Caution: When you are…
-
4) Ensure that the pipe does not sink during the bending process; ensure that the cross section of the bending pipe is larger than 2/3 of the original area, otherwise it cannot be used. twinkle will easily appear on this side the pipe sink easily on the side 3.1.4 Brazing welding operation 3.1.4.1.…
-
4. Cautions for Welding Pipe Fittings
1) Adopt transition pipe. 2) Charge nitrogen from the side of the short pipe, because short distance may result in perfectible nitrogen replacement effect. brazing welding part nitrogen copper pipe direct connection assistant pipe assembly brazing welding part copper pipe elbows nitrogen assistant…
-
6) If the pipeline between the position for charging nitrogen and the welding spot is rather long, ensure that the nitrogen is charged for sufficient time so as to discharge all the air from the welding spot. 7) After completing the welding, charge the nitrogen continuously until the pipe cools down…
-
outdoor unit
3. Use blind plug to block all connectors of liquid side copper line (including unit B) soundly, excluding indoor unit A. 4. Turn on nitrogen gas cylinder valve, and then pressurize to 5kgf/cm2 gradually through adjusting valve. 5. Check whether nitrogen has passed through the liquid pipe at the…
-
⑥ ⑤ ④ ③ ① Caution: When flushing one pipe opening, block all pipe openings which are connected to this opening. 6) After finishing flushing, seal soundly all openings linked with atmosphere to prevent the entering of dust, trash and moisture. 3.1.6 Installation highlight of pipe system 1) Pipe…
-
and nitrogen shall leak into outdoor unit system through the ball valve
① ② ③ ④ ⑤ Liquid pipe Oil balancer Gas pipe Gauge point Low pressure ball valve 3.2.2 Operation of air tightness test 3.2.2.1 Operation procedure 1. When conducting air tightness test, make sure that gas pipe and liquid pipe are kept in full-shut status; otherwise, nitrogen might enter the…
-
Using halogen leak detector when finding out pressure drop but not finding the leak source
a. Keep nitrogen at 3.0kgf/cm2. b. Supplement refrigerant to 5.0kgf/cm2. c. Use halogen leak detector, methane leak detector and electric leak detector for detection. d. If the leak source still could not be found, continuously pressurize to 40.0kgf/cm2 (R410A)and then detect again. Outdoor unit Gas…
-
After the vacuum process of R410Arefrigerant circulation is over, vacuum pump stops running and the
lubricant in vacuum pump shall flow back to air conditioning system, for the inner of pump soft pipe is in vacuum status. In addition, same situation shall happen if vacuum pump suddenly stops during operation. At this moment, different oils will mix, which induce the refrigerant circulating system…
-
a. The first vacuum drying2 hours
b. The second vacuum damage, filling nitrogen to 0.5Kgf/cm2. Because nitrogen is dry gas, vacuum damage could achieve the effect of vacuum drying, but this method could not achieve drying thoroughly when there is too much moisture. Therefore, special attention shall be drawn to prevent the entering…
-
Diameter of Liquid Pipe
-
4. Drainage Pipe Engineering
4.1 Installation Highlights of Drainage Pipe 4.1.1 Installation principle of drainage pipe: 1) Slope; 2) reasonable pipe diameter; 3) nearby discharge 4.1.2 Installation highlights of drainage pipe: 1. Before installing condensate water pipeline, determine its route and elevation to avoid…
-
smoothness of drainage and leakage of pipeline system
6. Use specific glue to adhesive the seam of thermal insulation materials, and then bind with rubber or plastics adhesive tape. The width of the adhesive tape shall not be less than 50mm to ensure fastness and prevent condensation. 7. The drainage pipe of air conditioner shall be installed…
-
4.2 Water Storing Elbow of Drainage Pipe
4.2.1 To indoor unit with large negative pressure at the outlet of water-containing plate, the drainage pipe must be equipped with water storing elbow. Function of water storing elbow: When indoor unit is in motion, prevent generating negative pressure to cause drainage difficulty or blow water out…
