1. Features
1.1 Energy saving 1.1.1 All DC inverter compressors All DC inverter compressors make the capacity output better distributed, and always work at 60-120Hz which is the most efficient range. It makes the efficiency more than 30% higher than the normal. New structure-enhanced mid-frequency performance…
-
1.2 Flexible design
1.2.1 Wide capacity range The outdoor units capacity range from 8HP to 64HP in 2HP increment. Maximum 64 indoor units with capacity up to 130% of total outdoor units can be connected in one refrigeration system. 1.2.2 Wide operation range The V4 Plus R series system operates stably at extreme…
-
1.3 High reliability
1.3.1 Double cycle duty operation The cyclical start-up sequence of outdoor units and DC inverter compressors equalized compressor duty and extends operating life. Priority Priority Priority Priority Compressor cycle duty in one module Cycle duty between modules 1.3.2 Double backup operation Outdoor…
-
1.4 Enhanced comfort
1.4.1 Cooling and heating simultaneous for new designed MS (Mode Switch) equipment The outdoor unit individual controls the operation mode of each group indoor unit to achieve simultaneous heating and cooling in one system under the MS unit which adopts solenoid valve to precise control refrigerant…
-
1.5 Convenient installation & maintenance
1.5.1 Remote addressing Addressing indoor units are able to be done just by pressing the button of the controller. Remote addressing No need to set the address by the DIP switch one by one. 1.5.2 Simple communication wiring Centralized controller (CCM03) can connect from indoor side or outdoor side…
-
2. Outdoor units lineup
-
Combination table
-
3. MS units lineup
-
4. Indoor units lineup
Cassette type One-way cassette Capacity Two-way cassette Compact four-way cassette Four-way cassette (×100W) 18 ● 22 ● ● ● 28 ● ● ● ● 36 ● ● ● ● ● ● 45 ● ● 56 ● ● ● 71 ● ● ● 80 ● 90 ● 100 ● 112 ● 140 ● Duct type Capacity Low static pressure duct Medium static pressure duct High static pressure duct…
-
Indoor units lineup
Cased floor-standing Floor-standing/Ceiling & Floor/Console Uncased floor-standing Ceiling & floor console Capacity (×100W) 22 ● ● ● 28 ● ● ● 36 ● ● ● ● 45 ● ● ● ● 56 ● ● ● 71 ● ● ● 80 ● ● ● 90 ● 112 ● 140 ● 160 ● Wall mounted Wall mounted (S panel) Wall mounted (C panel) Wall mounted (D panel) 22 ●…
-
5. Nomenclature
5.1 Outdoor unit MDV – 252 (8) W / D2 R N1 T (C) Series code T: 3-pipe type Omit: 2-Pipe type Refrigerant type N1: R410A Power supply R: 380-415V, 3Ph, 50Hz Inverter type D2: All DC inverter type Omit: AC inverter Outdoor unit Cooling capacity (HP), (only for combinable type) Cooling capacity…
-
5.3 Indoor unit
MDV – D 28 Z / D D N1 A Series code Refrigerant type N1: R410A Electrical Auxiliary Heater D: with EAH Omit: without EAH Motor Type D: DC Fan Motor Omit: AC fan Motor Indoor unit type* (refer to below table) Cooling Capacity (×100W) VRF Indoor Unit Midea Meaning of the code* Type code Meanings Q1…
-
1. Introduction
1.1 Model selection procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. -conditioning load, Calculate the maximum air-conditioning load for each room or zone. Selection of an air conditioning system Design of the control…
-
rooms may be considered
The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at 100% combination ratio of each outdoor unit. Up to 8~16 indoor units can be connected to one outdoor unit. It is recommended to choose a larger…
-
INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE
Indoor Unit Combination Ratio kW(Btu/h) Outdoor Unit 40(385600) 42(409500) 44(426500) 46(443600) 48(460600) 50(488600) 52(498100) 54(516900) 56(539100) 58(563000) 60(580000) 62(597100) 64(614000) Selection Procedure 130% 120% 110% 100% 90% 80% 70% 60% 50% 146.9 135.6 124.3 113.0 101.7 90.4 79.1 67.8…
-
INDOOR UNIT CAPACITY INDEX
Model Model Model Model Model Model Model Model Model Model Capacity Index 1.8 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 kW(Btu/h) (6140) (7500) (9550) (12280) (15350) (19110) (24230) (27300) (30710) (38220) Model Model Model Model Model Model Model Model Model Capacity Index 12.5 14.0 kW(Btu/h) (42650)…
