Инструкция на Наружные блоки мини VRF-системы V4+ 8-10-12-14-16-18 (сервис мануалы)
Наружные блоки мини VRF-системы V4+ (220~240V~1ph 50Hz). Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
1. Product Lineup
-
2. Nomenclature
MDV- V 105 W / D N1 Refrigerant type N1:R410A Inverter Type D: DC Inverter W: Outdoor unit Cooling Capacity (×100W)* Inverter System Midea *Note: the actual cooling capacity please refer to the nameplate. 4 General Information
-
3. Features
3.1 Wide application The Full DC Inverter mini VRF system is a highly efficient solution for small commercial buildings requiring heating and cooling of up to 7 zones with one outdoor unit. Such as villa, restaurant, school etc. Midea offers a variety indoor unit, about 100 models of 10 types.…
-
3.2 High efficient DC inverter compressor
Full DC inverter mini VRF adopts highly intelligent inverter-driven compressor. This advanced technology enables the output of the outdoor unit to be modulated by the real heat load demands.. This advanced system ensures precise temperature regulation and highly efficient energy usage, making a…
-
3.6 Wide operation temperature range
No matter in extremely cold winter when outdoor temperature gets as low as -15°C or in hot summer when temperature is up to 48°C, the mini VRF system will keep stable performance. COOLING MODE HEATING MODE 24 27°C -15°C -20 3.7 Flexible piping design 48°C -15°C -10 °C 50 Outdoor temp. °C(D.B.)…
-
Outdoor unit can
distribute address for indoor unit automatically MCAC-VTSM-2013-12 Shield signal wire Wired and wireless controller can enquire and modify address of each IDU. 3.11 Easy piping connection Offering four directions to connect pipes and wirings to meet various installation requests. Front side Right…
-
4. Indoor Units Lineup
Cassette type One-way cassette Capacity (×100W) Compact four-way cassette Two-way cassette 15 Four-way cassette ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Duct type Medium static pressure duct High static pressure duct Capacity (×100W) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Cased…
-
Capacity
(×100W) Wall mounted (S panel) MCAC-VTSM-2013-12 Wall mounted (C panel) Wall mounted Wall mounted (D panel) Wall mounted (R panel) ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Note: If ODU connect only one IDU, the capacity of IDU should be not more than ODU. If ODU connect more than one IDU, the…
-
1. Specifications
Sale Model MDV-V80W/DN1 MDV-V105W/DN1 MDV-V120W/DN1 Code 260V00000190 260V00000191 220095101631 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz Power supply Cooling Heating V-Ph-Hz Capacity kW 8 10.5 12.3 Input kW 2.05 2.68 3.25 EER kW/ kW 3.90 3.92 3.78 Capacity kW 9 11.5 13.2 Input kW 2.24 2.90 3.47 COP…
-
Sale Model
-
MDV-V160W/DN1(B) MDV-V180W/DN1 Insulation class E E E Safe class IP23 IP23 IP23 Sale Model Outdoor Fan motor Input W 2*100 2*100 2*100 Output W 2*85 2*85 2*85 Rated current A 2*0.9 2*0.9 2*0.9 r/min Material ASG20 ASG20 ASG20 Type Axial fan Axial fan Axial fan Speed Outdoor fan Outdoor coil Diameter…
-
H
-
3. Service Space
Unit: mm Single unit installation >300 (Wall or obstacle) Air inlet >300 Maintain channel Air inlet >2000 >600 Air outlet Parallel connect the two units or above >300 >600 >2000 Parallel connect the front with rear sides >2000 16 >500 >3000 >3000 >300 Specifications & Performance