-
Attention: through converge point need use PVC40 or larger pipe
4.3.4 Operation process of concentrated drainage Install indoor unit → connect drainage pipe → water passing test and overflowing water test → thermal insulation of drainage pipe Caution: 1) Increase drainage point as much as possible and reduce quantity of connected indoor units, to ensure…
-
hard pipe at drainage outlet to confirm whether it can discharge water
2. Pump drainage mode 1) Remove plug of water level switch, remove water-finding cover and slowly infuse water-containing plate with about 2000ml water through water-finding port to prevent touching the motor of drainage pump. 2) Power on and let the air conditioner operate for cooling. Check…
-
5. Duct Engineering
5.1 Fabrication of Duct 1. The material, specification, performance and thickness of metal duct should be in accordance with the relevant regulations of present National Products Standard. The thickness of steel sheet or galvanized steel sheet should not be less than the regulation in table below…
-
3) Diameter of bolt and rivet to duct flange for middle/low pressure system should be no more than 150mm. As for duct of high pressure system, it should be no more than 100mm. 4) Four angles of rectangle duct flange should be designed with screw hole. 5) When improving the strength of duct flange…
-
5.4 Installation of Assembly
1. The regulating device of duct should be installed in place where is easy to operate, flexible and reliable. 2. The airport should be installed firmly and air pipe should be connected tightly. Frame should be tightly contact with decorate of building. The appearance should be smooth and flat, and…
-
6. Heat Insulation Engineering
The insulation of refrigerating equipment and pipe is carried out through general insulation method, which binding the equipment and pipe with solid multi-hole insulation material and exploiting proper wet-proof and protection measures, called insulation structure. The form of insulation structure…
-
a. Gas pipe and liquid pipe are carried out heat insulation separately
Note: After gas pipe and liquid pipe are carried out heat insulation separately, bind with tape. If it is bound over tightly, the spliced insulation joint shall be damaged. b. The surrounding of pipe connecting section shall be carried out insulation entirely. Highlights: 1. No gap in joint of…
-
5. Finally, bind the seam with rubber/plastic tape
6. Prohibit conducting insulation by using binder fabric in concealed section, so as to avoid influencing insulation effect. 6.2 Insulation of Condensate Water Pipe 6.2.1 Insulation of condensate water pipe 1. Select rubber/plastic tube with burning retardant of rating B1. 2. Thickness of insulation…
-
R410A
R DC Inve erter V4 Plus 50Hz 5 MCAC-V VTSM-2013-08 8 7. 7 Electrica al Enginee ering 7.1 Wiring te erminals ins struction A B C N Indoo or units Indoor units Outdoor units u centrralized commun nication communication contrros Outdoor units O Ne etwork ce entralized ac ccounting m monitoring Thre…
-
OFM: Outdoor Fan Motor
FLA: Full Load Amps. (A) KW: Rated Motor Output (kW) The current value of combination unit is the total value of each basic mode (refer to units combination table in part 1) For example: 46HP=14HP+16HP×2 Power current: MCA=33.9+37.6×2=110 TOCA=31.8+32.8×2=98 MFA=35+35×2=105 Compressor…
-
Outdoor unit
(master unit) Outdoor unit (slave unit) Outdoor unit (slave unit) Outdoor unit (slave unit) All shield terminals of shield wires should connect to COMM terminal (P Q E) (H1 H2 E) (H1 H2 E) (H1 H2 E) (H1 H2 E) Signal wire between outdoor units To closed end of shield wire (P Q E) Signal wire between…
-
7.3.2 Example connection of wiring
7.3.3 Signal wire of centralized control Signal wire of centralized control When centralized control is needed, one CCM03 (central controller of indoor unit) can only control the indoor units which are in the same refrigerant system via the port X Y E of outdoor unit. Outdoor unit will automatically…
-
8. Commissioning and Trial Running