-
H: Height difference between outdoor and indoor unit. Positive data means outdoor unit is top. Negative data means outdoor unit is down. 1.5.2 Heating capacity modification H(m) 100% 10 -10 -20 -30 -40 -50 -60 -70 -80 -90 -100 -110 L(m) 2. Unit selection (based on cooling load) 2.1 Given condition…
-
For the 92% combination, calculate the cooling capacity of outdoor unit (MDV-280(10)W/D2RN1T(C))
-
1. Specifications
-
Tube type
Coil dimension inner-groove tube inner-groove tube inner-groove tube 42×1-1/2×48-1/2 42×1-1/2×48-1/2 42×1-1/2×48-1/2 (1067×38×1232) (1067×38×1232) (1067×38×1232) in.(mm) (W×D×H) Condenser quantity Number of circuits m /h 12,000 12,000 13,000 CFM 7,060 7,060 7,650 dB(A) % 50-130 50-130 50-130 Outdoor…
-
Independent unit specifications
-
m /h 15,000 15,000 CFM 8,830 8,830 dB(A) 60 60 % 50-130 50-130 23 26 inch 49-7/32×63-9/16×30-1/8 49-7/32×63-9/16×30-1/8 mm 1250×1615×765 1250×1615×765 inch 51-9/16×70-1/2×32-1/2 51-9/16×70-1/2×32-1/2 mm 1305×1790×820 1305×1790×820 Net weight Ibs.(kg) 666.6(303) 666.6(303) Gross weight Ibs.(kg)…
-
Combination unit specifications
-
Sound pressure level
-
Combination unit specifications
-
m /h 27,000 27,000 30,000 CFM 15,890 15,890 17,660 dB(A) % 50-130 50-130 50-130 Outdoor air flow Sound pressure level Connectable Total capacity indoor unit Max. quantity inch (49-7/32×63-9/16×30-1/8)×2 mm (1250×1615×765)×2 inch (51-9/16×70-1/2×32-1/2)×2 mm (1305×1790×820)×2 Net dimension (W×H×D)…
-
Combination unit specifications
-
Tube type
Coil dimension inner-groove tube inner-groove tube inner-groove tube 42×1-1/2×48-1/2 42×1-1/2×48-1/2 42×1-1/2×48-1/2 in.(mm) (W×D×H) (1067×38×1232) (1067×38×1232) (1067×38×1232) 3 m /h 30,000 30,000 39,000 CFM 17,660 17,660 22,950 dB(A) % 50-130 50-130 50-130 Outdoor air flow Sound pressure level…
-
Combination unit specifications
-
Tube outside diameter
-
Combination unit specifications
-
Coil dimension
-
Combination unit specifications
-
Hydrophilic
Fin type Hydrophilic aluminium Hydrophilic aluminium aluminium Tube outside diameter in.(mm) Tube type Coil dimension Ф5/16(7.94) Ф5/16(7.94) Ф5/16(7.94) inner-groove tube inner-groove tube inner-groove tube 42×1-1/2×48-1/2 42×1-1/2×48-1/2 42×1-1/2×48-1/2 in.(mm) (W×D×H) (1067×38×1232)…
-
Combination unit specifications
-
Fin spacing
R410A All DC Inverter V4 Plus R Series 50/60Hz in.(mm) Fin type Tube outside diameter in.(mm) Tube type Coil dimension 1/16(1.6) 1/16(1.6) 1/16(1.6) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Ф5/16(7.94) Ф5/16(7.94) Ф5/16(7.94) inner-groove tube inner-groove tube inner-groove…
-
Combination unit specifications
-
Tube outside diameter
-
1.2 MS units specifications
-
2. Dimensions
-
2.3 MS dimensions
-
3. Service space
3.1 Service space for outdoor unit Ensure enough space for maintenance. The modules in the same system must be on the same height. When installing the unit, leave enough space for maintenance. Unit: in.(mm) (Air outlet) (Air inlet) 4(100)< (Air inlet) 39-3/8(1000) Installation and maintenance…
-
When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to facilitate heat dissipation. See the figure below. The height of the air…
-
4. Piping diagrams
8/10/12HP EXV-A Liquid valve EXV-B Heat exchanger 1 ST1 ST2 Heat exchanger 2 Low pressure gas valve ST3 High pressure gas valve Oil balance valve Pressure release valve Pressure switch Pressure sensor SV5 SV2 Oil separator Gas-liquid separator SV4 Pressure switch DC inverter compressor Gas balance…
-
Key components
Oil separator: It is used to separate oil from high pressure and high temperature gas refrigerant, which is pumped out from compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon. Gas-liquid separator: It is used to store the liquid refrigerant…
-
5. Wiring diagram and field wiring
5.1 Wiring diagram 8/10/12HP 50 Specifications & Performances
-
14/16HP
Specifications & Performances 51
-
5.2 Field wiring
