Инструкция на Наружные блоки мини VRF-системы V4+ 8-10-12-14-16-18 (сервис мануалы)
Наружные блоки мини VRF-системы V4+ (R410a 380). Часть 4. Устранение неисправностей. Сервис мануал.
Смотрите также: Сервис мануал →
Загружаем документ…
Текст инструкции
-
Part 4
Troubleshooting 1. Normal Air Conditioner Phenomenon 73 2. Air Conditioner Protection in Common 73 3. Malfunction Code and Troubleshooting 74 Troubleshooting 73
-
1. Normal Air Conditioner Phenomenon
1.1 When outdoor unit appears white vapor or water, the reasons is as follows: 1) The fan of outdoor unit stops to begin defrosting. 2) The electromagnet valve sends out the noise when the defrosting begins and ends. 3) There is sound like water flowing when running or off; and the noise enlarges…
-
supply switch to cut it off. Before restarting machines, please press the on/off key again as above
3. Malfunction Code and Troubleshooting If there is phenomenon as follows, please stop air conditioner running and cut power supply and refer to the following. However, if the problem insists, please contact the customer service center of Midea commercial air conditioner company, and offer machine’s…
-
18kW malfunction code
Display 76 Malfunction or Protection HF Not matched with M_HOME indoor unit E9 EEPROM malfunction E2 Communication malfunction between indoor and outdoor units H0 Communication malfunction in outdoor PCB E4 T3&T4 temperature sensor malfunction E5 Outdoor unit voltage protection E6 DC fan motor…
-
Outdoor Unit Display E0/E9 Error Explanation EEPROM malfunction. Supposed Causes 1. The EEPROM is not inserted well. 2. Outdoor main board broken. Troubleshooting LED indicates E0 EEPROM malfunction Check whether the EEPROM is inserted well No Insert the EEPROM well Yes Replace outdoor main board…
-
3.2 "E2": Communication malfunction between
indoor/outdoor units Outdoor Unit Display E2 Error Explanation Communication malfunction between indoor/outdoor units Supposed Causes 1. Indoor unit power is off 2. The signal wiring is not shield cable or the shield cable is not earthed. 3. The signal wiring between the indoor and outdoor units is…
-
3.3 "E3"/"H0"
Communication malfunction in outdoor PCB Outdoor Unit Display E3/H0 Error Explanation Communication malfunction in outdoor PCB Supposed Causes 1. The outdoor main board 2 is broken 2. The connecting wiring between the IPM module and the CN1 on the main board 2 is break off Troubleshooting LED…
-
Use the multi-meter to measure whether the
voltage between the P and the N on the power board is between+(277V~345)V Yes Replace the IPM module No Replace the power board 80 Troubleshooting
-
Outdoor Unit Display E4 Error Explanation T3&T4 temperature sensor malfunction. Supposed Causes 1. Outdoor temperature sensors (T4/T3) are malfunction. 2. The resistance of outdoor temperature sensors(T3/T4) is wrong Troubleshooting LED indicates E4 T3&T4 temperature sensor malfunction Outdoor temp.…
-
3.5 "E5": Outdoor unit voltage protection
Outdoor Unit Display E5 Error Explanation Outdoor unit voltage protection. Supposed Causes 1. Power supply fault. 2. Power board broken. Troubleshooting LED indicates E5 Outdoor unit voltage protection Check the voltage of outdoor unit power supply, whether the voltage between L and N is about…
-
3.6 "E6": DC fan motor malfunction
Outdoor Unit Display E6 Error Explanation Direct current fan motor malfunction Supposed Causes 1. The wiring connected is fault. 2. Power supply voltage is not normal. Troubleshooting LED indicates E6 DC fan motor malfunction No Judge 1:Check the wiring connected is right according the wiring…
-
than 5 minutes in Heating model Outdoor Unit Display E7/EA Error Explanation A fan in the A region run for more than 5 minutes in Heat model. Supposed Causes Troubleshooting 84 When LED indicates E7, please connect local branch company. Troubleshooting
-
3.8 "P0"/"PL"
Radiator high temperature protection Outdoor Unit Display P0/PL Error Explanation Recovery the compressor stop three minutes later for temperature reduced. Supposed Causes Troubleshooting LED indicates P0 Radiator high temperature protection Stop unit and waiting for Three minutes for temperature…
-
3.9 "P1": High pressure protection