8.1 Work before Commissioning 8.1.1 Inspection and confirmation before Commissioning 1. Check and confirm that refrigeration pipe line and communication wire with indoor and outdoor unit have been connected to the same refrigeration system. Otherwise, operation troubles shall happen. 2. Power…
-
Salve unit 2 2 12HP 3 Salve unit 3 3 14HP ≥4 Invalid address, system error 4 16HP ≥5 Invalid dial switch --8.2 Commissioning of Trial Run 8.2.1 Commissioning for trail run of single unit. 1. Each independent refrigeration system (i.e. each outdoor unit) should be conducted trail operation. 2.…
-
Test Data for Test Run of __________System
Model of outdoor unit Production series no. Operation data of outdoor unit (Cooling) Unit Run Voltage No.1 No.2 No.3 V Total current of run A Operation current of compressor High-pressure pressure Kg/cm Low-pressure pressure Kg/cm Inlet air temperature A 2 2 C Outlet air temperatureC Operation…
-
System parameter
SW1: (CHECK)――Used to query outdoor unit data. Check point sequence and corresponding actuality is as follows: No. Display content Note No. Display content Remark 1 ADDR of outdoor unit 0,1,2,3,4 13 Discharge temp. of inverter compressor Actual value 2 Cap. of outdoor unit 8,10,12,14,16 14 3 Qty. of…
-
1. Outdoor electric control box assembly instructions
NO. Content 1 Cement resistor 2 Aluminum electrolysis capacitor 3 Main control board 4 Intermediate adapter plate 5 Terminal block, 4P 6 Transformer 7 Contactor 8 Thermistor 9 Contactor 10 Fan module heat sink assembly 11 Bridge rectifier 12 Inverter module, Electronic control module component-IPM…
-
2. Main board ports instructions
Main board ports instruction No. 1 CN1 2 CN2 3 CN3 4 CN4 5 CN11 7 CN8 8 CN21 9 CN22 10 CN25 Content Reserved Discharge temperature test port T7C3 for No.2 fixed compressor Discharge temperature test port T7C2 for No.1 fixed compressor Discharge temperature test port T7C1 for inverter compressor…
-
24 CN18 System pressure test port
Outdoor ambient temperature sensor T4 and condenser temperature 25 CN9 sensor T3 26 CN19 Current test port for inverter No.1,and No.2 fixed compressor 27 CN16 Communication port among outdoor units 28 CN14 Control port for No.1 DC fan 29 CN13 Control port for No.2 DC fan 30 CN12 31 CN15 Reserved…
-
Fan speed 0-Fan stop, 1~9-Speed increase sequentially, 9-The maximum fan speed. 10 Average temp. of T2B/T2 Actual value 11 T3 pipe temp. Actual value 12 T4 ambient temp. Actual value 13 Discharge temperature of inverter compressor Actual value 14 Discharge temperature of No.1 fixed compressor Actual…
-
3.2 System setting dial switches instructions
Dial switch Content Note ENC3 System address setting Setting range: 0-7 S3 Reserved ENC2 Outdoor unit capacity setting 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP ENC1 Outdoor units addresses setting 0: master unit; 1-3: slave unit S1 Starting up time setting : starting time is 3 minutes; starting…
-
3.4 LED on Main board instructions
LED1 LED2 LED3 LED4 LED5 LED1: Power supply indicator lamp of network centralized control chip. The lamp will be on if the power supply is normal. LED2: Running indicator lamp of network centralized control chip. The lamp will be on if the system running is normal. LED3: Malfunction indicator lamp…
-
4. Error/Protection code table
Error code Content Note E0 Communication error between outdoor units Only display on faulty slave unit, all the ODU in standby E1 Phase sequence error Display on faulty unit, all the ODU in standby E2 Indoor units and master unit communication error Only display on master unit, all the ODU in…
-
5. Troubleshooting
5.1 E0: Communication error between outdoor units (Only display on faulty slave unit, all the ODU in standby) E0: Communication error between outdoor units ODU addresses (ENC1) are set incorrectly (the master unit address should be set to 0, slave units addresses should be set from 1 to 3, and the…
-
5.2 E1: Phase sequence error (Display on faulty unit, all the ODU in standby)