-
4. Piping Diagrams
Electronic expansion valve High pressure switch Condensor High pressure liquid accumulator can Evaporator Electronic expansion valve Oil seperator Oil return capilary Compressor Low pressure Low pressure switch liquid accumulator can Specifications & Performance 17
-
5. Wiring Diagrams
8/105 model 18 Specifications & Performance
-
120~160 model
Specifications & Performance R410a Full DC Inverter Mini VRF 19
-
180 model
20 MCAC-VTSM-2013-12 Specifications & Performance
-
6. Field Wiring
Specifications & Performance 21
-
7. Capacity Tables
-
R410a Full DC Inverter Mini VRF 29 6.49 1.24 7.71 1.60 8.57 1.85 8.69 1.86 8.80 1.87 9.03 1.89 9.29 1.90 31 6.49 1.33 7.71 1.71 8.43 1.92 8.57 1.93 8.69 1.94 8.91 1.96 9.14 1.98 33 6.49 1.41 7.71 1.82 8.31 1.99 8.43 2.01 8.54 2.01 8.77 2.04 9.00 2.06 35 6.49 1.50 7.71 1.95 8.17 2.07 8.29 2.08 8.43…
-
24 MCAC-VTSM-2013-12 27 5.40 0.91 6.43 1.15 7.49 1.43 8.00 1.58 8.51 1.74 8.80 1.78 9.00 1.80 29 5.40 0.97 6.43 1.23 7.49 1.53 8.00 1.69 8.49 1.84 8.69 1.86 8.89 1.87 31 5.40 1.03 6.43 1.32 7.49 1.63 8.00 1.80 8.37 1.91 8.54 1.93 8.74 1.95 33 5.40 1.10 6.43 1.40 7.49 1.74 8.00 1.92 8.23 1.99 8.43…
-
4.31 0.65 5.14 0.80 5.97 0.98 6.40 1.07 6.83 1.17 7.66 1.38 8.49 1.61 27 4.31 0.69 5.14 0.86 5.97 1.04 6.40 1.15 6.83 1.25 7.66 1.48 8.49 1.72 29 4.31 0.73 5.14 0.91 5.97 1.11 6.40 1.22 6.83 1.34 7.66 1.58 8.49 1.84 31 4.31 0.78 5.14 0.97 5.97 1.19 6.40 1.30 6.83 1.43 7.66 1.69 8.34 1.91 33 4.31…
-
3.23 0.47 3.86 0.56 4.49 0.65 4.80 0.70 5.11 0.75 5.74 0.87 6.37 1.00 25 3.23 0.48 3.86 0.57 4.49 0.68 4.80 0.73 5.11 0.80 5.74 0.93 6.37 1.06 27 3.23 0.50 3.86 0.60 4.49 0.72 4.80 0.78 5.11 0.85 5.74 0.99 6.37 1.14 29 3.23 0.53 3.86 0.64 4.49 0.77 4.80 0.83 5.11 0.90 5.74 1.05 6.37 1.21 31 3.23…
-
Combination
-
90% 80% 28 MCAC-VTSM-2013-12 -3 -3.7 8.26 2.42 8.26 2.49 8.23 2.55 8.23 2.59 8.20 2.62 8.20 2.69 0 -0.7 8.91 2.51 8.91 2.57 8.89 2.64 8.89 2.66 8.89 2.70 8.63 2.64 3 2.2 9.63 2.60 9.60 2.65 9.60 2.71 9.57 2.73 9.26 2.62 8.63 2.41 5 4.1 10.11 2.65 10.11 2.70 9.91 2.68 9.57 2.57 9.26 2.47 8.63 2.26 7…
-
-10 7.00 2.58 6.97 2.64 6.97 2.69 6.97 2.72 6.74 2.62 6.29 2.40 -8.5 -9.1 7.14 2.61 6.64 2.66 7.11 2.71 6.97 2.65 6.74 2.55 6.29 2.33 -7 -7.6 7.40 2.64 7.40 2.70 7.20 2.64 6.97 2.53 6.74 2.43 6.29 2.23 -5 -5.6 7.80 2.69 7.66 2.68 7.20 2.48 6.97 2.38 6.74 2.29 6.29 2.10 -3 -3.7 8.11 2.71 7.66 2.52…
-
-17 5.07 2.24 4.78 2.09 4.50 1.95 4.33 1.87 4.19 1.80 3.90 1.66 -13.7 -15 5.07 2.14 4.78 1.99 4.50 1.85 4.33 1.79 4.19 1.72 3.90 1.59 -11.8 -13 5.07 2.03 4.78 1.89 4.50 1.76 4.33 1.70 4.19 1.63 3.90 1.51 -9.8 -11 5.07 1.92 4.78 1.79 4.50 1.67 4.33 1.61 4.19 1.55 3.90 1.44 -9.5 -10 5.07 1.87 4.78…
-
32 MCAC-VTSM-2013-12 33 8.51 1.85 10.12 2.38 10.91 2.61 11.06 2.62 11.21 2.63 11.51 2.66 11.81 2.69 35 8.51 1.96 10.12 2.54 10.72 2.70 10.87 2.72 11.06 2.73 11.36 2.76 11.66 2.79 37 8.51 2.09 10.12 2.71 10.57 2.80 10.72 2.81 10.87 2.83 11.17 2.86 11.48 2.89 39 8.51 2.22 10.09 2.86 10.39 2.89 10.54…
-