5.2.1 Signal wire between outdoor unit and indoor unit Signal wire of indoor/outdoor unit adopts 3-core shielded wire (≥0.0012in.2(0.75mm2) which has polarity, please connect it correctly. outdoor unit outdoor unit outdoor unit outdoor unit (master unit) (slave unit) (slave unit) (slave unit) (P Q…
-
6. Electric characteristics
Units Model Hz MDV-252(8)W/ 50/ D2RN1T(C) 60 MDV-280(10)W/ 50/ D2RN1T(C) 60 MDV-335(12)W/ 50/ D2RN1T(C) 60 MDV-400(14)W/ 50/ D2RN1T(C) 60 MDV-450(16)W/ 50/ D2RN1T(C) 60 Power supply Compressor OFM Voltage Min. Max. MCA TOCA MFA MSC RLA (V) (V) (V) (A) (A) (A) (A) (A) 380~415 342 440 18.4 20.8 25…
-
7. Capacity tables
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
Cooling capacity table
-
таблицы и схемы — в просмотре
-
7.2 Heating capacity tables
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
Heating capacity table
-
таблицы и схемы — в просмотре
-
8. Operation limits
Cooling o Heating o C o o -5 -10 -15 Indoor temperature (DB) -5 -10 23 -15 14 -20 5 o 35 C o 95 F Range for intermittent operation 35 Range for continuous operation F 86 Outdoor temperature (DB) 30 Range for intermittent operation 50 F 122 Range for continuous operation Outdoor temperature (DB) C -4…
-
9. Sound levels
Notes: • Data is valid at free field condition • Data is valid at nominal operating condition Front • Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular 51-3/16(1300) 39-3/8(1000) room in which the equipment is installed •…
-
10. Accessories
10.1 Standard accessories Name Shape Quantity Function Installation manual of outdoor unit 1 / Operation manual of outdoor unit 1 / Operation manual of indoor unit 1 / 1 For toggling of indoor and outdoor units Toggling flathead screw - 1 (8HP,10HP) 90°mouthing elbow 2 (12HP~16HP) Seal plug…
-
1. Select installation position
Ensure that the outdoor unit is installed in a dry, well-ventilated place. Ensure that the noise and exhaust ventilation of the outdoor unit do not affect the neighbors of the property owner or the surrounding ventilation. Ensure that the outdoor unit is installed in a well-ventilated…
-
R410A All DC Inverter V4 Plus R Series 50/60Hz Position illustration of screw bolt (Unit: in.( mm)) D C B A 5/8×7/8(15×23)long U-shape hole Size (in.(mm)) 8-16HP A 44-1/8(1120) B 49-1/4(1250) C 29(736) D 30-1/8(765) 3. Master and slave unit setting When the quantity of outdoor unit is more than two…
-
When the outdoor unit is higher than the surrounding obstacle
Unit: in.(mm) One row Two rows More than two rows When the outdoor unit is lower than the surrounding obstacle, to avoid cross connection of the outdoor hot air from affecting the heat exchange effect, please add an air director onto the exhaust hood of the outdoor unit to facilitate heat…
-
If miscellaneous articles are piled around the outdoor unit, such articles must be 31-1/2inch(800mm) below the top of the outdoor unit. The articles must be 31-1/2inch(800mm) below the top of the outdoor unit. Otherwise, a mechanic exhaust device must be added. Unit: in.(mm) Set the snow-proof…
-
5. Air ventilation assembly installation
The ventilation assembly is provided at the field installation. When installing, please take off the mesh cover firstly, and then install the unit as the following method. Example A Unit: in.(mm) Support 47-5/8(1210) C A Radius 3-9/16(90) 28-9/16(725) B 4(100) Air outlet louver dimension (optional)…
-
12 ST3.9 self-threading screws 3/8(10) 12-Φ1/8(3.2) Remove the two iron filters firstly 765 3/8(10) 3 93 16-3/16 8-3/8 16-3/16 (411) (213) (411) 16-3/16 8-3/8 16-3/16 (411) (213) (411) 49-7/32(1250) Unit: in.(mm) Example A Example B A A≥11-3/4(300) A A≥11-3/4(300) B B≥9-7/8(250) B B≥9-7/8(250) C…
-
6. Refrigerant piping installation
-
6.3 Example
-
6.4 Piping connection between outdoor units
All connection pipes between outdoor units should be horizontally, it is not allowed the concave at junction site. The height of each connection pipe between outdoor units is not allowed to over the height of refrigerant outlet pipe. √ Correct way Correct way × Wrong way × Wrong way . 6.5 Branch…