Outdoor Unit Display P1 Error Explanation High pressure protection. Supposed Causes 1.Wiring between the high pressure switch and main control board is not connected well or correctly. 2.The high pressure switch is broken. 3.The outdoor unit is bad ventilation. 4.The heat exchanger is dirty. 5.The…
-
Check whether the refrigerant pipe is blocked
Replace outdoor main board Troubleshooting R410a Full DC Inverter Mini VRF Drop refrigerant, then use the high pressure nitrogen or refrigerant to blow pipe, vacuumize and add the refrigerant again 87
-
3.10 "P2": Low pressure protection
Outdoor Unit Display P2 Error Explanation Low pressure protection Supposed Causes 1. The wiring between the low pressure switch and main control board is not connected well or not correctly. 2. The low pressure switch is broken. 3. The outdoor ambient temperature is too low. 4. The refrigerant of…
-
Validate: Connect the pressure gauge to the
gauge joint of the system, check whether the pressure is lower than 0.15MPa No Judge 5: The refrigerant pipe is blocked No Yes Leak hunting: charge nitrogen or refrigerant to the system, if the leakage is serious, there will be distinct gas leakage “cici” sound; if the leakage is little, use the…
-
3.11 "P3": Compressor current protection
Outdoor Unit Display P3 Error Explanation Compressor current protection Supposed Causes 1. The outdoor ambient temperature is too high. 2. The outdoor unit is bad ventilation. 3. The heat exchanger is dirty. 4. The refrigerant pipe is blocked. Troubleshooting Normally the only way to deal with is to…
-
3.12 "P4": Compressor discharge temperature
protection Outdoor Unit Display P4 Error Explanation When compressor discharge temperature is more than 115°C, the unit will stop, and unit runs again when compressor discharge temperature is less than 90°C. Supposed Causes 1.The wiring connection is not right between compressor discharge temp.…
-
3.13 "P5": Condenser high temperature protection
Outdoor Unit Display P5 Error Explanation When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp. less than 52°C. Supposed Causes 1. The temperature sensor is broken. 2. The voltage transformer of IDU is defective. 3. The heat exchanger is dirty.…
-
3.14 "P6": IPDU modules protection
Outdoor Unit Display P6 Error Explanation IPDU modules protection. Supposed Causes 1. 2. 3. 4. DC generatrix is not lined correctly. DC generatrix low or high voltage protection. MCE malfunction. Compressor’s frequency changes incorrectly. Troubleshooting Troubleshooting 93
-
Detailed Malfunction Code of Module Protection (P6) (Only for 18kW)
Display Malfunction or Protection definition Note L0 Module Malfunction Module or compressor L1 Low voltage protection of DC generatrix Check power supply of module L2 High voltage protection of DC generatrix Check power supply of module L3 Reserved L4 MCE Malfunction/synchronization/ cycle loop…
-
2 Voltage check of module
2.1 The voltage between N and P should be 1.41times to local power supply. 2.2 The voltage between 1 and 2 should range from 510V to 580V 2.3 The resistance between 1,2,3,4,5 should be infinite. If any of them is about 0, which means the module has already been broken down, we need to replace the…
-
3.3 Measure the current of the compressor's U,V,W terminal respectively, which should be more or less the same, by e.g. current flow table clamp.They should be 4A at the frequency of 35 Hertz. 4 P6 appears after the compressor turns on with difficulties 4.1 Check the module according to step 3…
-
Error
R410a Full DC Inverter Mini VRF Low voltage protection Here are 3 circumstances: a) The voltage between the two electrolytic capacitors is less than 450V. The AC contactor should be picked up. If not, there's something wrong with the main control board or the PTC resistors, which need to be replace…
-
3.15 "P7"/"PE"
Evaporator high temperature protection Outdoor Unit Display P7/PE Error Explanation Evaporator high temperature protection. Supposed Causes Temperature sensor port connected is not right. Troubleshooting LED indicates P7 98 ODU's load is excess. Adjust IDU's load or add ODU. Refrigerant is excess.…
-
3.16 "P8": Typhoon protection
Outdoor Unit Display P8 Error Explanation Typhoon protection. Supposed Causes Typhoon Troubleshooting LED indicates P8 No A Typhoon occurrence. Whether the DC Fan motor is broken Yes Whether system in standby state detect DC fan speed was 400 RPM . Replace the DC Fan motor. Stop system until detect…