R410a Full DC Inverter Mini VRF 31 7.09 1.35 8.44 1.72 9.82 2.13 10.50 2.35 10.99 2.50 11.21 2.52 11.47 2.55 33 7.09 1.43 8.44 1.83 9.82 2.27 10.50 2.51 10.80 2.60 11.06 2.62 11.33 2.64 35 7.09 1.52 8.44 1.95 9.82 2.42 10.50 2.68 10.61 2.69 10.87 2.72 11.14 2.74 37 7.09 1.62 8.44 2.07 9.82 2.58…
-
MCAC-VTSM-2013-12 29 5.66 0.96 6.75 1.19 7.84 1.46 8.40 1.60 8.96 1.75 10.05 2.06 11.14 2.41 31 5.66 1.01 6.75 1.27 7.84 1.55 8.40 1.70 8.96 1.86 10.05 2.20 10.95 2.50 33 5.66 1.08 6.75 1.35 7.84 1.65 8.40 1.81 8.96 1.98 10.05 2.35 10.80 2.60 35 5.66 1.14 6.75 1.43 7.84 1.76 8.40 1.93 8.96 2.11…
-
4.24 0.65 5.06 0.79 5.89 0.94 6.30 1.03 6.71 1.11 7.54 1.29 8.36 1.48 29 4.24 0.69 5.06 0.84 5.89 1.00 6.30 1.09 6.71 1.18 7.54 1.38 8.36 1.59 31 4.24 0.73 5.06 0.89 5.89 1.07 6.30 1.16 6.71 1.26 7.54 1.46 8.36 1.69 33 4.24 0.77 5.06 0.94 5.89 1.13 6.30 1.23 6.71 1.34 7.54 1.56 8.36 1.80 35 4.24…
-
Combination
-
90% 80% R410a Full DC Inverter Mini VRF -3 -3.7 10.55 3.14 10.55 3.22 10.51 3.31 10.51 3.35 10.48 3.39 10.48 3.48 0 -0.7 11.39 3.25 11.39 3.33 11.35 3.41 11.35 3.45 11.35 3.49 11.03 3.42 3 2.2 12.30 3.36 12.27 3.44 12.27 3.51 12.23 3.54 11.83 3.40 11.03 3.11 5 4.1 12.92 3.43 12.92 3.50 12.67 3.46…
-
MCAC-VTSM-2013-12 -9.5 -10 8.94 3.34 8.91 3.42 8.91 3.49 8.91 3.53 8.62 3.39 8.03 3.10 -8.5 -9.1 9.13 3.37 8.48 3.45 9.09 3.51 8.91 3.43 8.62 3.30 8.03 3.02 -7 -7.6 9.46 3.42 9.46 3.49 9.20 3.42 8.91 3.28 8.62 3.15 8.03 2.89 -5 -5.6 9.97 3.48 9.78 3.46 9.20 3.21 8.91 3.08 8.62 2.96 8.03 2.72 -3 -3.7…
-
-17 6.48 2.90 6.11 2.71 5.75 2.52 5.53 2.43 5.35 2.33 4.99 2.15 -13.7 -15 6.48 2.76 6.11 2.58 5.75 2.40 5.53 2.31 5.35 2.23 4.99 2.06 -11.8 -13 6.48 2.62 6.11 2.45 5.75 2.28 5.53 2.20 5.35 2.12 4.99 1.96 -9.8 -11 6.48 2.49 6.11 2.32 5.75 2.17 5.53 2.09 5.35 2.01 4.99 1.86 -9.5 -10 6.48 2.42 6.11…
-
1.20 1.21 1.23 1.24 1.27 1.29 1.31 1.34 1.36 1.38 1.44 1.54 1.64 1.75 1.86 1.98 2.11 2.24 2.38 2.41 2.43 2.51 2.60 1.02 1.03 1.04 1.06 1.07 1.09 1.11 1.12 1.14 1.16 1.18 1.20 1.23 1.24 1.27 1.35 1.45 1.54 1.64 1.74 1.85 1.97 2.09 2.19 2.28 2.41 2.52 0.90 0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.02 1.04…
-
-5 -2 80% 70% -5 -2 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 6.63 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80 5.80…
-
-5 -2 60% 50% -5 -2 5.80 5.80 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.96 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15…
-
Combinati
-
70% -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13…
-
-19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8…
-
-5 -2 100% 90% -5 -2 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 10.40 11.39 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.45 9.79 8.50…
-
-5 -2 80% 70% -5 -2 8.50 8.50 8.50 8.50 8.50 8.50 8.50 8.50 8.50 8.50 8.50 8.50 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 7.55 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60 6.60…
-
-5 -2 60% 50% -5 -2 6.60 6.60 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 5.65 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73…
-
Combinatio
-
70% 52 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13…
-
-19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8…
-
-5 -2 100% 90% -5 -2 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 11.51 12.61 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46 10.46…