E1: Phase sequence error The 3-phase sequence of power supply is wrong. (The A, B, C terminal of three-phase power supply should meet compressor phase sequence requirement. If the phase sequence is adverse, the compressor will operate inversely. Yes Exchange any two of the 3-sequence No Some power…
-
5.3 E2: Indoor units and master unit communication error (Only display on master unit, all the ODU
in standby) E2: Indoor units and master unit communication error Signal wires P, Q, E are short circuit or disconnected (Measure the resistance among P, Q and E, the normal resistance is 120Ω) Yes Reconnect the signal wires Yes Connect the signal wires in line shape Yes Ensure the signal wires and…
-
1. Pressing the manual button continued for 5 seconds, it will display the indoor units communication address. LED light Operation Timer DEF./FAN Alarm Code Communication address Four LED display Buzzer not warning 00---15 Normally on Buzzer not warning 16---31 Flash Buzzer warning 32---47 Normally…
-
For example
Pressing the manual button continued for 10 seconds: If all the LED lights turn off, that means the capacity code is 0 and the capacity of indoor units is 22×100W(0.8HP); If the “Timer” and “Alarm” lights are normally on, that means the capacity code is 5=(4+1) and the capacity of indoor unit is…
-
5.4 E4: Pipe temperature T3/Ambient temperature sensor (T4) error (Display on faulty unit, all the
ODU in standby) E4: Pipe temperature T3/Ambient temperature sensor (T4) error T3/T4 port on board is loose main Yes Fasten the T3/T4 port No T3/T4 sensor is short circuit or disabled (Using a multimeter to measure resistance, if the resistance is too small, the sensor is short circuit, if the…
-
5.5 E8: Outdoor unit address is wrong (Only display on faulty slave unit, all the ODU in standby)
E8: Outdoor unit address is wrong Yes The ODU's address is more than 3 or be set repeatedly The addresses should be set less than 3 and differently No No Main board is disabled Replace main board Note: The ODU often loses information and can’t display the E8 error when the address is repeated 5.6…
-
5.7 H0/H1
H0: IR341 and 78F0034 communication error (Display on faulty unit, all the ODU in standby) H1: 0537 and 78F0034 communication error (Display on faulty unit, all the ODU in standby) IR341 chip: IR 341chip is used for inverter compressor drive. 0537 chip: 0537chip is used for control the communication…
-
5.8 H2/H3
H2: Quantity of outdoor units decrease error (Only display on master unit, all the ODU in standby) H3: Quantity of outdoor units increase error (Only display on master unit, all the ODU in standby) H2/H3 Signal wire between outdoor units is loose Yes Fasten the signal wire No Some outdoor units…
-
5.9 H7: Quantity of indoor units decrease error (Only display on master unit, all the ODU in standby) “H7” error will display when the quantity of indoor units decrease above 3 minutes. H7: Quantity of indoor units decrease error Communication terminals P Q E are loose Yes Fasten the communication…
-
5.10 H8: High pressure sensor error
When the discharge pressure is lower than 0.3MPa, the system will display H8 error, the ODU in standby. When the discharge pressure is back to normal, H8 disappears and normal operation resumes. H8: High pressure sensor error Yes High pressure sensor connection port on main board is loose Fasten the…
-
5.11 P0/P4/H6: High temperature protection (Display on faulty unit, all the ODU in standby)
P0: Top temperature protection of inverter compressor When the top temperature is over 120℃, the operation will stop, when the temperature goes back to normal range, P0 disappear and normal operation resumes. P4: Discharge temperature protection of all compressors When the discharge temperature of…
-
5.12 P1: High pressure protection (Display on faulty unit, all the ODU in standby)
When the pressure is over 4.4MPa, the system will display P1 protection, all the ODU in standby. When the pressure is lower than 3.2MPa, P1 disappearing and normal operation resumes. P1: High pressure protection The high pressure sensor is disabled Replace the high pressure sensor Yes No The heat…
-
5.13 P2/H5: Low pressure protection (Display on faulty unit, all the ODU in standby)