-
tg
7. Caution for brazing Make sure to blow through with nitrogen when brazing. Blowing through with nitrogen prevents the creation of large quantities of oxidized film on the side of the pipe. An oxidized film adversely affects valves and compressors in the refrigerating system and prevents proper…
-
9. Gas tightness test
Charge 40kgf/cm2 nitrogen gas from the high-pressure gas valve from the meter connector. Pressure inside should be maintained no less than 24 hrs. MS Nitrogen Liquid pipe Nitrogen High-pressure gas pipe Nitrogen Low-pressure gas pipe Indoor unit Note: 2 Pressurized nitrogen (3.9MPa; 40kgf/cm ) is…
-
Respectively connect the vacuum pump in the gas balance valve and oil balance valve
Perform the pump (last for 10 minutes or above) Close the pressure gauge and vacuum pump in turn Open the gas balance valve and oil balance valve of the outdoor unit Remove the pressure gauge and vacuum pump After the system power outages, switch the code S5 . After the system is powered on, press…
-
If vacuum level could not get to -0.1MPa, please check whether resulted by leakage and confirm the leakage site. If no leakage, please operate the vacuum pump again 1 or 2 hrs. 11. Additional refrigerant charge Calculate the additional refrigerant charge according to the diameter and the length…
-
Power current: MCA=33.4+33.4+27.9=94.7A
TOCA=32.8+32.8+31.8=97.4A MFA=35+35+35=105A Compressor: RLA=(17.4+10.5)+ (17.4+10.5)+ (17.4+10.5)=83.7A OFM: FLA=5.9+5.9+5.9=17.7A Notes: o o o 1. RLA is based on the following conditions, Indoor temp. 27°C(80.6 F) DB/19°C(66.2 F) WB, Outdoor temp. 35°C(95 F) DB 2. TOCA means the total value of each…
-
Leakage
protector M anual sw itch Outdoor unit GND Outdoor unit GND GND Outdoor unit Branch box GND Outdoor unit Power facilities 1 Outdoor unit GND (with leakage protector) Outdoor unit Leakage protector Manual switch GND Outdoor unit GND Outdoor unit GND Branch box Outdoor unit GND Power facilities 2…
-
12.4 Control system installation
The control line should be shielded wire. Using other wiring shall create signal interference, thus leading to error operation. The shielded nets at the two sides of shielded wires are either grounded to the earth, or connected with each other and jointed to the sheet metal along to the earth.…
-
12.5 Dial switch setting
S1: Starting time setting S1 Starting time is 10 minutes S1 Starting time is 12 minutes (default) S2: Night silent time setting S2 Night silent time is 6h/10h (default) S2 Night silent time is 6h/12h S2 Night silent time is 8h/10h S2 Night silent time is 8h/12h S3: Silent mode selection S3 Night…
-
ENC2: Outdoor unit capacity setting
Only 0, 1, 2, 3, 4 are available. 0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP ENC4: Network address setting Only 0, 1, 2, 3, 4, 5, 6, 7 are available. 13. Running test 13.1 Inspection and confirmation before commissioning Check and confirm that refrigeration pipe line and communication wire of…
-
Outdoor unit
Indoor unit Room full of leaking refrigerant (All the refrigerant has leaked) Calculate the critical thickness through following steps, and take necessary actions. 1. Calculate the refrigerant charge A 2. Total refrigerant charge = delivered refrigerant charge (nameplate) + supplemental…
-
1. Select installation position
1. 2. 3. 4. A place can provide enough installation and maintenance space. Horizontal ceiling and its building construction is able to withstand the set’s weight. A place where the connecting pipes and drain pipes can be connected easily. The installation location should consider the length of the…
-
3. Body installation
3.1 Install the Φ25/64inch(Φ10mm) hoisting screw 1. Please useΦ25/64inch(Φ10mm) hoisting screw. 2. Remove the ceiling: For different architectural structure, details please contact with indoor decoration personnel. Ceiling: For make sure the ceiling level and for avoiding to the ceiling vibration…
-
3.4 Hanging the MS