-
70% -5 -2 -5 -2 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 9.41 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 8.36 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31 7.31…
-
-5 -2 60% 50% -5 -2 7.31 7.31 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 6.26 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23 5.23…
-
Combination
-
70% -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13…
-
-19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -19.8 -18.8 -16.7 -13.7 -11.8 -9.8 -9.5 -8.5 -7 -5 -3 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8 11.8 13.7 -20 -19 -17 -15 -13 -11 -10 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6 7.9 9.8…
-
62 MCAC-VTSM-2013-12 39 14.19 4.40 16.81 5.66 17.31 5.72 17.56 5.76 17.81 5.79 18.37 5.85 18.88 5.91 41 14.19 4.52 16.68 5.70 17.18 5.76 17.43 5.80 17.68 5.83 18.24 5.87 18.33 5.95 43 14.19 4.59 16.59 5.74 17.04 5.80 17.29 5.82 17.54 5.85 17.92 5.88 18.05 6.07 45 14.19 4.64 16.50 5.79 16.88 5.85…
-
R410a Full DC Inverter Mini VRF 43 11.81 3.72 14.06 4.68 16.37 5.74 16.41 5.78 16.87 5.84 17.36 5.92 17.43 5.99 45 11.81 3.94 14.06 4.89 16.37 5.84 16.06 5.86 16.78 5.95 17.21 6.01 17.08 6.07 48 -5 12.23 4.11 14.57 5.06 16.96 5.85 15.95 5.92 17.35 6.06 16.74 6.08 17.30 6.13 10.62 1.47 12.69 1.77…
-
MCAC-VTSM-2013-12 48 -5 9.44 2.84 11.25 3.33 14.69 4.19 14.00 4.67 14.94 5.02 16.75 5.95 18.64 6.04 8.25 1.16 9.87 1.36 11.44 1.54 12.25 1.65 13.06 1.76 14.63 2.01 16.25 2.32 -2 8.25 1.17 9.87 1.36 11.44 1.55 12.25 1.68 13.06 1.79 14.63 2.05 16.25 2.35 0 8.25 1.17 9.87 1.38 11.44 1.58 12.25 1.71…
-
5.91 0.86 7.06 1.01 8.19 1.15 8.75 1.21 9.31 1.28 10.44 1.45 11.63 1.56 0 5.91 0.88 7.06 1.03 8.19 1.17 8.75 1.23 9.31 1.30 10.44 1.47 11.63 1.59 2 5.91 0.89 7.06 1.04 8.19 1.19 8.75 1.24 9.31 1.32 10.44 1.48 11.63 1.62 4 5.91 0.90 7.06 1.06 8.19 1.21 8.75 1.26 9.31 1.35 10.44 1.52 11.63 1.66 6 5.91…
-
Combination
-
R410a Full DC Inverter Mini VRF 33 15.40 3.44 18.32 4.45 19.75 4.87 20.02 4.89 20.29 4.91 20.83 4.97 21.37 5.01 35 15.40 3.67 18.32 4.74 19.41 5.04 19.68 5.07 20.02 5.09 20.56 5.15 21.10 5.20 37 15.40 3.90 18.32 5.05 19.14 5.22 19.41 5.25 19.68 5.28 20.22 5.33 20.76 5.39 39 15.40 4.15 18.25 5.34…
-
68 MCAC-VTSM-2013-12 27 12.83 2.22 15.27 2.82 17.78 3.49 19.00 3.85 20.22 4.23 20.90 4.35 21.38 4.39 29 12.83 2.37 15.27 3.01 17.78 3.73 19.00 4.12 20.15 4.49 20.63 4.54 21.10 4.57 31 12.83 2.52 15.27 3.21 17.78 3.98 19.00 4.39 19.88 4.67 20.29 4.71 20.76 4.75 33 12.83 2.68 15.27 3.42 17.78 4.24…
-
10.25 1.50 12.21 1.81 14.18 2.14 15.20 2.30 16.22 2.50 18.19 2.95 20.15 3.42 23 10.25 1.53 12.21 1.85 14.18 2.24 15.20 2.45 16.22 2.68 18.19 3.15 20.15 3.67 25 10.25 1.58 12.21 1.96 14.18 2.39 15.20 2.62 16.22 2.86 18.19 3.38 20.15 3.93 27 10.25 1.68 12.21 2.09 14.18 2.55 15.20 2.80 16.22 3.05 18.19…
-
7.67 1.09 9.16 1.29 10.65 1.50 11.40 1.60 12.15 1.71 13.64 1.94 15.13 2.18 18 7.67 1.11 9.16 1.31 10.65 1.52 11.40 1.63 12.15 1.75 13.64 1.97 15.13 2.22 20 7.67 1.13 9.16 1.33 10.65 1.55 11.40 1.66 12.15 1.78 13.64 2.01 15.13 2.26 21 7.67 1.14 9.16 1.34 10.65 1.56 11.40 1.68 12.15 1.79 13.64 2.03…
-
8. Electric Characteristics
-
9. Sound Levels
-
10.Operation Limits
