1. Feature
1.1 Compact size 1.1.1 Only 210 mm (22~56 models) or 270mm (71 to 112 model) or 300mm (140 model)in height, this model can be installed in rooms with as little as 240mm~300 mm depth between the drop-ceiling and ceiling slab. 1.1.2 The EXV is built-in design of the indoor unit, makes the main body…
-
1.5.5 Standard built-in drain pump
Drain pump is equipped as standard accessory with 750 mm pump head. Pump 1.6 Flexible control and convenient for maintenance 1.6.1 Standard Wired remote controller KJR-29B1/BK-E, and wireless remote controller RM05/BG(T)E-A is as an option. 1.6.2 The display board is connected with the E-box in…
-
Indoor Unit
Concealed Duct Type (A5 Type) 91
-
2. Specifications
-
Model
-
таблицы и схемы — в просмотре
-
3. Dimension
-
Outline dimension
-
4. Service Spaces
Ensure the needed spaces for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The outlet and the inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The…
-
5. Piping Diagrams
motor fan T2B flare nut EXV T1 gas side T2 heat exchanger flare nut liquid side 98 Indoor Unit
-
6. Wiring Diagrams
Indoor Unit 99
-
7. Fan Performance
How to Read the Diagram The vertical axis is the External Static Pressure (Pa) while the horizontal axis represents theAir Flow (CFM). The characteristic curve for the “H,” “M, ” and “L ” fan speed control. The nameplate values are shown based on the “H ” air flow. Therefore in the case of 22T2Type…
-
P(Pa) P(Pa) MDV-D80(90)T2/N1-BA5 8.0/9.0KW 11.2/14KW High speed High speed Medium speed Medium speed 60 30 Low speed Low speed 1050 1200 1350 1500 1650 1000 1250 1500 1750 2000 2250 2500 2750 Q(CFM) Q(CFM) If the external static pressure is too great (due to long extension of duct, for example)…
-
8. Capacity Tables
-
7.1 8.0 Indoor Unit 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0…
-
11.2 14.0 104 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 42.0 44.0 46.0 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0…
-
5.6 7.1 8.0 106 13.70 -20 -19 -17 -15 -13.00 -11.00 -10.00 -9.10 -7.60 -5.60 -3.70 -0.70 2.20 4.10 6.00 7.90 9.80 11.80 13.70 -20 -19 -17 -15 -13.00 -11.00 -10.00 -9.10 -7.60 -5.60 -3.70 -0.70 2.20 4.10 6.00 7.90 9.80 11.80 13.70 -20 -19 -17 -15 -13.00 -11.00 -10.00 -9.10 -7.60 -5.60 -3.70 -0.70…
-
11.2 14.0 Indoor Unit -9.10 -7.60 -5.60 -3.70 -0.70 2.20 4.10 6.00 7.90 9.80 11.80 13.70 -20 -19 -17 -15 -13.00 -11.00 -10.00 -9.10 -7.60 -5.60 -3.70 -0.70 2.20 4.10 6.00 7.90 9.80 11.80 13.70 -20 -19 -17 -15 -13.00 -11.00 -10.00 -9.10 -7.60 -5.60 -3.70 -0.70 2.20 4.10 6.00 7.90 9.80 11.80 13.70 -20…
-
9.80 11.80 13.70 108 MCAC-VTSM-2013-10 9.00 11.00 13.00 15.00 16 16.4 17.1 17.5 16 16.4 16.7 16.7 15.5 15.5 15.5 15.5 14.3 14.3 14.3 14.3 Indoor Unit
-
9. Electrical Characteristics
-
10. Sound Levels
-
Sound pressure level dB(0dB=0.0002μ bar) Sound pressure level dB(0dB=0.0002μ bar) MDV-D45(56)T2/N1-BA5 A udibility limits of continuous w hite sound Audibility limits of continuous white sound Octave band center frequency (Hz) Octave band center frequency ( Hz ) MDV-D112T2/N1-BA5 Sound pressure…
-
11. Accessories
11.1 Standard accessories Name Quantity Shape Usage Installation manual 1 / / Pipe insulation material 2 Heat insulation Adhesive tape for seal 2 To connect drain pipe Wired controller 1 / Network matching wire 1 The indoor unit witch at the terminal of communication system should connect a…