1. Adjust the nut’s site, the interval between gasket (Down Side) and the ceiling should according to actual construction. 2. 3. Hang the nut of hanging screw bolt into the slotted hole of the installing ear. Use the level gauge to confirm the horizontality of the unit. (Prohibitfalling toward…
-
to connect the drain pipes and the connecting pipes, and use the connecting pipes to fasten the drain pipes. Unit: in.(mm) 6. Central install the drain pipes please follow below diagram to match pipes. As long as possible (about 4(100)) Downside gradient over 1/100 VP30 Unit: in.(mm) 7. The end of…
-
indoor unit
max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max capacity:16kW(54.6kBtu/h) indoor unit max:4 units, max…
-
c)
d) 2. 3. a) R410A All DC Inverter V4 Plus R Series 50/60Hz When connecting or disconnecting the pipe, be sure to use two spanners concurrently. Do not rest the weight of the connective pipe on the adapter of the indoor unit. Too heavy load on the adapter of the indoor unit may deform the pipe and…
-
5.4 Pipe connection
1. Flare Use a pipe cutter to cut off the pipe. 90 Slant Coarse Burr Pull the pipe into the rear flare of the connective nut. A in.(mm) Outer diameter in.(mm) Max. Min. Φ1/4(6.35) 11/32(8.7) 5/16(8.3) Φ3/8(9.53) 1/2(12.4) 15/32(12.0) Φ1/2(12.7) 5/8(15.8) 39/64(15.4) Φ5/8(15.9) 3/4(19.0)…
-
Protect with wet
towel when brazing Pipe connection from outdoor unit Low pressure gas pipe connection(Brazing) High pressure gas pipe connection(Brazing) Liquid pipe connection(Brazing) Pipe connection to intdoor unit Gas pipe(Flare) Liquid pipe(Flare) 5.6 Airtight test The refrigerant pipe after installation and…
-
6.1 Power supply specifications
The power supply cable specifications are as follows. In case power capacity is too low may result in over-heating of piping that would be burned out the unit. Item Model Power supply (V/Ph/Hz) Power switch Capacity Safety (A) fuse (A) Power supply cable Power wire Ground wire MS02/N1-C…
-
Note: 1. The signal wire must use shielding wire. User other wires might cause signal interference and lead to malfunction. 2. All the shielding wires network should be interconnected, and finally connected together to the metal plate grounding. 3. Do not tie up the signal wire together with the…
-
3. Finish spot check operation
6.4 Spot check instruction MS Spot check keys SW1-SW6 are separately corresponded to No.1-6 system No. Content 1 The quantity of downstream indoor units of this MS 2 The operation mode of this MS 3 Subcooling inlet temperature (T1C2) 4 Subcooling outlet temperature (T1C1) 5 Total T2(B) average value…
-
8. Trial running
Use the wired controller to control the operation of the unit, check the following items according to the instruction. If there is error, check the error according to the instruction and solve them. 8.1 Indoor unit 1) Check whether the switch of the wired/remote controller is normal; 2) Check…
-
1. Outdoor electric control box assembly instructions
8/10/12HP Bottom layer of electric control box Top layer of electric control box No. Content 1 Electric control box assembly 2 Three phase bridge 3 Inverter module 4 Outdoor current detection board 5 Outdoor power supply board 6 DC fan module 7 Intermediate adapter board 8 Temperature sensor 9…
-
14/16HP
Bottom layer of electric control box Top layer of electric control box No. Content 1 Electric control box assembly 2 Inverter module 3 Three phase bridge 4 Temperature sensor 5 Outdoor power supply board 6 Outdoor current detection board 7 Outdoor power supply board 8 DC fan module 9 Intermediate…
-
2. Outdoor main control board instructions
2.1 Main PCB ports instructions Troubleshooting 139
-
Outdoor main PCB ports instructions
No. Port code Content Port voltage 1 CN10 Discharge temperature detection port of inverter compressor A DC 0~5V (in dynamic change) 2 CN11 Discharge temperature detection port of inverter compressor B DC 0~5V (in dynamic change) 3 CN4 Inverter module temperature detection port DC 0~5V (in dynamic…
-
Troubleshooting