Cooling Heating -5 -10 -15 -20 -5 -10 10 20 Range for continuous operation 30 25 Range for intermittent operation Outdoor temperature (℃ DB) 35 30 Outdoor temperature (℃ WB) 45 40 Range for intermittent operation Range for continuous operation Indoor temperature (℃ WB) Indoor temperature (℃ DB)…
-
1. Precautions
Ensure that all Local, National and International regulations are satisfied. Read this “PRECAUTIONS” carefully before Installation. The precautions described below include the important Items regarding safety. Observe them without fail. After the installation work, perform a trial…
-
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit
Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply. An insufficient power supply capacity or inappropriate installation may cause fire. Use the specified cables for wiring connect the…
-
3. Outdoor unit installation
3.1 Installation space selection Install the outdoor unit at a place where discharge air is not blocked. When an outdoor unit is installed in a place that is always exposed To a strong wind like a coast or on the high store of a building, secure a normal fan operation by using a duct or a wind…
-
>60cm
R410a Full DC Inverter Mini VRF Fix with bolt Single unit installation >300 (Wall or obstacle) Air inlet >300 Maintain channel Air inlet >2000 >600 Air outlet Parallel connect two units or above >300 >600 >2000 Parallel connect the front with rear sides >2000 >500 >3000 >3000 >300 All the pictures…
-
While installing the outdoor unit, pay attention to the installation place and the drainage pattern; if it’s installed at the alpine zone, the frozen condensed water will block up the water outlet, please pull out the rubber stopper of the reserve water outlet. If that still fails to satisfy for the…
-
Note: When the total equivalent piping length of liquid + gas side is ≥90m, it must increase the size of air side main pipe. Besides, according to the distance of refrigerant pipe and the over matched state of indoor unit, when the capacity is decreasing it still can increase the gas side main pipe…
-
4.3 Refrigerant pipe selection
R410a Full DC Inverter Mini VRF The first connecting method Outdoor Unit L1 L2 A L3 B L4 C b a c L5 D f E d e The first Line Branch Pipe The second connecting method Outdoor Unit(Take Model 160 for example) N1 (28) a L1 L2 A L3 The first Line Branch Pipe intdoor Units B N2 (28) b L4 C N3 (28) c D L5…
-
Low static pressure 5.6
15.9(Flaring nut) Thin duct type 7.1 12.7(Flaring nut) A5 duct type 2.2~4.5 12.7(Flaring nut) A5 duct type 5.6~8.0 15.9(Flaring nut) A5 duct type 9.0~14.0 15.9(Flaring nut) Console Type 2.2~4.5 12.7(Flaring nut) Two-way Cassette Type 2.2~4.5 12.7(Flaring nut) Two-way Cassette Type 5.6~7.1…
-
4.4 Remove Dirt or Water in the Piping
R410a Full DC Inverter Mini VRF Make sure there is no any dirt or water before connecting the piping to the outdoor units. Wash the piping with high pressure nitrogen, never use refrigerant of outdoor unit. 4.5 Airtight Test Charge pressured nitrogen after connecting indoor/outdoor unit piping to do…
-
5. Electric Wiring Installations