When the pressure is lower than 0.05MPa, the system will display P2 protection, all the ODU in standby. When the pressure is higher than 0.15MPa, P2 disappear and resumes normal operation. H5 error will display when system appear 3 times P2 protection in 30 minutes, it cannot resume automatically…
-
5.14 P3/P7/P8: Compressor current protection (Display on faulty unit, all the ODU in standby)
P3: Current protection of inverter compressor When the current of inverter compressor is over12A, the system will display P3 protection, all the ODU in standby. When the current goes back to normal range, P3 disappear and normal operation resumes. P7/P8: Current protection of No.1/No.2 fixed…
-
5.15 P5: Condenser temperature T3 protection (Display on faulty unit, all the ODU in standby)
When condenser temperature is over 65℃, the system will display P5 protection, all the ODU in standby. When the temperature goes back to normal range, P5 disappear and normal operation resumes. P5: Condenser temperature protection Yes T3 port on Main board is loose Fasten the T3 port No Yes ① T3…
-
5.16 P6/H4: Inverter module protection (Display on faulty unit, all the ODU in standby)
If the system display three times P6 protection in 30 minutes, the system will stop and display H4 error code. When the system displays H4 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. H4 will display…
-
DC generatrix check
1) Check the voltage of DC generatrix, the normal value should be 510 to 580V. If the value is less than 510V, go to next step. 2) Check the wiring connection of rectifier circuit, find out any loose in the circuit, and check the filter board, single-phase rectifier stack, and three-phase rectifier…
-
Step 1: Replace the modular with correctly wire connection and start the system, if system is still malfunction, then go to step2 to check the compressor. Step 2: Take out the compressor from the malfunction system, short-circuit the suction and the discharge, vacuum dry and charge 0.3kg~0.4kg…
-
5.16.2 L1/L4 troubleshooting
Step 1: Check the DC voltage between P and N terminal, the normal value should be 510V~580V, if the voltage is lower than 510V, go to step 2. Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If wires are OK, replace the PCB. 3-Phase…
-
5.17 P9/H9: Fan module protection (Display on faulty unit, all the ODU in standby)
If the system display three times P9 protection in 30 minutes, the system will stop and display H9 error code. When the system displays H9 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. P9/H9: Fan…
-
P9 protection analysis
Conditions Fault indicator Power supply Digital lamp of fan indicator lamp tube module of fan module display Malfunction analysis Check the power supply circuit for fan module. Power on Off Off Quantity Check whether there has power supply for lightning of IDU or protection plate, whether the…
-
Attached table 1
Resistance value of ambient temperature and pipe temperature sensor Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) -20 115.266 20 12.6431 60 2.35774 100 0.62973 -19 108.146 21 12.0561 61 2.27249…
-
Attached table 2
Resistance value of compressor discharge temperature sensor Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) Temperature (℃) Resistance value (kΩ) -20 542.7 20 68.66 60 13.59 100 3.702 -19 511.9 21 65.62 61 13.11 101 3.595 -18 483 22…
-
Attached table 3: Commissioning and operating parameters of refrigerant system
Conditions 1: Make sure outdoor unit can detect all the indoor units, the quantity of indoor units display steadily and be equal to actual quantity of installed indoor units. Conditions 2: Make sure all the valves in outdoor unit are open, indoor units EXV have connected to indoor PCB. Conditions 3…
-
GD Midea Heating & Ventilating Equipment Co., Ltd
Is certified under the ISO 9001 International standard for quality assurance. NO.01 100 019209 GD Midea Heating & Ventilating Equipment Co., Ltd. Is certified under the ISO 14001 International standard for environmental management. Certificate No.15912E10020R0L Commercial Air Conditioner Business…