S7 chip Communication switch Dial S4 S2 ENC4 ENC2 S1 ENC1 ENC3 S12 S3 Dial switch Dial switch Main control chip drive chip Inverter LED digital tube display Spot Check button Forced cooling button MCAC-VTSM-2013-10 R410A All DC Inverter V4 Plus R Series 50/60Hz 2.2 Main PCB parts instructions 141
-
2.2.1 Spot check content instructions
No. Normal display Content (present frequency) Note 1 0-- Outdoor unit address 0, 1, 2, 3 2 1-- Outdoor unit capacity setting Refer to note 1 3 2-- Outdoor unit quantity Available for main outdoor unit 4 3-- Running mode Refer to note 2 5 4-- Total capacity of outdoor units Capacity requirement 6…
-
Note
When the outdoor unit is in standby, the first two numbers on LED digital tube will display the address of the outdoor unit, and the last two numbers display the indoor unit’s quantity which can communicate with outdoor unit. When the outdoor unit is operating, it will display the rotation frequency…
-
Dial switch setting
ENC3+S12: Indoor unit quantity setting ENC3 ENC3 ENC3 ENC3 S12 S12 S12 S12 The quantity of indoor unit is 0-15 The quantity of indoor unit is 16-31 The quantity of indoor unit is 32-47 The quantity of indoor unit is 48-63 ENC1: Outdoor unit address setting Only 0, 1, 2, 3 are available. 0 is for…
-
2.3 LED on main control board instructions
LED3 LED2 LED1 LED5 LED7 LED4 LED6 LED1: Power supply indicator lamp. The lamp will be on if the power supply is normal. LED2: Running indicator lamp. The lamp will be on if the system running is normal. LED3: Malfunction indicator lamp of network centralized control chip. The lamp will flash in…
-
3. Error code table
Error code Content E0 Communication error between outdoor units E1 Phase sequence error Display on the faulty unit, all the ODUs are in standby. Communication error between indoors and the Only display on the master unit, all the ODUs are in master unit. standby. E2 E4 Outdoor ambient temperature…
-
P9
Fan module protection PL Temperature protection of main inverter module L0 Inverter module error Display after P6 displaying for one minute L1 DC generatrix low voltage error Display after P6 displaying for one minute L2 DC generatrix high voltage error Display after P6 displaying for one minute L3…
-
4.2 E1: Phase sequence error
The error only display on faulty unit, all the ODU will be standby. E1: Phase sequence error The 3-phase sequence of power supply is wrong. (The A, B, C terminal of three-phase power supply should meet compressor phase sequence requirement. If the phase sequence is adverse, the compressor will…
-
4.3 E2: Communication error between indoors and the master unit
The error only display on faulty slave unit, all the ODU will be standby. E2: Indoor units and outdoor unit communication error Communication wires P, Q, E are short circuit or disconnected (Measure the resistance among P Q and E, the normal resistance is 120Ω) Yes Reconnect the communication wires…
-
Note
1. Press the manual button on display board of indoor unit for 5 seconds, the communication address code of indoor unit will display; Codes are as follows: Indicator light Running Timer Fan/defend cold fan Warning Code Buzzer Communication address Four LED display Not warning 00---15 Normally on Not…
-
For example
Pressing continued the manual button for 10 seconds: If all the LED lights turn off, that means the capacity code is 0 and the capacity of indoor units is 22×100W(7510Btu/h); If the “Timer” and “Alarm” lights are normally on, that means the capacity code is 5=(4+1) and the capacity of indoor…
-
4.4 E4: Temperature senor (ambient temperature sensor T4, pipe temperature sensor T3/T5)
E7: Discharge temperature sensor error The error only display on faulty unit, all the ODU will be standby. E4/H7: Temperature sensor error Temperature sensor port on main PCB are loose Fasten the temperature sensor port Yes No Temperature sensor is short circuit or disabled (Using a multimeter to…
-
4.5 E5: Voltage error