5. 1 Highlights of electrical installation 1) Please separately design the special power of indoor units and outdoor units. 2) The power adopts special circuit, and installs creepage protector and manual switch. 3) The indoor units’ power, creepage protector and manual switch connecting to the same…
-
3) The wiring through pipe shall not be in the form with ends jointing. If there must be joint, connection box should be installed at the corresponding place. 4) The wiring with different voltage should not pass through the same wire tube. 5) Total sectional area of wiring through wire tube shall…
-
Indoor unit connect with power supply which is 220-240V~50Hz. Outdoor unit connect with power supply which is 220-240V~ 50Hz (Please set all the indoor unit power supply of one system into the same circuit. It should turn on or shut down the unit at the same time, otherwise, the service life would…
-
7. Test Running
Operate according to “key points for test running” on the electric control box cover. CAUTION Test running cannot start until the outdoor unit has been connected to the power for 12hours. Test running cannot start until all the valves are affirmed open. Never make the test running if the…
-
1. PCB ports instructions
80/105 model PCB ports instruction No. 1 CN27 2 CN33 3 CN32 4 CN19 5 CN21 6 CN14 7 CN22 8 CN15 9 CN23 10 CN16 11 CN34 12 13 CN18 14 CN30 15 CN29 Content PCB power supply output port EXV download output port Online programmable port Reserved Load output port Load output port (SV6) Load output port…
-
120~160 model
PCB ports instruction No. 1 CN48 2 CN24 3 CN42 4 CN26 5 CN25 6 CN43 7 CN23 8 CN45 9 CN44 10 CN47 11 CN46 12 CN20 13 14 CN11 15 CN10 16 17 CN1 18 CN6 19 CN7 20 21 CN8 21 CN8 22 CN49 Port voltage AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V AC 220V DC 5V / DC 5V DC…
-
180 model
PCB ports instruction No. Content Port voltage 1 CN3 PCB power supply output port 220V 2 CN4 PCB power supply output port 220V 3 CN7 Load output port (SV6) 0V or 220V 4 CN13 Load output port(4-way valve STF1) AC 220V 5 CN35 Load output port(crankcase heating) AC 220V 6 CN31 Load output port(single…
-
7 CN26
-
2. PCB parts instructions
80/105 model SW1: Forced LED digital cooling tube display button SW2: Query button Function setting dial switch SW2 query instructions No. Content 1 Normal display Operating mode Operating fan speed level The total required capacity of the indoor unit The required capacity of the revised outdoor…
-
120~160 model
SW1: Forced cooling button SW2: Query button LED digital tube display Function setting dial switch SW-1 query instructions No. Content 1 Normal display Operating mode Operating fan speed level The total required capacity of the indoor unit The required capacity of the revised outdoor unit T3 piping…
-
180 model
SW1: Forced cooling button SW2: Query button LED digital tube display Function setting dial switch SW2 query instructions No. Content 0 Normal display Operating mode Operating fan speed level The total required capacity of the indoor unit The required capacity of the revised outdoor unit T3 piping…
-
T2 average temperature Actual value 13 Total quantities of the indoor units Actual value 14 The quantities of the operating indoor units Actual value 15 Model Type 8KW: 8; 16 Priority mode Reserved 17 Version of the program 18 The last malfunction or protection code 19 Display “--” 10KW: 10 If there…