The error only display on faulty unit, all the ODU will be standby. E5: Voltage error Voltage of power supply is too high or too low (the normal voltage between A and N (B and N, C and N) should be 198V~242V) Yes Provide normal power supply No Check the high voltage circuit. Whether the compressor…
-
4.6 E8: Outdoor unit address is wrong
The error only display on faulty slave unit, all the ODU will be standby. E8: Outdoor unit address is wrong The ODU's address is more than 3 or be set repeatedly Yes The addresses should be set less than 3 and differently Yes Replace or reconnect communication wires No The communication wires H1, H2…
-
4.8 H0: Communication error between main control chip and inverter driver chip
H1: Communication error between main control chip and communication chip The error only display on faulty unit, all the ODU will be standby. H0/H1 Power supply for main transformer is abnormal① PCB and Yes Provide normal power supply No The transformer is damaged② Yes Replace the transformer No…
-
4.9 H2: Quantity of outdoor unit decreased; H3: Quantity of outdoor unit increased
The error only display on master unit, all the ODU will be standby. H2/H3 Yes Communication wire between outdoor units is loosen Fasten the communication wire No Some outdoor units’ addresses (ENC1) are setting repeatedly Yes Set the addresses (ENC1) differently No Some outdoor units in combination…
-
4.10 H7: Quantity of indoor units decrease error
The error only display on master unit, all the ODU will be standby. It will display when the quantity of indoor units decrease above 3 minutes. H7: Quantity of indoor units decrease error Communication terminals P Q E are loose Yes Fasten the communication terminals Yes Set the IDU addresses…
-
4.11 H8: High pressure sensor error
When the discharge pressure is lower than 0.3MPa(43.5PSI), the system will display H8 error, the ODU in standby. When the discharge pressure is back to normal, H8 disappears and normal operation resumes. H8: High pressure sensor error High pressure sensor connection Yes port on main control board is…
-
4.12 XHd: Slave units malfunction (X stands for corresponding slave unit)
XHD is only displayed on master unit. X stands for corresponding slave unit. If X is 1, it means no.1 slave unit has problem, then you should check no.1 slave unit. 4.13 P1: High pressure protection When the pressure is over 4.4MPa, the system will display P1 protection, the ODU in standby. When the…
-
4.14 P2/H5: Low pressure protection
When the pressure is lower than 0.05MPa, the system will display P2 protection, the ODU in standby. When the pressure is higher than 0.15MPa, P2 disappears and resumes normal operation. H5 error will display when system appear 3 times P2 protection in 60 minutes, it cannot resume automatically, and…
-
compressor) P3: When the current of inverter compressor is over12A, the system will display P3 protection, the ODU in standby. When the current goes back to normal range, P3 disappears and normal operation resumes. P3: Compressor current protection Yes The indoor load is too large① Make sure the…
-
4.16 P4: Discharge temperature protection; H6: P4 protection appears three times in 100 minutes
The error only display on faulty unit, all the ODU will be standby. H6 error cannot resume automatically, and it can resume only by restarting the machine. P4/H6 Discharge temp. sensor is short circuit or disabled①. Yes Replace the sensor No System is lack of refrigerant②. (Refrigerant recharging is…
-
4.17 P5: Condenser temperature protection
When condenser temperature is over 65oC(149oF), the system will display P5 protection, the ODU in standby. When the temperature goes back to normal range, P5 disappear and normal operation resumes. P5: Condenser temperature protection Yes T3/T5 port on main control board is loose Fasten the T3/T5…
-
4.18 XP6: Inverter module protection (When X is 1, it means A inverter module; 2 means B inverter
module) H4: P0 protection appears three times in 60 minutes When the system displays H4 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. H4 will display if P6 occur 3 times in 30 minutes Check whether…