-
4. LED on PCB instructions
The lamp on the 80/105 model, refers to the following picture LED 2 (Red) LED 1 (Green) IR341 chip The lamp on the 120~160 model, refers to the following picture LED 2 (Red) LED 1 (Green) LED1: Malfunction indicator lamp of inverter module. The lamp will be off if the system running is normal. And…
-
5. PCB Introduction
80/105 model PFC Module IPM Module Filter Board Drive Board Main PCB 120~160 model IPM Module Drive Board Main PCB Filter Board PFC Module 98 Troubleshooting
-
180 model
IPM Module PFC Module Troubleshooting Main PCB Filter Board 99
-
6. Error code table
Error code H0 Content 80/105/180 Communication malfunction between IR341 and main control board E3 model 120~160 model E2 Communication malfunction between the indoor chip and outdoor chip. All models E4 Pipe temperature T3& ambient temperature T4 sensor malfunction All models E5 Outdoor unit…
-
model
L7 Wrong phase protection 80/105/180 model L8 Frequency difference in one second >15Hz protection 80/105/180 model L9 Frequency difference between setting speed and running speed more than 15Hz protection 80/105/180 model Note: P6 display on digital tube automatically, L0~L9 these error codes will…
-
7. Troubleshooting
7.1 H0/E3: Communication malfunction between IR341 and main chip on the main PCB. (H0 is for 80/105/180 model,E3 is for 120~160 model.) IR341 chip: it is used for inverter compressor drive. 0537 chip: it is used for control the communication between indoor unit and outdoor unit, and the…
-
7.2 E2: Communication malfunction between indoor chip and outdoor chip.(for all models)
LED displays E2 Communication malfunction between indoor unit chip and outdoor unit chip. NO Check whether the indoor unit is power on. Plug the indoor unit in. YES Check whether the three-cored shielded wire is used as the communication wire and earthed properly. Replace shielded wire or earth the…
-
HP
MCAC-VTSM-2013-12 0.8 1.0 1.2 1.6 2.0 2.5 3.0 3.2 4.0 5.0 For example: Press the button for 5 seconds: If the “running” and “warning” lights are normally on, that means the address code is 9=(8+1) If the lights are blink, the address code should plus 16, so the address code is 25=16+(8+1) Press the…
-
7.3 E4: Pipe temperature T3& ambient temperature T4 sensor malfunction (for all models)
LED displays E4 Pipe temperature T3& ambient temperature T4 sensor malfunction NO YES Whether the wire body is broken. Connect the wire again. NO Judge whether temperature sensor pin connects properly. YES Connect again. NO PCB is disabled. Replace PCB. Case: There is no display on PCB of one…
-
7.4 E5: Voltage protection malfunction (for all models)
LED displays E5 Voltage protection malfunction Whether the input voltage is 180-260V. NO Check the power supply. YES Replace the filter board and check whether the unit can operate normally. YES OK NO Replace the main PCB 106 Troubleshooting
-
(E6 is for all models, Eb is for 80/105/180 model, E8 is for 120~160 model) If the system display twice E6 in 10 minutes, the system will stop and display E8/Eb. When the system displays E8/Eb, the system can resume only by restarting the machine. At this time, malfunction should be disposed…