-
1) L0 troubleshooting
Step 1: Compressor check Measure the resistance between each two of U, V, W terminals of the compressor, all the resistance should be the same and equal to 0.9~5 Ohms. (Fig. A and Fig. B) Measure the resistance between each of U, V, W terminals of the compressor to ground (Fig. C), all the…
-
2) L1/L4 troubleshooting
Step 1: Check the DC voltage between 1 and 2 terminal, the normal value should be 510V~580V, if the voltage is lower than 510V, go to step 2. 1 2 Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If wires are OK, replace the main PCB. 166…
-
3) L2 troubleshooting
Step 1: Check the DC voltage between 1 and 2 terminal, the normal value should be 510V~580V, if the voltage is higher than 580V, go to step 2. 1 2 Step 2: Check the voltage between the two electrolytic capacitors, the normal value should be 510V~580V. Turn the measure range of the meter to 1kV…
-
Extend the power line of the inverter compressor of system B, connect compressor A to the control box of system B, make sure that the U, V, W terminals are connected in right order, then start system B. If compressor A can start normally, that means compressor is OK, the control box of system A is…
-
black, feculent, or even there is impurity in the oil, that means the system has problems and the oil has gone bad, the oil need to be replaced. The oil is black, it has been carbonized The oil is a little yellowing, but it is clear and transparent, the quality is OK Theoil oilisisstill…
-
The
The crankshaft crankshaft is worn. is A normal bearing of the compressor A clean filter (on the suction pipe of the system) 170 The scroll plate of is worn. the The bearing is worn seriously, it is damaged completely The filter is blocked by impunity, the suction and of the exhaust compressor of the…
-
Step 3: Replace the compressor
Pour out some oil from each compressor (Inv & Fix); check the quality of the oil The oil is clean The oil is dirty Pour out all of the oil from the compressor, oil separator and gas-liquid separator Check the filter between the ball valve and the 4-way valve The filter is clean The filter is blocked…
-
low-pressure accumulator
3. Add oil to the compressor from the discharge pipe. The discharge pipe is connected to the oil pool of the compressor by the inner oil balance pipe, add oil from the discharge pipe with a funnel 4. The type of the oil is FVC-68D, make sure the type of the oil is right because different compressor…
-
If the system display three times P9 protection in 60 minutes, the system will stop and display H9 error code. When the system displays H9 error code, the system can resume only by restarting the machine. At this time, malfunction should be disposed promptly to avoid further damage. P9/H9: Fan…
-
P9 protection analysis
Conditions Fault indicator Power supply Digital lamp of fan indicator lamp tube module of fan module display Malfunction analysis Check the power supply circuit for fan module. Power on Off Off Quantity Check whether there has power supply for lightning of IDU or protection plate, whether the…
-
4.20 PL/C7: Temperature protection of main inverter module
When the temperature of inverter module is over 80oC, it will display PL protection. If the system display three times PL protection in 100 minutes, the system will stop and display C7 error code. When the system displays C7 error code, the system can resume only by restarting the machine. PL/CL…
-
Attached table 1: Resistance value of ambient temperature and pipe temperature sensor
-
Attached table 2: Resistance value of compressor discharge temperature sensor
-
Attached table 3: Commissioning and operating parameters of refrigerant system
Conditions 1: Make sure outdoor unit can detect all the indoor units, the quantity of indoor units display steadily and be equal to actual quantity of installed indoor units. Conditions 2: Make sure all the valves in outdoor unit are open, indoor units EXV have connected to indoor PCB. Conditions 3…