-
7.6 E7: Discharge Temperature Sensor Malfunction (only for 80/105/180 models.)
LED displays E7 Discharge sensor malfunction. Check whether discharge temperature sensor’s head is inside the sleeve or its wiring is connected to the main PCB properly. NO Connect again. YES NO Check whether the discharged sensor is normal. ① Replace discharge sensor. YES NO Check whether the 4-way…
-
The malfunction may be caused by two reasons: 1) The EEPROM is not inserted well; 2) Outdoor main board is broken. LED display E9/E0 EEPROM malfunction Check whether the EEPROM is inserted well. NO Insert the EEPROM well YES Replace outdoor main PCB. Troubleshooting 109
-
7.8 EA/E7: T3 pipe temperature exceeds 27 degrees for more than 5 minutes when heating mode
(EA is for 8/105/180 model, E7 is for 120~160 model) LED displays EA/E7 System faulty that T3 pipe temperature exceeds 27 degrees for more than 5 minutes when heating mode. Whether the outdoor ambient temperature is higher than the unit’s operating condition when heating mode. YES Belongs to system…
-
7.9 P1: High pressure protection (for all models)
LED displays P1 High pressure protection NO Whether the wiring is correct. Connect again. YES Whether the wire body is broken. YES NO Short-circuit high pressure switch. Check whether the system can operate normally. Replace the high pressure switch. YES Check whether the cooling system operates…
-
7.10 P2: Low pressure protection (for all models)
When the pressure is lower than 0.05MPa, the system will display P2 protection, the ODU in standby. When the pressure is higher than 0.15MPa, P2 disappears and resumes normal operation. LED displays P2 Low pressure protection Whether wiring connection between low pressure switch and PCB is connected…
-
7.11 P3: Compressor current protection (for all models)
It will protect when input current is more than 30A. It will recover when input current is less than 30A. It will recover automatically. LED displays P3 Input current protection Check whether the input current of the power wire is more than 30A. YES Check cooling system is normal or not. Check…
-
7.12 P4: Compressor discharged temperature protection (for all models)
When the discharged temperature of the compressor is higher than 115°C, the unit will stop running. When the discharged temperature of the compressor is lower than 90°C , the unit resumes normal operation automatically. LED displays P4 Discharged temperature of the compressor Check whether the…
-
7.13 P5: Condenser high temperature protection (for all models)
When condenser temperature is higher than 62 degrees for 3 seconds, the unit will stop operating. When pipe temperature outside is lower than 52 degrees, the unit will resume operate. LED displays P5 Condenser T3 high temperature protection YES Check whether condenser temperature is higher than 62…
-
7.14 P6: IPM Module protection
The following explanation is for 80/105 model. LED displays P6 IPM module protection Check whether P-N voltage on the IPM module NO is OK. The DC voltage is from 277 to 356V. YES Check if wiring connection between main PCB and IPM module is fasten or not. NO NO Connect firmly again and check whether…
-
P6: Module protection
P6 code can display on digital tube automatically. L0~L9 these error codes will display on digital tube only through check button. L0~L9 is only display on the 80/105 model but not on 120~160 model. P6 will disappear in one minute. Then press the check button to find the specific error code when P6…
-
DC generatrix check
Direction of the current in DC supply wire is running through the inductor should be the same as the direction of arrow marked on the inductor Check the voltage of DC generatrix, the normal value should be 296 to 324V. If the value is less than 296V, go to next step. 1) Check the wiring connection…
-
Step 1: Replace the modular with correctly wire connection and start the system, if system is still
malfunction, then go to step2 to check the compressor. Step 2: Take out the compressor from the malfunction system, short-circuit the suction and the discharge, vacuum dry and charge 0.3kg~0.4kg R410A, and then connect the U,V,W terminals to control box B which is took apart from normal system. If…
-
7.14.2 L1/L4 troubleshooting
Step 1: Check the DC voltage between P and N terminal, the normal value should be 510V~580V, if the voltage is lower than 510V, go to step 2. Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If wires are OK, replace the PCB. 1-Phase Filter…
-
7.15 PE/P7 malfunction: Evaporator T2 high temperature protection
(PE is for 8/105/180 model, P7 is for 120~160 model) When the middle average temperature of the evaporator is higher than 63 degrees for 50 seconds, the unit will stop operating. When pipe temperature is lower than 50 degrees, the unit will resume running. LED displays PE/P7 Evaporator T2 high…
-
7.16 P8: Typhoon protection (for all models)
LED displays P8 Typhoon protection When air conditioner is standby or in malfunction stopping status, check if there is strong air blows the fan phenomenon. NO YES Belongs to normal protection NO Check whether the fan motor is normal. Replace fan motor. YES Replace outdoor main PCB or transfer board…